Evikon PluraSens E2618-O2-L User Manual Download Page 4

E2618_UM_EN Annex 1. E2618 series Modbus holding registers (part 2)
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR RW

Description

Supported values (dec)

Default

0x00A2

162 / 40163 RW

Zero adjustment for temperature data, °C × 100

-32000...+32000 (-320,00...+320,00 °C)

0

0x00A5

165 / 40166 RW

Zero adjustment for gas data, ADC

-32000...+32000 ADC units

0

0x00A6

166 / 40167 RW

Slope adjustment for gas data

1...65535

512

0x00A7

167 / 40168 RW

Change rate limit for gas data, ppm (‰ for O

2

) / s

1...32000, 0 - no limit

0

0x00A8

168 / 40169 RW

Integrating filter time constant, s

1...32000 (seconds), 0 - no filter

0

0x00C9

201 / 40202 RW

Parameter tied to analog output 1

0 – none
1 – temperature
2 – gas concentration
9 – forced Modbus control, value set in MHR / 40204

2

0x00CA

202 / 40203 RW

Parameter tied to analog output 2

0 – none
1 – temperature
2 – gas concentration
9 – forced Modbus control, value set in MHR / 40205

0x00CB

203 / 40204 RW

Forced value for analog output 1***

0...1000 (0,0%...100,0% of output scale)

0

0x00CC

204 / 40205 RW

Forced value for analog output 2***

0...1000 (0,0%...100,0% of output scale)

0

0x00FF

255 / 40256 RW

Sensor, analog outputs, LED and buzzer status

bit[0]=0/1 –  sensor present/absent, read-only!
bit[1]=0/1 – analog outputs deactivated/activated
bit[2]=0/1 – in case the sensor is absent, turn signaling off/on analog output1
bit[3]=0/1 – in case the sensor is absent, turn on signaling with low current/high
current on analog output1; if bit[2]==0 this bit will be ignored
bit[4]=0/1 – in case of sensor absent, turn signaling off/on analog output2
bit[5]=0/1 – in case of sensor absent, turn on signaling with low current/high current
on analog output2; if bit[4]==0 this bit will be ignored
bit[6]=0/1 – current/voltage output detected on output1, read-only!
bit[7]=0/1 – current/voltage output detected on output2, read-only!
bit[8]=0/1 – LED deactivated/activated
bit[9]=0/1 – buzzer deactivated/activated (always 0 for E2618)

-

0x0100

256 / 40257

R

Raw temperature data, °C×100

signed integer, -4000...+8500 (-40,00...+85,00 °C)

0x0101

257 / 40258

R

Raw gas sensor data

ADC data 0...4095

0x0102

258 / 40259

R

Measured temperature, °C×100

signed integer, -4000...+12500 (-40,00...+125,00 °C)

0x0103

259 / 40260

R

Gas concentration, gas units

0...65535, gas units

0x0105

261 / 40262 RW

0% value for analog output 1

signed integer, -32000...+32000 (ppm / ‰)

0

0x0106

262 / 40263 RW

100% value for analog output 1

signed integer, -32000...+32000 (ppm / ‰)

1000

0x0107

263 / 40264 RW

0% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

0

0x0108

264 / 40265 RW 100% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

1000

* – The new value is applied after restart.
** – Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.
*** – This value is dynamic and not kept in EEPROM after restart

NOTE 1 

Sensor absense signalling (bits from [2] to [5]) is available only

for sensors with digital interface ( e.g.-CO2 10K, -O2-L).

NOTE 2

 We recommend to set the difference between the upper and

bottom limits of the output scale not narrower than 20% of detection
range (for CO detectors the scales down to 5% of range are
allowed). In any case, do not set the output scale below the tenfold
resolution of the device.

Reviews: