6.3 Alarm display – causes of errors
Current list
4.5 Current list
Alarm 02
Alarm 01
2009-02-10
2009-02-10
Alarm 03
2009-02-10 18:22:50
Alarm 04
12012
2009-02-10 18:25:00
Alarm 05 13071
2009-02-10 19:00:00
01144
10:54:17
02144
11:01:12
03073
Alarm code
If an alarm has been generated, an alarm code is shown in the display in the for-
mat XXYYZ, where .
XX = unit
YY = fault code
Z = category of alarm. See category table in this section.
16 alarms
There can be up to 16 alarms on the "Current list". The first alarm to be added to
the queue will be the first alarm to be removed, if there are more than 16 alarms
(FIFO principle).
Info in EXact
shown only in the alarm log list Menu 4.6
Example - list of
alarms
36024 is an alarm on EC controller 1 (
36
024). The alarm description is
"The sup-
ply voltage to the EC controller is too low"
(36
02
4). The category is critical
(3602
4
).
Any active alarm is shown under the alarm symbol. If there is more than one
alarm, each individual alarm is shown for two seconds on a rotation basis.
Category
Category
(Z)
Alarm level Effect on operation
Icon
1
Info
Operation continues
2
Warning
Operation continues
3
Alarm
Operation continues but with reduced
functionality
4
Critical
Operation stops
5
Fire
Triggered fire alarm procedure mode
starts
Find troubleshooting directions in the list of alarms via the alarm number.
Alarm log list -
Menu 4.6
Note: It takes 19 seconds for the list to appear.
3006401-2022-05-04
Alarms