Ex-baltic BA444DF-P PROFIBUS PA Instructions Manual Download Page 3

3

1.  DESCRIPTION
The 

BA444DF-P 

fieldbus 

indicator 

is 

an

intrinsically  safe,  PROFIBUS  PA  instrument,  that
may  be  configured  as  a  fieldbus  node  or  as  a
fieldbus listener.  It can  display up to  eight fieldbus
process  variables  on  a  five  digit  LCD  and  a  31
segment  analogue  bargraph.      The  instrument  is
bus  powered  so  no  additional  power  supply  is
required 

and 

has 

PROFIBUS 

PA 

User

Organisation approval, certificate Z01505.

Fieldbus  node  configuration  may  be  performed  by
either  a  User  PRM  data  download  or  by  a  DPV1
configurator,  and  if  required,  the  instrument
address  may  be  entered  via  the  front  panel  push
buttons.

When  configured  as  a  fieldbus  listener,  the
BA444DF-P  is  not  visible  to  the  fieldbus  host  and
can  only  be  configured  using  the  push  buttons  on
the front of the instrument.

Housed in a robust IP66 glass reinforced polyester
(GRP)  enclosure  with  a  toughened  glass  window,
the  BA444DF-P  is  surface  mounting,  or  may  be
pipe mounted using one of the accessory kits.

The  instrument  is  intrinsically  safe  and  has  been
certified  by  European  Notified  Body  Intertek
Testing  and  Certification  Ltd  (ITS)  to  the  ATEX
Directive  94/9/EC  for  use  in  explosive  gas  and
combustible  dust  atmospheres.      ATEX  dust
certification is an option – see Appendix 1.

For  use  in  the  USA  and  Canada,  the  BA444DF-P
is  available  with  intrinsic  safety  and  nonincendive
FM and cFM Approval – see Appendix 2.

For  international  applications,  all  versions  of  the
BA444DF-P  PROFIBUS  PA  indicator  have  IECEx
intrinsic  safety  approval  allowing  installation  in
explosive  gas  atmospheres.      IECEx  dust
certification  is  available  as  an  option  –  see
Appendix 3.

The instrument’s communication protocol is shown
on a label inside the terminal cover.  The ‘-P’ order
code  suffix  also  indicates  the  protocol  but  is  not
shown  on  the  instrument  certification  label.
There  is  an  alternative  version  of  the  fieldbus
display,  order  code  BA444DF-F  for  use  on
FOUNDATION™ fieldbus networks.

1.1  Documentation
This  instruction  manual  describes  ATEX  system
design  and  installation  of  the  BA444DF-P
PROFIBUS PA indicator.

System design information for non-ATEX and  dust
approvals is shown in appendices to this manual.

2.  OPERATION
The  BA444DF-P  indicator  can  display  up  to  eight
pre-configured  PROFIBUS  PA  process  variables
designated  in-1  to  in-8.      The  operator  can  select
which  variable  is  displayed  using  the 

and 

push  buttons  which  scroll  the  display  through  the
eight  inputs.      A  numeric  annunciator  on  the  left
hand  side  of  the  display  shows  which  of  the  eight
inputs is currently being displayed.

2.1  Error messages

‘no ConF’

No inputs have been
configured or are enabled.

‘no dAtA’

No data is being received
with the current configuration.

3.  INTRINSIC SAFETY CERTIFICATION

3.1 ATEX certificate
The BA444DF-P has been issued with an EC-Type
Examination  Certificate  by  Notified  Body  Intertek
Testing  and  Certification  Ltd  (ITS)  confirming
compliance  with  the  European  ATEX  Directive
94/9/EC 

for 

Group 

II, 

Category 

gas

atmospheres,  Ga  Ex  ia  IIC  T4  and  for  dust
atmospheres  Ex  iaD  20  T100ºC  IP66.  The
BA444DF-P  is  also  FISCO  compliant.    The
instrument bears the Community Mark and, subject
to  local  codes  of  practice,  may  be  installed  in  any
of  the  European  Economic  Area  (EEA)  member
countries.    ATEX  certificates  are  also  acceptable
for installations in Switzerland.

This  manual  describes  ATEX  installations  in
explosive  gas  atmospheres  which  conform  with
EN  60079:Part  14    Electrical    Installation    in
Hazardous  Areas.    When  designing  systems  for
installation  outside  the  UK,  the  local  Code  of
Practice should be consulted.

For  use  in  the  presence  of  combustible  dust,
please  refer  to  Appendix  1  that  describes  ATEX
installations complying with EN 61241: Part 14.

Summary of Contents for BA444DF-P PROFIBUS PA

Page 1: ...Issue 2 23 rd June 2011 BA444DF P PROFIBUS PA Intrinsically safe Field mounting 8 variable Fieldbus Indicator Issue 2 ...

Page 2: ...meters 6 4 3 Enter address display parameters 6 4 4 Enable selected input 6 4 5 Enter source address 6 4 6 Enter destination address 6 4 7 Enter Index 6 4 8 Decimal point position 6 4 9 Configuration of bargraph 6 4 10 Scale numeric display 6 4 11 Access code for listener configuration menu 6 4 12 Change from fieldbus listener to fieldbus node 6 4 13 Reset to listener factory defaults 7 Maintenanc...

Page 3: ...he protocol but is not shown on the instrument certification label There is an alternative version of the fieldbus display order code BA444DF F for use on FOUNDATION fieldbus networks 1 1 Documentation This instruction manual describes ATEX system design and installation of the BA444DF P PROFIBUS PA indicator System design information for non ATEX and dust approvals is shown in appendices to this ...

Page 4: ...sed comply with the Fieldbus Intrinsically Safe Concept FISCO defined in IEC 60079 Part 27 and also have separate entity parameters as shown below FISCO Entity Ui 17 5V dc 22 0V dc Ii 380mA dc 250mA dc Pi 5 32W 1 2W The maximum equivalent capacitance and inductance at terminals 1 2 is Ci 0nF Li 8µH 3 4 Certification Label Information The certification information label is fitted in a recess on the...

Page 5: ...erminals and the two mounting holes are located in a separate compartment with a sealed cover allowing the instrument to be installed without exposing the display assembly The BA444DF P earth terminal is connected to the carbon loaded GRP enclosure If this enclosure is not bolted to a post or structure connected to the plant potential equalising network the instrument s earth terminal should be co...

Page 6: ...s obtained by operating the P and E buttons simultaneously If the BA444DF P is not protected by an access code the first parameter Addr will be displayed If the instrument is protected by an access code CodE will be displayed first Pressing P will allow the four digit security code to be entered digit by digit using the or button to adjust the flashing digit and P to move control to the next digit...

Page 7: ...ss the P button to move control to the next digit which should be set to u When the four letters of 5urE have been entered operating the E button will cause the instrument to restart as a fieldbus listener in the display mode CAUTION All the instrument s node configuration information will be lost when it is changed from a fieldbus node to a fieldbus listener Please refer to the quick set up proce...

Page 8: ...iew the value of the data at the selected addresses with a zero index i e the first five bytes in the data string If the format of the data is not DS 33 status float no dAt will be displayed The selected source and destination addresses may be allocated to one of the eight BA444DF P listener inputs in 1 to in 8 Operating the P button will reveal the current listener input which may be changed usin...

Page 9: ...9 ...

Page 10: ...meters Sub menu which allows known fieldbus device addresses to be entered and all display parameters adjusted for each of the eight fieldbus listener inputs See section 6 4 3 Enb Enable selected input Enables each of the eight listener inputs in 1 to in 8 to be enabled or disabled without affecting any parameters See section 6 4 4 SrC Enter Source Address Allows hexadecimal fieldbus device source...

Page 11: ... source address to the selected input and return the display to the source and destination addresses from which another data source address may be selected When a data source address is allocated to a listener input any previous allocation will be overwritten If the required process variable has an index above 5 i e it is not the first five bytes in the data string the required index should be ent...

Page 12: ...ay mode irrespective of the numeric value When positioned as required operating the E button will enter the selection and return to the dP prompt in the edit sub menu 6 4 9 Configuration of bargraph display bAr This function contains three sub functions that enable the bargraph justify its position and define the relationship between the bargraph and the instrument s numeric display Sub function b...

Page 13: ...revised access code will be activated when the transmitter is returned to the display mode If the access code is lost please contact BEKA associates 6 4 12 Change from fieldbus listener to fieldbus node tYPE This function enables the BA444DF P to be conditioned as a fieldbus node or as a fieldbus listener To change the function of the instrument select tYPE in the listener configuration menu using...

Page 14: ...l number followed by the firmware version will be displayed prior to entering the display mode 7 2 Fault finding after commissioning ENSURE PLANT SAFETY BEFORE STARTING MAINTENANCE Live maintenance is permitted on intrinsically safe equipment installed in a hazardous area but only certified test equipment should be used unless a gas clearance certificate is available If a BA444DF P fails after it ...

Page 15: ... new pre printed self adhesive escutcheon ensure that the gasket is correctly positioned before reassembling the instrument enclosure 8 2 Tag plate The BA444DF P can be supplied with a blank or custom laser marked stainless steel plate secured by two screws to the front of the instrument enclosure This plate can accommodate 1 row of 9 alphanumeric characters 10mm high or 1 row of 11 alphanumeric c...

Page 16: ...1 explosive atmosphere in the form of a cloud of combustible dust in air is likely to occur occasionally in normal operation Zone 22 explosive atmosphere in the form of a cloud of combustible dust in air is not likely to occur in normal operation but if it does occur will only persist for a short period Be used with dusts having a Minimum Ignition Temperature of Dust cloud 150 o C Dust layer on BA...

Page 17: ...t comply with the Canadian Electrical Code C22 2 and with BEKA associates Control Drawing CI410 12 which is attached to this Appendix The FM and cFM entity parameters are identical to the ATEX parameters and like the ATEX certification confirm that the BA444DF P complies with the FISCO Field Device requirements specified in IEC60079 27 The intrinsically safe system shown in Fig 1 of this manual ma...

Page 18: ...18 ...

Page 19: ...19 ...

Page 20: ...20 ...

Page 21: ...21 ...

Page 22: ...22 ...

Page 23: ...23 ...

Page 24: ...24 ...

Page 25: ...ety parameters and installation requirements The ATEX system design requirements described in section 5 of this manual may therefore be used for IECEx installations in gas atmospheres but the local code of practice should also be consulted A3 2 IECEx Certificate of Conformity Use in presence of combustible dusts In addition to IECEx certification permitting installation in explosive gas atmosphere...

Page 26: ... downloaded from www beka co uk www iecex com or requested from the BEKA sales office A3 3 Versions of the BA444DF All versions of the BA444DF P PROFIBUS PA Indicator have IECEx certification This includes ATEX version for use in gas atmospheres IECEx code Ex ia IIC T4 Ga FISCO Field Device Ex ia IIC T4 Ta 40ºC to 70º o C ATEX version for use in gas and dust atmospheres IECEx code Ex ia IIC T4 Ga ...