28 

 

2551868A 

 

WARRANTY 

The warranty has value if good practice has been strictly observed during installation and in use. 

Evinox Energy is not liable for equipment breakdown and damage to persons and objects caused by:

 

 

Transportation damage

 

 

Installation in which the instructions and good practice were not complied with

 

 

Improper use of the device, abnormal use conditions, tampering by unauthorised personnel or 

inadequate maintenance; corrosion and/or sludge accumulation; lack of electrical energy; 

absence of suitable drainage; exceeding operating limits, electrical and water system faults

 

 

Frost damage

 

 

Wear due to normal use

 

 

Malfunctioning of system controls and or safety systems

 

 

Corrosion due to oxygenation poor water quality or roaming currents

  

 

The pump being run against a closed system. 

 

From commissioning, ModuSat® XR appliances have a warranty against all manufacturing faults and 

material defects for a period of:

 

 

5 years for the stainless-steel plate heat exchangers

 

 

2 years for parts and labour Note: -

Where Evinox Energy do not carry out the commissioning or 

have no “developer agreement” in place the two-year warranty will cover parts only with no 

labour cover)

 

The ModuSat® warranty will always start from the commissioning date providing this date is within 

six months of the date of invoice to allow for project completion. If the ModuSat® XR is 

commissioned outside the 6-month extension date, the warranty will reduce accordingly.

 

This warranty is strictly limited to the supply, free of charge, of parts acknowledged as being 

defective after inspection by our technical department. Any costs arising from this inspection will be 

charged if the part is deemed not to be defective. The defective parts must be returned otherwise 

the replacement part will be charged for.

 

Failure to comply with the relevant installation requirements of the Building Regulations, Local 

Water Byelaws and Building Standards will invalidate any warranty claim.

 

The ModuSat® must be fitted with the ModuSat® Flushing by-pass isolation valve kit for ease of 

servicing and undertaking warranty work. Warranty calls that include draining the system will be 

chargeable if isolation valves have not been fitted. 

 

It is imperative that the level of corrosion protector within the system is kept within industry 

guidelines at all times. Special attention should be given to ensure that, after any decoration or 

building works where radiators might be removed, the system is replenished with chemicals. Non-

use of inhibitor will invalidate the warranty.

 

We will record details of the unit and commence the warranty when we commission the ModuSat® 

units.

 

Any warranty claims that are a result of user error, poor installation or lack of servicing will be 

chargeable. Please note that all replacement parts provided under warranty are subject to factory 

inspection to determine cause of failure. Replacement parts are chargeable until passed as faulty by 

Evinox Energy, when a credit will be provided. Any parts that have failed as a result of poor servicing 

or misuse will not be covered by our warranty.

 

Summary of Contents for ModuSat XR ECO CHHC

Page 1: ...1 2551868A Evinox ModuSat XR ECO CHHC Combined Heating Hot Water and Cooling...

Page 2: ...t heating and cooling systems 15 Water treatment 16 Water Quality Guidelines 16 Dosing Secondary System 17 Warranty due to Water Quality 17 Electrical Connections 18 Removing the Front panel 18 ModuSa...

Page 3: ...to read and follow the instructions provided within this document may cause a safety hazard or and failure of the equipment Qualified personnel only The Evinox heat interface unit must be installed co...

Page 4: ...the electricity supply before starting any works on the unit Qualified personnel Electrical installation must only be carried out by qualified personnel In the case of water leak Take caution of hot...

Page 5: ...requested by the end user controller the heating operation is started The electronically controlled PICV is used to modulate the primary flow rate to match the heating demand The unit has an integrat...

Page 6: ...plate heat exchanger Cooling C2 Cooling Pressure Independent Control Valve PICV with actuator C5 Cooling meter DHW Secondary Side Circuit 6 Flow sensor Heating Secondary Side Circuit 7 Heating expansi...

Page 7: ...Drain G 1 2 1 2 1 2 Primary cooling flow A1 3 4 1 1 1 4 Primary cooling return B1 3 4 1 1 1 4 Secondary cooling flow C1 3 4 1 1 1 4 Secondary cooling return D1 3 4 1 1 1 4 Type 5 Type 6 7 Type 8 Prim...

Page 8: ...t Apartment heating circuit recommended cold fill pressure 1 bar Apartment heating maximum pressure 3 bar Apartment heating expansion vessel size 8 L Apartment cooling circuit recommended cold fill pr...

Page 9: ...9 2551868A Typical Dimensions...

Page 10: ...servicing Top 250 mm To allow for H type flushing by pass Front 700 mm Side 50 mm Flushing by pass kits for 1 1 4 are not supplied by Evinox installer must ensure that there is enough space for the 1...

Page 11: ...property Lifting Take care when lifting this appliance It is recommended that at least two people perform the lifting Leave caps over the connections Ensure that the protective cover caps over the Mo...

Page 12: ...ections and domestic water hydraulic connections as shown below The Evinox Energy flushing by pass valve kit should be installed before connecting the unit to the network Isolation valves should not b...

Page 13: ...it for heating circuit Close valves Before connecting flushing by pass kit to the HIU ensure all isolation valves are closed Valves can be opened after LTHW system has been flushed Evinox ModuSat flus...

Page 14: ...all the connections are tightened to avoid any leaks First fill of the HIU Clean and flush the system before connecting the unit Filling the system should be performed only after the system has been...

Page 15: ...system should be performed only after the system has been fully flushed and clean Poor water quality may cause failure of the operation of the unit First fill of apartment heating and cooling systems...

Page 16: ...to BSRIA Application Guide BG29 2012 BS7593 2006 Requirements of your local water authority The Water Industry Act 1991 Section 119 HSE The Control of Legionella 1991 HSC Approved Code of Practice an...

Page 17: ...ater may lead to scale build up and corrosion This may damage the ModuSat unit or reduce the performance Please confirm with the water treatment consultants that the chemicals used and cleaning method...

Page 18: ...on will invalidate the warranty Evinox Energy cannot accept any responsibility for incorrect wiring The ModuSat wiring boards are located within the ModuSat itself under a removable metal cover To acc...

Page 19: ...ailed in the wiring principle drawings shown on pages 21 23 The Control Board The control board is located next to the connection board The control board cover must not be removed Doing so may invalid...

Page 20: ...20 2551868A ModuSat Connection Board Please Note When connecting external valves or pumps to the ModuSat control board it must be ensured that each connection does not exceed 1amp 220 240V AC...

Page 21: ...21 2551868A 5 4 Typical ModuSat Electric Wiring Diagram Two Evinox ViewSmart Room Controllers See drawing STD MOD BMS CHHC_A...

Page 22: ...oard and does not require batteries or additional power cabling External Valve and Pump Requirements When connecting external valves or pumps to the control board of the ModuSat it must be ensured tha...

Page 23: ...system wiring ModuSat CHHC can be used in two network topologies RS485 Bus and TCP IP Typical Modbus system architecture See drawing STD MOD 2013 BUS 1 E Typical TCP IP system architecture See drawing...

Page 24: ...report to Evinox Energy Pre commissioning checklist Pre requisite of Commissioning 1 Primary network and plant room fully operational and complete including water treatment in line with these instruct...

Page 25: ...609 l h 575 l h Start up P 25 kPa 25 kPa 25 kPa Max P 400 kPa 400 kPa 400 kPa Valve size DN20 DN25 DN15 Thread G 1 G 1 1 4 G 3 4 Actuator Stroke 2 5 mm 5 5 mm 2 5 mm Actuator control signal 0 10V 0 10...

Page 26: ...rmal operation Blinks red green Pump in function but stopped Pump restarts by itself after the fault is disappeared 1 Low voltage U 160 V or High voltage 253 V 1 Check voltage supply 195 V U 253 V 2 M...

Page 27: ...ty check 4 Ensure the unit has an ID number record serial numbers of the control board and the heat meter Evinox Technical Personnel Evinox Technical Personnel who will visit the project during the co...

Page 28: ...dingly This warranty is strictly limited to the supply free of charge of parts acknowledged as being defective after inspection by our technical department Any costs arising from this inspection will...

Page 29: ...re long life reliability and efficiency Exclusions to the Warranty The following are not covered by the warranty Electric degradation of parts resulting from connection and installation on electricity...

Page 30: ...30 20R R50 55 30R R60 30 20R R60 55 40R R20 30 30R R20 55 40R R30 30 30R R30 55 40R R40 30 30R R40 55 40R R50 30 30R R50 55 40R R60 30 30R R60 70 10A R20 30 40R R20 70 10A R30 30 40R R30 70 10A R40 3...

Page 31: ...R40 100 10A R50 100 10A R60 100 20A R20 100 20A R30 100 20A R40 100 20A R50 100 20A R60 100 30A R20 100 30A R30 100 30A R40 100 30A R50 100 30A R60 100 40A R20 100 40A R30 100 40A R40 100 40A R50 100...

Page 32: ...32 2551868A WRAS CERTIFICATE...

Page 33: ...Evinox Energy Ltd Barwell Business Park Leatherhead Road Chessington London KT9 2NY Tel 44 0 1372 722 277 Fax 44 0 1372 744 477 DRAWN DATE SCALE Evinox www evinox co uk EVINOX RESERVES THE RIGHT TO M...

Page 34: ...ACTERISTICS OF ITS EQUIPMENT WITHOUT PRIOR NOTICE AS PART OF ITS CONTINUING PRODUCT DEVELOPMENT NOTES Energy MODUSAT SmartTalk DATA LOGGER AND SUPPLY UNIT BUS PRINCIPLE SYSTEM ARCHITECTURE BJW AUGUST...

Page 35: ...TIONAL NETWORK SWITCH INSIDE APARTMENT OPTIONAL MODUSAT UNIT MODUSAT CONTROL BOARD MODUSAT UNIT MODUSAT CONTROL BOARD MODUSAT UNIT MODUSAT CONTROL BOARD MODUSAT UNIT MODUSAT CONTROL BOARD NETWORK SWIT...

Reviews: