Excelsys XS1000-24 Manual Download Page 3

INPUT

Parameter

Conditions/Decription

Min

Nom

Max

Units

Input Voltage Range

Universal Input 47-440Hz

85

264

VAC 

120

380

VDC 

Power Rating

XS500

504

W

XS1000

1008

W

Input Current

XS500

5

A

XS1000

10 

A

Inrush Current

230VAC @ 25°C

25

Undervoltage Lockout

Shutdown

65

74

VAC

Fusing            

XS500 250VAC

F8A HRC

XS1000 250VAC

F12A HRC        

OUTPUT

Parameter

Conditions/Description

Min

Nom

Max

Units

Output Voltage Range                    

XS500/1000-24: Multi-turn potentiometer

19

28

VDC

XS500/1000-24: Dynamic Vtrim range

14

28

VDC

XS500/1000-36: Multi-turn potentiometer

26

40                 VDC

XS500/1000-36: Dynamic Vtrim range

20 

40                 VDC

XS500/1000-48: Multi-turn potentiometer                                                  36

58

VDC

XS500/1000-48: Dynamic Vtrim range

29

58

VDC

Output Current Range

XS500-24

21

A

XS1000-24

42

A

XS500-36                       

14

A   

XS1000-36                                                                    

28           

A

XS500-48  

10.5

A

XS1000-48    

21

A

Load & Cross Regulation

For 25% to 75% load change 

±0.2

%

ORing Option

±0.4

%

Transient Response

For 25% to 75% load change Voltage Deviation

2.5

Settling Time     

500                µs          

Ripple and Noise

XS500/1000-24: 20MHz 

240

mV pk-pk

XS500/1000-36: 20MHz 

360                              

mV pk-pk

XS500/1000-48: 20MHz 

480

mV pk-pk

Overvoltage Protection

XS500/1000-24

Latching

33

34

37

VDC

XS500/1000-36

Latching

44

47            

52                  VDC

XS500/1000-48: Latching                                                                   

61           

63           

69

VDC                     

Overcurrent Protection

Straight line with hiccup activation at <30% of Vnom. 

105

115

130

%

Line Regulation

For ±10% change from nominal line

±0.5

Remote Sense

0.5

VDC

Overshoot

2

%

Rise Time

Monotonic  

3

5

ms

Turn-on Delay

From AC in  

500           

800

ms

From Remote On/Off

10

ms

Hold-up Time

For nominal output voltages at full load.  

17

ms

GENERAL

Parameter

Conditions/Description

Min

Nom

Max

Units

Isolation Voltage

Input to Output

4000

VAC 

Input to Chassis

1500

VAC

Output to Chassis

1500

VAC

Efficiency

230VAC, 1008W @ 24V/36V/48V

>92

%

Safety Agency Approvals

EN60601-1 2nd and 3rd Edition, cTUVus 60601-1
EN60950 2nd Edition, cTUVus 60950

Leakage Current

264VAC, 60Hz, 25°C 

300

µA

264VAC, 60Hz, 25°C (Option 4)

150

µA

Signals

See Page 3  

Bias Supply

Always on, current 300mA, 50mA XS500

12.0

VDC

Weight 

XS500

1.1

Kg

XS1000

1.3

Kg

MTBF

Telecordia SR-332, 40°C ground benign, parts count.                                                  

550,000

Hours

EMC

Parameter

Standard

Level

Units

Emissions

Conducted

EN55011, EN55022, FCC

Class B

Radiated

EN55011, EN55022, FCC

Class B

Harmonic Distortion 

EN61000-3-2 Class A 

Compliant

Flicker & Fluctuation 

EN61000-3-3 

Compliant

Immunity

Electrostatic Discharge

EN61000-4-2 

Level 2

Radiated Immunity 

EN61000-4-3 

Level 3

Fast Transients-Burst

EN61000-4-4 

Level 3

Input Line Surges

EN61000-4-5 

Level 3

Conducted Immunity 

EN61000-4-6 

Level 3

Voltage Dips

EN61000-4-11, SEMI F47 Compliant.

(1)

Compliant

ENVIRONMENTAL 

Parameter

Conditions/Description

Min

Nom

Max

Units

Operating Temperature

-40

+70

°C

Storage Temperature

-40

+85

°C

Derating

See Page 62 for full temperature deratings

Relative Humidity

Non-condensing

5

95

%RH

Shock and Vibration

Designed to meet MIL810G 

(2)

55

G

Altitude  

EN60601-1 Operational: 3000m, Storage 8000m

3000

m

EN60950    Operational: 5000m, Storage 8000m

5000

m

Single Output Power Supply 

500W - 1000W

Xsolo

2

www.excelsys.com

Summary of Contents for XS1000-24

Page 1: ...Solo Designer Manual...

Page 2: ...24V 36V or 48V IEC60950 2nd Edition IEC60601 1 2nd 3rd Edition IEC60601 1 2 4th Edition EMC compliant Ultra high efficiency 92 Low profile 1U height 40mm Convection Cooled 500W Fan Cooled 1000W variab...

Page 3: ...5 ms Turn on Delay From AC in 500 800 ms From Remote On Off 10 ms Hold up Time For nominal output voltages at full load 17 ms GENERAL Parameter Conditions Description Min Nom Max Units Isolation Volta...

Page 4: ...d to meet MIL810G and is also compliant with SEMI F47 for voltage dips and interruptions as well as being compliant with all relevant EMC emission and immunity standards Optional features include I2C...

Page 5: ...our website http www excelsys com technical support XS500 24 and XS1000 24 By applying a control voltage Vcontrol between J5 Pin 9 Vtrim and J5 Pin 10 Sense the output voltage of XS1000 24 and XS500 2...

Page 6: ...Pin 1 negative The delay from Inhibit to output turning OFF is typically 1ms Maximum current source allowed is 6 5mA Maximum applied voltage allowed is 13V Fan Fail Fan Fail is an Open collector signa...

Page 7: ...ote sensing may be implemented by connecting the Positive Sense pin J5 pin 11 to the positive side of the remote load and the Negative Sense pin J5 pin 10 to the negative side of the remote load The m...

Page 8: ...r W Section 6 6 Options Environmental Conformal Coating Option C Xsolo is available with conformal coating for harsh environ ments and MIL COTs applications It is IP50 rated against dust and protected...

Page 9: ...ic measuring equipment and process control UltiMod Xsolo and Xgen models are certified to comply with the requirements of IEC950 EN60950 UL60950 1st and 2nd Editions and CSA 22 2 no 234 and IEC1010 wh...

Page 10: ...eet the requirements of the limits on voltage fluctuations and flicker in low voltage sup ply systems EN55022 Class B Conducted Emissions For system compliance to EN55022 Level B additional filtering...