ViewSmart Room controller connections
The Room controller is a white ABS box with a graphic display. If ViewSmart is not installed on the
unit, it should be installed in the main living area of the dwelling. It must be connected to the
connection board within the ModuSat® (please refer to the electrical diagram)
. The cable must not
be installed adjacent to other 220/240 Volt (AC) lines.
Power Supply for ViewSmart
The ModuSat® room controller’s power is supplied by the ModuSat® board and
does not require batteries or additional power cabling.
External Valve and Pump Requirements
When connecting external valves or pumps to the control board of the ModuSat®
it must be ensured that each connection does not exceed 1amp @ 220/240V (AC).
Cable Requirement
ViewSmart should be connected to ModuSat® connection board with 4 core x 0.33
mm
2
screened cable
Dimensions:
H = 80 mm
L = 130 mm
D = 22 mm
To open the cover to access connections:
Step 1
To open the cover to access
connections, use a screwdriver
in the tab at the bottom as
shown below.
Step 2
Once the tab has been released the
cover can be hinged up to access
connection
Step 3
Connection terminal with room
controller