Volatile Organic Compounds
Highly volatile organic liquids. The definitions of VOC may vary depending on
application field and country. E2658-VOC is intended to detect vapours of solvents
(acetone, benzene, ethanol, ethyl acetate, toluene, xylenes etc.
See Annex 2 for more information on the properties of various gases.

Installation guidelines
(See Installation and connections section for general information.)
Solvent  vapours  are  heavier  than  air  and  tend  to  sink.  Consider,  if  the  vapours  are
heated or not, if the detector is used for fire safety (LEL range) or air quality control
(0...100 to 0...1000 ppm range) etc.
Calibration

E2658-VOC  detectors-transmitters  have  been  calibrated  by  Manufacturer  with
standard  gas  mixtures  before  delivery.  Provided  that  the  sensor  is  used  under
moderate  conditions,  field  recalibration  is  recommended  once  a  year.  Please
contact your dealer for more information.

E2658-VOC_UM_EN 

Rev 1

4.07

.2020

Specifications

Sampling method

diffusion

Sensor type

metal oxide semiconductor

Default calibration

toluene

Typical detection range

0...100% LEL

up to 0...1000 ppm

Resolution / digital unit

0.1% LEL

1 ppm

Response time T90

< 120 s

Sensor lifetime

> 5 years

Calibration interval

12 months

Signal update

every 1 second

Power supply options

11...30 VDC, 24 VAC

or 90...265 VAC (with mains power unit)

Power consumption

< 2 VA

Analog outputs

2 × 4-20 mA / 0-10 V, user settable

Outputs assignment

OUT1 2 gas; OUT2 2 gas

Load resistance

R

L

 < (Us - 2 V) / 22 mA for 4-20 mA

R

L  

> 250 kOhm for 0-10 V mode

Digital interface

RS485, Modbus RTU protocol

no galvanic isolation

Enclosure

Grey die-cast aluminium, wall mount, IP66

Cable gland

M25 for SWA cable or steel conduit Ø10...17 mm

Dimensions

H

8

0 × W125 × D57

 / H80 × W175 × D80

 mm

Protection

flameproof, ATEX: II 2 GD, Ex ed IIC T4 Gb

ATEX Approvals

Enclosure:
ATEX / IECEx

DEMKO 13 ATEX 1327771U

II 2 G Ex c IIC Gb 

II 2 D Ex tb IIIC Db IP66

Glands:
ATEX / IECEx

II2G Ex e II IP68

IBExU08ATEX 1063 X Ex II 1D Ex tD A20 IP 6x Ex

CE marking

Flameproofepd to IEC EN 60079-1
Increased safety to IEC EN 60079-7
EMC Emissions to EN 61000-6-3, EN 61326-1
EMC Immunity to EN 61000-6-1, EN 61000-6-2

Operating conditions

-30...+70 °C

< 95% RH non-condensing, 0,9...1,1 atm

Explosion-safe zones and ATEX Zones 2 and 22

Normal ambient oxygen level

Avoid exposure to corrosive gases or silicone

containing products

Relay option

Output relays

2 × SPST relays (closing contact),

250 VAC / 30 VDC, 5 A max

Alarm setpoints
(set/release)

RE1 (LOW): 20/16 % LEL;

RE2 (HIGH): 50/40% LEL

RE1 (LOW): 100/80 ppm;

RE2 (HIGH): 300/240 ppm

(for 0...500 ppm range)

Evikon MCI OÜ

                Teaduspargi 7/9, Tartu

[email protected]

         Tel. +372 733 6310 

  50411 Estonia

www.evikon.eu

PluraSens

®

Flame Proof
Solvent Vapours Detector-Transmitter

E2658-VOC

User Manual

Summary of Contents for PluraSens E2658-VOC

Page 1: ...ons 11 30 VDC 24 VAC or 90 265 VAC with mains power unit Power consumption 2 VA Analog outputs 2 4 20 mA 0 10 V user settable Outputs assignment OUT1 2 gas OUT2 2 gas Load resistance RL Us 2 V 22 mA f...

Page 2: ...g to the relevant connection diagram Use ATEX certified armoured cables or cable conduits The screwless quick connect spring terminals on the E2658 series devices are suitable for a wide range of wire...

Page 3: ...AWINGS AND DIAGRAMS Note for 24V versions only one terminal block is mounted J1 OUT1 type open 4 20 mA closed 0 10 V J2 OUT2 type open 4 20 mA closed 0 10 V J3 return to factory settings J1 OUT1 type...

Page 4: ...may be addressed either from 00001 or 40001 base Addr Reg MHR RW Description Supported values dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product s...

Page 5: ...in MHR 40205 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 2...

Page 6: ...d bit 10 0 1 LED is on off in normal condition bit 11 0 1 LED and buzzer syncing off on with RE1 bit 12 0 1 LED and buzzer syncing off on with RE2 user defined 0x0101 257 40258 R Raw gas sensor data 0...

Page 7: ...ort term exposure to high levels of ethyl acetate results first in irritation of the eyes nose and throat followed by headache nausea vomiting sleepiness and unconsciousness Exposure limits NIOSH TWA...