E2638 series Modbus holding registers (part 2)
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR

RW

Description

Supported values (dec)

Default

0x00A2

162 / 40163 RW

Zero adjustment for temperature
data, °C × 100

-32000...+32000 (-320,00...+320,00 °C)

0

0x00A5

165 / 40166 RW

Zero adjustment for gas data, ADC

-32000...+32000 ADC units

0

0x00A6

166 / 40167 RW

Slope adjustment for gas data

1...65535

512

0x00A7

167 / 40168 RW

Change rate limit for gas data,

gas unit / s

1...32000, 0 - no limit

0

0x00A8

168 / 40169 RW

Integrating filter time constant, s

1...32000 (seconds), 0 - no filter

0

0x00C9

201 / 40202 RW

Parameter tied to analog output 1

0 – none
1 – temperature
2 – gas concentration
9 – forced Modbus control, value set in MHR / 40204

2

0x00CA

202 / 40203 RW

Parameter tied to analog output 2

0 – none
1 – temperature
2 – gas concentration
9 – forced Modbus control, value set in MHR / 40205

2

0x00CB

203 / 40204 RW

Forced value for analog output 1***

0...1000 (0,0%...100,0% of output scale)

0

0x00CC

204 / 40205 RW

Forced value for analog output 2***

0...1000 (0,0%...100,0% of output scale)

0

0x00D3

211 / 40212 RW

Parameter tied to relay RE1

0 – none
1 – temperature
2 – gas concentration
9 – control by Modbus control, state set in MHR / 40214

2

0x00D4

212 / 40213 RW

Parameter tied to relay RE2

0 – none
1 – temperature
2 – gas concentration
9 – control by Modbus control, state set in MHR / 40215

2

0x00D5

213 / 40214 RW

Forced state for relay RE1***

0 – off, 1 – on

0

0x00D6

214/ 40215 RW

Forced state for relay RE2***

0 – off, 1 – on

0

0x00D7

215 / 40216 RW

Switching delay for relay RE1

0...1000 (s)

0

0x00D8

216 / 40217 RW

Switching delay for relay RE2

0...1000 (s)

0

0x00D9

217 / 40218 RW

Minimal on/off time for relay RE1

0...1000 (s)

0

0x00DA

218 / 40219 RW

Minimal on/off time for relay RE2

0...1000 (s)

0

* – The new value is applied after restart.
** – Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be

the only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.

*** – This value is dynamic and not kept in EEPROM after restart