About Failure

Failure

No display when power 

is on.

Displayed temperature is

unstable or there exists 

misplay..

Cooler works with 
overfrequency

EI

 is displayed

The sensor wiring is short circuit or open circuit.

Check to see if the sensor wiring has good contact 
with coupling end or not.

Check to see if the power is short circuit.

The thermostat fails.

The set temperature is higher than the present
 temperature.
The heat protector is open circuit because the 
 pressure is over loads.

The sensor wiring is interfered, poorly contacted or

is tied with other cables. The current is light because 

of damage  in the wiring.

The locations for the sensors are not correct or 
sensor wiring is too long and its resistance is too 
big. The wiring contact is poor and the sensor`s 
damag.

The sensor is not correctly installed and cannot
 measure the correct temperature. Compressor 
contactor fails.

Return difference value is too small or the 

setting for pressure protection is not correct.

Check power supply and change fuse.

Check if there is 220V power input or change 

 thermostat with our distributor.

Reset the necessary controlling temperature.
Check the reasons for overload and overheating. 
 After the trouble is solved, restart to work.

Separate sensor wiring with power cables or change 

shielded lines or check if the contact is tight or not.

All sensors should be corrected at their locations. 

Enlarge the cross section of the expanded wires. 

Make sure the wiring sealing, is good. Change sensor.

Check if the sensor has accurately measured the temperature 

or not. Change compressor contactor.

Reset and enlarge return difference value. Adjust
setting for pressure protection.

Causes

Precautions

Difference with temperat-
ure within storage and the
displayed temperature is
too big.

Machine does not stop 
when the temperature
reaches.

Machine does not work 

but display exits

Demand of install

Press        until NO.1 light flashes.

Then press         gently and NO.2

light flashes. Press        or       for

resetting operation value.

Press         gently, NO.2 and NO.3

lights will flash setting temperature.

Press        until NO.1 light flashes.

Then press        or        for resetting

temperature.

Press         until NO.1 light flashes.

Then press         gently for two times

and NO.3 light flashes. Press        or

       for resetting retum temperature

value.

Press         until NO.1 light flashes. Then 
press         gen-tly for three times and 
NO.4 light flashes. Press               
       Or       for resetting operation value.

Press         and        simultan-eously 
until four lights flash. Press       or         
to make adjustment.

Simultaneously press        or      and 
the back temperature can be viewed.

Press         until       flashes and the 
factory default setting will be 
resumed.

Press      and      at the same time, and 
Light 1 & 4 will twinkle. Then press             
         or        To start regulation. .

Setting Temperature

Temperature for Defrosting

Defrosting Withdrawal

Return Temperature

Delayed Time

EW-983A

EW-983A

EW-983A

EW-983A

EW-983A

Temperature Correction

Default Setting

Back Temperature

Defrost

EW-983A

EW-983A

EW-983A

EW-983A

Warnings

1. Please read this product instruction carefully and connect input/output 

plugs of power & sensor to the  corresponding sockets strictly by following 

connection diagram, otherwise the usage & operations will   be affected. 

Check again to make sure there is no mistake. Tighten all the screw of 

connection plugs again, and then connect it to the power for running.

2. Keep away this product from moist or corrosive air and high magnetic 

field. Otherwise the normal  operation of this product will be affected.
.

3. All our products have passed strict quality inspections before leaving 

factory. We provide one-year quality guarantee (which is limited to product 

itself ,and is not responsible for any other joint and several liability) period 

for this product.

    If you have any doubt or problem concerning the electronic 

temperature or humidity controller made by us, please contact 

our distributors and we will provide you high-quality after-

sale services. Thanks!

Guangzhou Eliweli Autocontrol Tech. Co., Ltd.

 

       

   If the products including but not limited to, the following is not the 

product itself quality problem caused by the damage, Install and use 

under the do not conform to the safe environment; That the load capacity 

is beyond the scope of product is allowed; Products by users to 

disassemble and change, change the internal components, etc.,We will 

not be so and damaged products provide a replacement and maintenance 

services, regardless of whether its in the quality assurance period; 

Meanwhile, we will not assume so direct or indirect losses caused by the 

liability to pay compensation.
        Product warranty date on the case is important basis of product 

quality assurance. Appeared including but not limited to full filling 

without permission, to change, to replace lost, damaged, scratched, dirty, 

and so on, we will not provide a replacement and maintenance services 

for these products.

http://www.eliweli.com

Reviews: