200
WT.050.580.000.DE.IM.0714
Installation
MFC
6.
6.3.11
Ym Calibration
Only with selection of "Electr.Pos. w. Ym".
Automatic calibration
1
Starting with the basic display in the main menu, open the
"Dosing" window from the "Module Type (1)" menu.
2
Select "Ym Calibration" and confirm the selection.
3
Select the "Auto" function and confirm the selection.
Feedback signal alignment starts automatically.
The motor moves to the end positions Ym = 100 % and
Ym = 0 %. The message "End" indicates the end of the
alignment. If an error occurs during automatic setting, "pos.-
error" appears and the setting is terminated.
4
Determine the running time of the positioner from 0 % to
100 %.
5
Enter the determined running time in the "Dosing" window
under Ty.
Please note
If automatic alignment is not successful, perform alignment
manually. For this purpose, manually move to YmCal. 0 % and
YmCal 100 % and save.
Manual calibration
Please note
The feedback signal can be adjusted by no more than 30 %.
1
Switch device to manual (Keys "Mode" ... "Change").
2
Manually close the positioner via the MAN.DOS ... Module
Type (1) key until the limit switch turns off.
3
Starting with the basic display in the main menu, open the
"Dosing" window from the "Module Type (1)" menu.
4
Select "Ym Cal. 0 %" and confirm the selection.
5
Manually open the positioner via the MODE - MAN.DOS –
Module Type (1) key until the limit switch turns off.
6
Starting with the basic display in the main menu, open the
"Dosing" window from the "Module Type (1)" menu.
7
Select "YmCal 100 %" and confirm the selection.
Please note
There must be a distance of at least 60 % of the total path between
Summary of Contents for WALLACE & TIERNAN MFC
Page 1: ...WALLACE TIERNAN MULTI FUNCTION CONTROLLER MFC from version V 2 00 INSTRUCTION MANUAL...
Page 2: ...2 WT 050 580 000 DE IM 0714 MFC Please note Original manual...
Page 6: ...6 WT 050 580 000 DE IM 0714 Introduction MFC 1...
Page 40: ...40 WT 050 580 000 DE IM 0714 Description MFC 3...
Page 247: ...MFC Certificates 10 247 10 Certificates...
Page 248: ...248 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 249: ...MFC Certificates 10 249...
Page 250: ...250 WT 050 580 000 DE IM 0714 Certificates MFC 10...
Page 262: ...262 WT 050 580 000 DE IM 0714 Settings table MFC 11...