Evo Flex Manual 

6.2 Frequency Conversion Board Fault Table 

Protection/Fault 

Fault Display 

Reason 

Elimination Methods 

IPM Overcurrent 

Shutdown Fault 

F00 

IPM Input current is large 

Check and adjust the current 

measurement 

Compressor Activation 

Failure 

F01 

Lack of phase, step or drive hardware 

damage 

Check the measuring voltage, check 

frequency conversion board 

hardware 

PFC Fault 

F03 

The PFC circuit protection 

Check the PFC switch tube short 

circuit or not 

DC Bus Overload 

F05 

DC bus voltage<Dc bus Overload – voltage 

protection value 

Check the input voltage 

measurement 

DC Bus Underload 

F06 

DC bus voltage<Dc bus underload – 

voltage protection value 

Check the input voltage 

measurement

 

AC Input Underload 

F07 

The input voltage is under, causing the 

input current to be too low 

Check the input voltage 

measurement

 

AC Input Overload 

F08 

The input voltage is over, causing the 

input current to be too high 

Check and adjust the current 

measurement

 

Input Voltage Sample Fault 

F09 

The input voltage sampling fault 

Check and adjust the current 

measurement

 

Communication Failure 

between DSP and PFC 

F10 

DSP and PFC connect fault 

Check the communication 

connection 

Communication Fault 

(DSP) 

F11 

DSP and Inverter board communication 

failure 

Check the communication 

connection 

Communication Fault 

(Inverter Board) 

F12 

Communication failure between inverter 

board and main board 

Check the wire connection between 

remote inverter board and main 

board 

IPM Overheat Stop 

F13 

The IPM module has overheated 

Check and adjust the current 

measurement 

Weak Magnetism Alarm 

F14 

Compressor magnetic force is not enough 

Input Voltage Lacking 

Phase 

F15 

The input voltage lost phase 

Check and measure the voltage 

adjustment 

IPM Current Sample Fault 

F16 

IPM Sampling electricity is fault 

Check and adjust the current 

measurement

 

Sensor Fault of 

Module/Radiator 

F17 

The transducer is overheating 

Check and adjust the current 

measurement

 

IGBT Power Device 

Overhear Alarm 

F20 

The transducer is overheating 

Check and adjust the current 

measurement

 

Overload Alarm 

F21 

The compressor input current is too large  Check and adjust the current 

measurement

 

AC Input OverCurrent 

Alarm 

F22 

Input current is too large 

Check and adjust the current 

measurement

 

EEPROM Fault Alarm 

F23 

MCU Error 

Destroyed EEPROM 

Activation Ban Alarm 

F24 

MCU Error 

LP 15V Underload Fault 

F25 

The V15V is overload or undervoltage 

Check the V15V input voltage in 

range 13.5V~16.5 or not 

IGBT Power Device 

Overheat Fault 

F26 

Transducer temperature is too high 

Check and adjust the current 

measurement 

Summary of Contents for EVO FLEX 10

Page 1: ......

Page 2: ..._______________________________________________________________ 10 5 2 4 Fast Heating _____________________________________________________________________________ 10 5 2 5 Timer Setting _____________...

Page 3: ...x Series can adjust the output capacity automatically and control the room temperature accurately The Evo Flex Series is ideal for domestic hot water and space heating and cooling Latest DC invert hea...

Page 4: ...3 Evo Flex Manual 2 Unit Specifications 2 1 Unit Structure Evo Flex 10 Evo Flex 17 25...

Page 5: ...pressor Quantity 1 1 1 Compressor Model Rotary Rotary Rotary Fan Quantity 1 2 2 Fan Power Input W 75 75 X 2 150 X 2 Fan Rotate Speed RPM 850 850 900 Noise dB A 54 58 62 Water Pump Input kW 0 18 0 5 0...

Page 6: ...5 Evo Flex Manual 2 3 Dimensions Evo Flex 10 Evo Flex 17 Evo Flex 25...

Page 7: ...t pump is installed on a strong and stable platform A circuit breaker must be installed for the unit Use supply wires suitable for 75 C Caution Single wall heat exchanger not suitable for potable wate...

Page 8: ...able to support the weight of a heavy unit such as a terrace roof the ground and any other places deemed suitable The location must have good ventilation The location must be free from heat radiation...

Page 9: ...itial Start up of the Unit INSPECTION BEFORE TRIAL RUNNING Check the indoor unit make sure that the pipe connection is done correctly and the relevant valves are open Check the water loop to ensure th...

Page 10: ...presents enabled 6 Setup key Click this key to check the unit status time factory parameters temperature curve timer setting and mute setting 7 Fault icon This icon will flash when there is an error o...

Page 11: ...t temperature to be set a pop up keyboard will appear 3 Pressing 3 will allow the target temperature of cooling mode to be set through the keyboard When the target temperature is being set the followi...

Page 12: ...Interface Key Name Key Function 1 Status Key Click this key to get into the status interface 2 Clock Key Click this key to set the operational time function 3 Mute Key Click to turn on off silent func...

Page 13: ...g the fault records it will ask for a code The password will be according to the display date For example if the display date is 12 11 2016 then the password is 12 5 2 9 Colour Display Calibration Kee...

Page 14: ...erloaded Check whether the system of the compressor is running normally Communication Fault E08 Communication failure between wire controller and mainboard Check the wire connection between remote wir...

Page 15: ...on Fault DSP F11 DSP and Inverter board communication failure Check the communication connection Communication Fault Inverter Board F12 Communication failure between inverter board and main board Chec...

Page 16: ...eakage and recharge freon Block on filter or capillary Replace filter or capillary Lack of water flow Clean the water filter and discharge the air in water loop Compressor do not run Power supply fail...

Page 17: ...ral Valve 12 Drain Valve 5 Three way Valve 13 Non return valve 6 Y type Filter 14 Water Pump 7 Safety Valve 15 Fan Coil 8 Expansion Tank Installation Request 1 The Factory only offers one main unit 1...

Page 18: ...the handle A can return close when the system is full of water Automatic filled water valve needs periodic cleaning When you must close the tap unscrew the plug D remove the inside filter net Reassem...

Page 19: ...2 x 6mm2 6mm2 40A 32 40A 2 x 10mm2 10mm2 63A 40 63A 2 x 16mm2 16mm2 80A 63 75A 2 x 25mm2 25mm2 100A 75 101A 2 x 25mm2 25mm2 125A 101 123A 2 x 35mm2 35mm2 160A 123 148A 2 x 50mm2 50mm2 225A 148 186A 2...

Page 20: ...19 Evo Flex Manual 7 3 Controller Interface Drawing...

Page 21: ...m exhaust temperature input 20 AI04 Reserved 21 AI05 System suction temperature input 22 AI06 System coil temperature input 23 AI07 Ambient temperature input 24 AI08 Water tank temperature input 25 AI...

Page 22: ...rvice agents Please contact EvoHeat tech support on 1300 859 933 for your local service agent details Should I check my unit regularly We recommend you check your unit regularly to avoid potential iss...

Page 23: ...damage to the product in transit 4 If warranty service is required you should a contact Evo Industries Australia on 1300 859 933 or via our Contact page on our web site b provide a copy of your receip...

Reviews: