STEP 2: Place the system 
into worst case scenario. 

(Smallest zone calling, all other 
zones closed).

Force the bypass damper to
The full open position & open 
the hand damper as well.

Start closing the bypass hand 
damper until the Delta P 
value matches the target 
value obtained in Step #1. 
When finished, lock it down 
and place the system back to 
normal operation.

STEP 1: Place the system 
into single zone scenario. 

(All zones are calling and the 
bypass is closed).

 

If 

necessary, use the hand 
damper to close-off the 
bypass completely.

Observe the Total ESP 
value at the bottom of the 
Manometer or do the math 
yourself. Record the value. 
That value is now the target 

P1 = 0.21
P2 = -0.30
0.21 - (-0.30) =

 0.51”wc

   Example values 
Your values will vary

   Example values 
Your values will vary

CONTROLS  INC.

Excellence Without Compromise

EW

C

CONTROLS  INC.

Excellence Without Compromise

EW

C

P1 = 0.16
P2 = -0.35
0.16 - (-0.35) = 

0.51”wc

   Example values 
Your values will vary

Adjust this damper
towards closed
until the Delta P
(ESP) value 
matches Step 1.

 Force Open
during Step 2
        only