OVER TEMPERATURE PROTECTION:

OVERPOWER, SHORT CIRCUIT PROTECTION:

The inverter is also

protected against overheating. It will provide its full rated output up
to the temperature listed in the specification sheet. If it is subjected
to higher ambient temperatures or air circulation is blocked, the
inverter may overheat. If the LOWBATT/THERM buzzer sounds,
immediate action is required or the inverter will shut down. Either
reduce load, or provide more cooling in the immediate environment.
If no action is taken, the inverter will likely shut down within 2
minutes. When the inverter shuts down, the alarm condition will
persist and the cooling fan will continue to run. Since the inverter
has eliminated its load, it will cool fairly quickly. It will automatically
restart when it has cooled sufficiently, and the LOW BATT/THERM
alarm will clear. “105 C internal temperature. Warning buzz 5 C
before shut off”.

Exeltech 2kw

C

°

°

o

.

.

The inverter has

three levels of overpower protection. The first

limits peak

instantaneous current. The second system limits absolute power
coming from the module. Both of these circuits act to reduce output
voltage as required, to limit current to a safe level. The overpower
protection circuit will recover instantly if the overpower condition
clears within 3-5 seconds. The third, is short circuit protection. If the
over current condition is so severe that it causes output voltage to
collapse for more than 5 seconds, the inverter will shut down and
not automatically restart. The LED will flash red and the fan will be
on. This requires the user to clear the short circuit safely, and
guarantee that hazardous voltage will not come back on line until
desired. To reset the inverter from this condition, cycle power switch
“OFF” then “ON” again.

inverters will provide peak current (45 A at 117VAC or

22A at 230VAC) or maximum surge (4000W) for 3 seconds when
the inverter

s internal temperature is at or below 30

. The output

power is then reduced to 2000W (rated power) for 4 secs.

If the

inverter cannot restore a full sine wave due to overload, the LED will
be red.

If the overload condition does not clear in the 7 secs.

Page 7

MCX/ICX INSTALLATION AND OPERATION MANUAL

Summary of Contents for ICX

Page 1: ...MCX ICX INSTALLATION AND OPERATION MANUAL ...

Page 2: ... be copied photocopied reproduced translated or converted to any electronic or machine readable form in whole or in part without prior written approval of Exeltech Inc Exeltech Inc 7317 Jack Newell Blvd North Fort Worth Texas 76118 7100 MCX ICX INSTALLATION AND OPERATION MANUAL ...

Page 3: ...oduction 1 0 Standard Features 2 0 Installation Operation 0 Appendix A Appendix B 3 Appendix C page 3 page 5 page 8 page 12 page 13 page 14 Table of Contents Page 2 MCX ICX INSTALLATION AND OPERATION MANUAL ...

Page 4: ... of products XP series inverters provide the cleanest best regulated sine wave output over the widest DC input of any inverter on the market today They are extremely low in Total Distortion specified to 2 and typically better than 1 5 Total Harmonic Distortion is typically 0 8 to 0 9 Remaining distortion is a result of residual switching noise which amounts to a very clean 25 kHz sine wave superim...

Page 5: ...e the power factor must also be specified Exeltech s inverters can output their full rated power continuously at 30 C 86 F The inverter will maintain a spectrally pure output with any load due to a specially designed non linear control loop in the primary DC to DC converter This circuitry is one of three circuits which protect the inverter from any overload condition EXELTECH 2KW INVERTERS These i...

Page 6: ...output as well as the charger s input which means that there will always be AC present on these outlets as well as the LOAD connections on the backplane The AC will come from the primary source when present and from the inverter when the primary source is not present DC INPUTS REMOTE ON OFF AC OUTPUTS Standard Features 2 0 supply it s peak current to the load for 3 seconds then it will scale back ...

Page 7: ...he battery voltage exceeds set limits the inverter charger will immediately and without warning shut off This will require the user to cycle the on off switch to turn the inverter back on This fault can usually be attributed to a poor battery connection or faulty battery When battery voltage falls to within 5 of low line voltage the LOW BAT THERM buzzer will sound If the condition continues withou...

Page 8: ...s peak instantaneous current The second system limits absolute power coming from the module Both of these circuits act to reduce output voltage as required to limit current to a safe level The overpower protection circuit will recover instantly if the overpower condition clears within 3 5 seconds The third is short circuit protection If the over current condition is so severe that it causes output...

Page 9: ...allowed the inverter shuts off flashing red indicator LED will be red in overload and or short circuit conditions Page 8 MCX ICX INSTALLATION AND OPERATION MANUAL ...

Page 10: ...nal first When reconnecting connect ungrounded terminal first and grounded terminal last Polarity of leads is critical to avoid damage to the unit or system Check batteries and battery cables for correct polarity and voltage Observe all National and Local Electric Codes when connecting AC Power Connections The AC neutral lead is bonded to chassis through the barrier terminal strip connector locate...

Page 11: ... wire has less resistance which translates to increased efficiencies An in line fuse is recommended to protect the battery and wiring to the inverter This fuse should be located very close to the battery positive terminal To select appropriate size fuse consult the Rated and Peak Current table in appendix A Disconnect the charger and inverter are off Make DC input connections to the inverter as il...

Page 12: ...ss than Rated Output Power of the inverter If more than one appliance will be run simultaneously the sum of their Input Power Requirements must be less than Rated Output Power of the inverter If using REMOTE switch the Front Panel Switch must be off If Appliance Load has been hard wired to the barrier terminal strip as illustrated in Appendix C then turn appliance on Otherwise plug the appliance i...

Page 13: ... at Low line Input voltage and Rated Output Power LESS THAN 15 Recommended Input Wire Sizes For Variable Distances from the Battery LESS THAN 10 LESS THAN 5 MODEL MCX ICX 12VDC MCX ICX 24VDC MCX ICX 48VDC MCX ICX 66VDC MCX ICX 108VDC 2 0 AWG 4 AWG 8 AWG 12 AWG 16 AWG 3 0 AWG 0 AWG 6 AWG 8 AWG 12 AWG 250mcm AWG 2 0 AWG 4 AWG 6 AWG 12 AWG 3 0 AWG 0 AWG 4 AWG 10 AWG 250mcm AWG Page 12 MCX ICX INSTALL...

Page 14: ... 017 9 417 266 R 133 3 4 KNOCK OUT MCX ICX Rear View with access cover removed AC DC Connections BAT BAT FROM UTILITY TO LOAD UTILITY LINE UTILITY NEUTRAL GROUND LINE NEUTRAL GROUND REMOTE BATTERY TEMPERATURE SENSOR MCX ICX INSTALLATION AND OPERATION MANUAL Page 13 ...

Page 15: ... Be sure to disconnect batteries and chargers Make all connections to the inverter connecting DC leads to the battery BEFORE Negative Ground Battery Inverter Appropriately rated fuse Positive Ground Battery Inverter Appropriately rated fuse Page 14 MCX ICX INSTALLATION AND OPERATION MANUAL ...

Page 16: ...e without notice 931 XICM 0B Made in the USA 7317 Jack Newell Blvd North Fort Worth Texas 76118 7100 817 595 4969 voice 817 595 1290 fax 800 886 4683 toll free website www exeltech com MCX ICX INSTALLATION AND OPERATION MANUAL ...

Reviews: