E2658-LEL
Rev 11.03.2022
0x00D3
211 /
40212
RW
Parameter tied to relay
RE1
0 –none
2 – gas concentration
9 – control by Modbus control,
state set in MHR / 40214
2
0x00D4
212 /
40213
RW
Parameter tied to relay
RE2
0 – none
2 – gas concentration
9- – control by Modbus
control, state set in MHR /
40215
2
0x00D5
213 /
40214
RW
Forced state for relay
RE1***
0 –off, 1 – on
0
0x00D6 214/ 40215 RW
Forced state for relay
RE2***
0 – off, 1 – on
0
0x00D7
215 /
40216
RW Switching delay for relay
RE1
0...1000 (s)
0
0x00D8
216 /
40217
RW Switching delay for relay
RE2
0...1000 (s)
0
0x00D9
217 /
40218
RW
Minimal on/off time for
relay RE1
0...1000 (s)
0
0x00DA
218 /
40219
RW
Minimal on/off time for
relay RE2
0...1000 (s)
0
Address
Reg / MHR RW Description
Supported values (dec)
Default
0x00DB
219 /
40220
RW Control logic for relay RE1
0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values
within the range
4 – relay on for the values
out of the range
0
0x00DC
220 /
40221
RW Control logic for relay RE2
0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values
within the range
4 – relay on for the values
out of the range
0
26