4.5.2. Energy Demand Points (Extension Cards)
Each Extension Card requires a certain amount of
Energy Demand Points
.
The energy demand points per Extension Card type are specified in this guide. Values are
given in the table of
#B. Flexy Extension Cards |outline
Examples are given below:
2 Serial Ports
FLA 3301
Single Ethernet
FLX 3101
3G GSM
FLB 3202
Energy Demand Points
1
1
10
Table of the Energy Demand Points for 3 types of Extension Cards
4.5.3. Power Balance Check Example
Considering the configuration shown in the second picture of §
Energy Points
(max 50°C)
Energy Points
(max 70°C)
Available Energy
Base Unit
Flexy 201
29
20
Energy Demand 2
Serial Ports Extension
FLA 3301
-1
-1
Energy Demand Single
Ethernet Extension
FLX 3101
-1
-1
Energy Demand
3G GSM Extension
FLB 3202
-10
-10
Energy Balance
17 > 0 = OK
8 > 0 = OK
Page 27 / 40