E2658_UM_EN. Annex 1. E2658 series Modbus RTU Communication Reference

RS485 communication interface

Databits: 8
Parity: none / odd / even
Stop bits: 1 or 2
Protocol: Modbus RTU

Supported Modbus functions:
03 – read multiple registers 
06 – write single register

Communication parameters

Parameter

Permitted values

Default

Supported
baudrates

1200, 2400, 4800, 9600, 19200,
38400, 57600

9600

Data bits

8

8

Parity

none / odd / even

none

Stop bits

1, 2

1

Protocol

Modbus RTU

Modbus functions

03 - read multiple registers
06 - write single register

Error codes

01 – illegal function
02 – illegal data address
03 – illegal data value
04 – slave device failure (details of last error 04
can be read from register 0x0008)

E2658 series Modbus holding registers
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR RW

Description

Supported values (dec)

Default

0x0001

1 / 40002

R

Hardware version

-

0x0002

2 / 40003

R

Software version

-

0x0003

3 / 40004

R

Product serial number

1...65535

-

0x0004

4 / 40005

RW

Slave ID (net address) *

1...247 **

1

0x0005

5 / 40006

RW

Baudrate *

1200, 2400, 4800, 9600, 19200, 38400, 57600

9600

0x0006

6 / 40007

RW

Response delay, ms

1...255

10

0x0007

7 / 40008

RW

Stop bits, parity bit *

1 – no parity bit, 1 stop bit (default after factory reset)
2 – no parity bit, 2 stop bits
3 – odd parity, 1 stop bit
4 – even parity, 1 stop bit
NOTE

: 3 and 4 are available starting from the Software version 0x218 (dec. 536)

1

0x0008

8 /40009

R

Last error code

1...255

-

0x0011

17 / 40018

RW

Restarts counter

write ‘42330’ to restart device

-

* – The new value is applied after restart.
** – Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be

the only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.

*** – This value is dynamic and not kept in EEPROM after restart

Summary of Contents for PluraSens E2658-VOC

Page 1: ...ons 11 30 VDC 24 VAC or 90 265 VAC with mains power unit Power consumption 2 VA Analog outputs 2 4 20 mA 0 10 V user settable Outputs assignment OUT1 2 gas OUT2 2 gas Load resistance RL Us 2 V 22 mA f...

Page 2: ...g to the relevant connection diagram Use ATEX certified armoured cables or cable conduits The screwless quick connect spring terminals on the E2658 series devices are suitable for a wide range of wire...

Page 3: ...AWINGS AND DIAGRAMS Note for 24V versions only one terminal block is mounted J1 OUT1 type open 4 20 mA closed 0 10 V J2 OUT2 type open 4 20 mA closed 0 10 V J3 return to factory settings J1 OUT1 type...

Page 4: ...may be addressed either from 00001 or 40001 base Addr Reg MHR RW Description Supported values dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product s...

Page 5: ...in MHR 40205 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 2...

Page 6: ...d bit 10 0 1 LED is on off in normal condition bit 11 0 1 LED and buzzer syncing off on with RE1 bit 12 0 1 LED and buzzer syncing off on with RE2 user defined 0x0101 257 40258 R Raw gas sensor data 0...

Page 7: ...ort term exposure to high levels of ethyl acetate results first in irritation of the eyes nose and throat followed by headache nausea vomiting sleepiness and unconsciousness Exposure limits NIOSH TWA...

Reviews: