EWC Controls ULTRA-ZONE HK2000 Technical Bulletin Download Page 10

T R O U B L E S H O O T I   N  G

EWC Controls Inc.   385 Highway 33    Englishtown, NJ 07726   800-446-3110   FAX 732-446-5362      E-Mail- [email protected]

10

REFER TO THE DAMPER MOTOR TROUBLESHOOTING SECTION ON PAGE 7.

SYMPTOM

______________________________

LED’S are responding properly but 

HVAC system is malfunctioning.

______________________________

LED’s are not responding properly 

and HVAC system is malfunctioning.

 

______________________________

LED’s do not illuminate and HVAC 

system does not respond.

______________________________

LED’s illuminate and HVAC system 

functions normally but dampers do not 

respond.

SOLUTIONS

_______________________________________________________________

Check HVAC system wiring for proper connections. 
Check HVAC system wiring for shorts/miswiring.
Check HVAC System.
Refer to Technical Bulletin for correct setup/wiring.
_______________________________________________________________
Check HVAC system wiring for shorts/miswiring.
Check HVAC system wiring for proper connections. 
Check HVAC thermostat for proper connections.
Refer to Technical Bulletin for correct setup/wiring.

_______________________________________________________________
Check HVAC system supply voltage.
Check HVAC system 24vac transformer voltage/fuse/HKcircuit breaker.
Check HVAC system wiring for shorts/miswiring.
Refer to Technical Bulletin for correct setup/wiring.
_______________________________________________________________
Check damper motor wiring for proper connections.
Check damper motor 24vac transformer voltage/fuse/HKcircuit breaker.
Check damper motor wiring for shorts/miswiring.
Refer to Technical Bulletin for correct setup/wiring.

DETECTING 24vac SHORTS

______________________________

HVAC system not responding and

HK2000 LED’s are off.

______________________________

Dampers not responding and HK2000 

LED’s are on.

______________________________

ISOLATING 24vac SHORTS

____________________________

F2 circuit breaker protects the 

HK2000 and reacts to a short in the 

thermostat field wiring.

______________________________

F1 circuit breaker protects the 

HK2000 and reacts to a short in a 

damper motor or the damper motor 

field wiring.

SYMPTOMS

_______________________________________________________________

If 24vac short has occurred, 24vac will be present at the

 HK2000 System Input 

terminals R & C;

 but 24vac will not be present at the Thermostat R&C terminals. 

Caution: Circuit breaker will be hot!
_______________________________________________________________

If 24vac short has occurred, 24vac will be present at the

 HK2000 Damper Motor 

Input terminals RM & CM; 

but will not be present at any Damper M1&M2 

terminals. 

Caution: Circuit breaker will be hot!

_______________________________________________________________

SOLUTIONS:

 

Remove 24vac power from HK2000 and allow circuit breaker(s) to cool!

_______________________________________________________________
Disconnect  the wire from the 

R terminal on the HK2000 thermostat terminal 

block 

and restore power. If the short has gone away, check thermostat and 

wiring for shorts. Replace wires if necessary.
______________________________________________________________
Disconnect all wires at all 

damper terminal blocks (M1,M2,M4 & M6) one at a 

time, until the 24vac power restores to terminals M1 & M2.

 Check the damper 

motors and wiring for shorts. Replace wires if necessary.

CHECK YOUR WIRING

TECHNICAL SUPPORT

EWC Controls provides superior toll free Troubleshooting Support for the HK2000 when you are on the job site!  
Call 1-800-446-3110  Monday - Friday 8am to 5pm EST
Otherwise call 1-732-446-3110 for information on the HK2000 and other ULTRA-ZONE products..

When calling for Technical Support, please have a multi-meter, pocket screwdriver, and wire cutter/stripper handy. 

Summary of Contents for ULTRA-ZONE HK2000

Page 1: ...reaker is tripped it will get quite hot To reset the breaker remove the 24vac power Locate and repair the short Then restore the power See Page 9 Compatible HVAC Systems Compatible Thermostats Operating Power Thermal Circuit Breakers EWC Controls Inc 385 Highway 33 Englishtown NJ 07726 800 446 3110 FAX 732 446 5362 E Mail info ewccontrols com Model HK2000 Fresh Air Economy Control System TB 214 P ...

Page 2: ... Cycle Setting is changed 0 2 4 6 8 10 12 FRESH AIR CYCLES HOUR Adjustable Outside Air Sensor The HK2000 includes a reliable 10K Thermistor Sensor The sensor must be mounted outdoors and wired back to the panel It provides the processor a means of reading the outside dry bulb temperature Used with OA Temp Mode and Mechanical Cooling Assistance Optional Return Air Sensor Required for Mechanical Ass...

Page 3: ...ROLS INC Englishtown NJ THERMOSTAT SYSTEM TRANSFORMER HEAT RELAY W COOL RELAY Y FAN RELAY G R C G R Y W C RETURN AIR SENSOR OPTIONAL USED ONLY IF MECHANICAL COOLING ASSISTANCE IS REQUIRED MA ND URD 6 4 1 M M C NO NC M M C NO NC MA ESR POWER CLOSE SPRING OPEN MA ESR POWER OPEN SPRING CLOSE OUTSIDE AIR SENSOR WIRING DIAGRAM FRESH AIR ECONOMIZER Model HK2000 Control Panel DRY BULB CONTROL MODE SEPARA...

Page 4: ... Outside Air Mode Free Cooling If the HK2000 detects that the Enthalpy control has opened it s contacts The HK2000 will terminate economy operation and energize mechanical cooling to satisfy the cooling demand All dampers default back to the Return Air Mode unless a Fresh Air Cycle occurs at the same time NOTE Follow the instructions when installing and setting up the Enthalpy control It should be...

Page 5: ... FRESH AIR MODE ENTHALPY MODE COOLING CALL BYPASS RUN O A TEMP R A TEMP ENTH ALPY C Y R G M6 M4 M2 M1 RM CM M6 M4 M2 M1 M6 M4 M2 M1 SYSTEM THERMOSTAT HK2000 ECONOMIZER FRESH AIR SYSTEM EWC CONTROLS INC Englishtown NJ THERMOSTAT 1 2 3 ENTHALPY CONTROL MODEL EC H705 A B D C G R Y W C WIRING DIAGRAM FRESH AIR ECONOMIZER Model HK2000 Control Panel ENTHALPY CONTROL MODE 42 48 54 60 66 72 78 DRYBULB ECO...

Page 6: ... Mode ReturnAir Damper OPEN DEFAULT OutsideAir Damper CLOSED ExhaustAir Damper CLOSED OUTSIDE Air Mode Return Air Damper CLOSED OutsideAir Damper OPEN ExhaustAir Damper OPEN FRESHAirMode ReturnAir Damper CLOSED OutsideAir Damper OPEN ExhaustAir Damper OPEN MECHANICAL ASSISTANCEMode Return Air Damper CLOSED OutsideAir Damper OPEN ExhaustAir Damper OPEN Warning Your application may limit the dampers...

Page 7: ...s Cooling Call LED illuminates when the panel detects a cooling demand from the Thermostat NOTE It is possible to observe both the Economy LED and the Compressor LED illuminated at the same time EXAMPLE 1 A call for cooling has occurred but outdoor conditions are not suitable to satisfy the demand so the compressor is activated and the Compressor LED illuminates The Fresh Air Cycle Schedule activa...

Page 8: ...s OFF A setting of 12 is continuous fresh air Example A single hour is divided into Five 5 minute increments of fresh air The installer has chosen a setting of 6 cycles per hour which results in a total of 30 minutes of fresh air every hour The HK2000 will activate the dampers into the Fresh Air Mode for 10 minutes the 1st qtr Hour 5 minutes the 2nd qtr Hour 10 minutes the 3rd qtr Hour and 5 minut...

Page 9: ...he life of your standard return air filter 4 Use hooded intake and exhaust fittings to stop rain or snow from falling into your duct 5 DO NOT install a return air damper or completely close off a return air damper if your fresh air duct is under sized or completely closed off Example Return air main is 20 x25 and you install an 8 round fresh air duct damper You will NOT install a return air damper...

Page 10: ..._______________________ Dampers not responding and HK2000 LED s are on ______________________________ ISOLATING 24vac SHORTS ____________________________ F2 circuit breaker protects the HK2000 and reacts to a short in the thermostat field wiring ______________________________ F1 circuit breaker protects the HK2000 and reacts to a short in a damper motor or the damper motor field wiring SYMPTOMS __...

Page 11: ...on to terminal 1 and 24vac hot to terminals 2 and 4 Damper should Open Remove 24vac hot from terminal 4 Damper should Close BMD SMD ND URD Dampers Connect 24vac common to terminal 1 and 24vac hot to terminal 4 Damper should Open Remove 24vac hot from terminal 4 and apply to terminal 6 Damper should Close SR ESR Power Close Spring Open Dampers Connect 24vac common hot to the two motor M terminals D...

Page 12: ...UTSIDE AIR SENSOR Model HK2000 Fresh Air Economizer Control Panel NOTE This diagram reflects Dry Bulb Mode Diagram also applies to Enthalpy Mode SEPARATE T40 VA 24 VAC 40VA T FORMER 42 48 54 60 66 72 78 DRYBULB ECONOMY CHANGEOVER TEMP 0 2 4 6 8 10 12 FRESH AIR CYCLES HOUR Set to desired Outdoor Changeover Temperature Set to desired number of Fresh Air Cycles Y2 W2 2 STAGE GAS or ELECTRIC FURNACE W...

Reviews: