EXHAUSTO Ltd.

Unit 3,Lancaster Court
Coronation Road
Cressex Business Park
GB-High Wycombe -HP12 3TD

Tel. 01494 465166
Fax 01494 465163
[email protected]
www.exhausto.co.uk

3001776 - 07.2005  Right to modification is reserved

Height (mm)

85

Width (mm)

126

Depth (mm)

32

Fuse rating (amps) (A)

3.15 A T

Fail safe (B)

 

Pressure differential switch (PDS)

24V DC

 

(Closed circuit supply)

Output to chimney fan (C)

1.8A / 230V (AC 3)

Output to soleniod valve (SMG) (D) 230V AC max. 100 VA

Dipswitch options (E)

• Manual reset
• After ventilation 3 min. period

Set-point running speed (F)

Potentiometer on PCB

Supply (G)

230V +/- 10%, 50 Hz

Input for external on/off switch (H) 24V DC

 

(Closed circuit supply)

Release out Relay (I)

Max. 3A 230V AC / 3A 

30V DC (Fused: 3.15AT)

Operating temperature

-10°C to 40°C

Degree of protection

IP 30

Material

ABS

Colour

White

CE-Approval No.

0063BN1144 based on 

EN298 (1993)

Description

EXHAUSTO controller EFC21 has been developed for use with 
gas fireplaces where an EXHAUSTO chimney fan 
or wall fan is installed.
The control system supervises the fail-safe function. In case of 
insufficient chimney draught, the EFC21 will shut off the gas 
supply.
The control system is developed to meet BS 5440: 
Part 1 (2000), BS 6644 (1991), Gas Appliance Directive 90/396/
EEC, EN298 (1993) and other relevant European  standards.

Function

By activating EFC21 the chimney fan will immediately start up 
on full speed. When the fail-safe supervision  confirms suffi-
cient chimney draught, the fireplace can be lit and the fan 
speed will adjust to the pre-set value  set during commissio-
ning.
The controller has a step-up function and a 15-second built-in 
delay function to avoid nuisance cut-outs. When EFC21 is 
turned off, the chimney fan stops. 
It is possible to pre-set an after-ventilation period of 
3 minutes.

EFC21 - Product Information 

EXHAUSTO controls are supplied with a 2 year warranty. EXHAUSTO is  certified  according to ISO 9001.

1

2

3

The system consists of

:  

1. Chimney fan
2. Controller EFC21
3. Solenoid valve SMG

EFC21 - Technical Data

The step-up function is part of the fail-safe system.  Should the 
draught fail during normal operating conditions: the controller 
will increase the fan speed to compensate.  This usually occurs 
on days that are windier than the commissioning day.  If 
sufficient draught cannot be re-established, then the EFC21 
will shut off the gas supply.