Evikon PluraSens E2611-HFC User Manual Download Page 2

RS485 communication interface 

Databits: 8 
Parity: none 
Stop bits: 1 or 2 
Protocol: Modbus RTU 

Supported Modbus functions: 
03 - read multiple registers 
06 - write single register 

Modbus registers (0-based, decimal format) 

Reg  Description 

Supported values 

1  Hardware version 

read only 

2  Software version 

read only 

3  Product serial number 

read only 

4  Slave ID (network address)*  

1...247, default 1 

5  Baud rate* 

1200...57600 baud, default 9600 

6  Response delay, ms 

1...255 ms, default 10 

7  Stop bits*  

1 / 2, default 1 

17   Restart  

write ‘42330’ for soft restart 

162  Temperature shift adjustment  -32000...+32000 T units (0,01 °C) 
165  Gas channel shift adjustment  -32000...+32000 gas units, default 0 
166  Gas channel slope adjustment  1...65535, default 512 
167  Output change rate limit  

1...32000 gas units/s, 0=no limit 

168  Integrating filter time constant   1...32000 s, 0=no, integrating filter 
201  Parameter assigned to OUT1  0=none, 1=T, 2=gas, 9=forced by 203 
202  Parameter assigned to OUT2  0=none, 1=T, 2=gas, 9=forced by 204 
203  Forced value for OUT1 

0...1000 (0.0...100.0% of full scale) 

204  Forced value for OUT2 

0...1000 (0.0...100.0% of full scale) 

211  Parameter assigned to RE1 

0=none, 1=T, 2=gas, 9=forced by 213 

212  Parameter assigned to RE2 

0=none, 1=T, 2=gas, 9=forced by 214 

213  Forced state for RE1 

0=off, 1=on (relay control by Modbus) 

214  Forced state for RE2 

0=off, 1=on (relay control by Modbus) 

215  Switch delay for RE1 

0...1000 s, default 0 

216  Switch delay for RE2 

0...1000 s, default 0 

217  Min on/off time for RE1 

0...1000 s, default 0 

218  Min on/off time for RE2 

0...1000 s, default 0 

219  Control logic for relay RE1 

0:_, 1:_↓↑

P, 2:

P↑↓_, 3:_↑

P↓_, 4:

P↓_↑

220  Control logic for relay RE2 

0:_, 1:_↓↑

P, 2:

P↑↓_, 3:_↑

P↓_, 4:

P↓_↑

221  LOW setpoint for relay RE1 

-32000...+32000, gas or T units 

222  HIGH setpoint for relay RE1 

-32000...+32000, gas or T units 

223  LOW setpoint for relay RE2 

-32000...+32000, gas or T units 

224  HIGH setpoint for relay RE2 

-32000...+32000, gas or T units 

258  Measured temperature 

-4000...+12500 T units (0,01 °C) 

259  Gas concentration 

0...65535 gas units 

261  0% value of OUT1 

-32000...+32000 gas units / integer °C 

262  100% value of OUT1 

-32000...+32000 gas units / integer °C 

263  0% value of OUT2 

-32000...+32000 gas units / integer °C 

264  100% value of OUT2 

-32000...+32000 gas units / integer °C 

 * - the new value is applied after restart 
Broadcast  ID=0  may  be  used  to  assign  a  new  ID  to  device  with  unknown  ID

 

 

E2611-HFC_UM_EN    

 

 

         Rev 19.11.2020 

Specifications 

Detected gases 

R-12,  R-123,  R-125,  R-134a,  R-143,  R-22,  
R-404a, R-407c, R-410a etc 

Default calibration 

R404a 

Sensor type  

Metal oxide semiconductor 

Sampling method 

Diffusion 

Detection range 

0...1000 ppm 

Resolution 

1 ppm 

Response time 

~ 15 seconds 

Sensor lifetime 

> 5 years 

Calibration interval 

12 months 

Warm-up time 

up to 1 minute, depending on unpowered period and 
atmosphere 

Load resistance 

for 4-20 mA output mode: R

L

 < (Us - 2V) / 22 mA 

for 0-10 V output mode: R

L

 > 250 kOhm 

Digital interface 

RS485, Modbus RTU protocol 

Power supply 

11...30 VDC, 24 VAC  
or 90...265 VAC (with mains power unit) 

Power consumption 

< 2 VA 

Analog outputs 

2 × 4-20 mA or 0-10 V 

Relay outputs 

2 × SPST, max 5 A, 30 VDC / 250 VAC 

Alarm signal 

Buzzer 85 dB 

Enclosure 

ABS plastic with ventilation slots, wall-mount,  
protection class IP20 

Dimensions 

85 × 85 × 37 mm 

Electromagnetic 
compatibility  

according to 2014/30/EU, 2014/35/EU and EN61321-
1 standard requirements 

Operating conditions 

-30...+70 °C  
<95 %RH, without condensation, non-ATEX 
Normal ambient oxygen level 
Avoid strong mechanical shock, vibrations or EMI 
Avoid exposure to corrosive gases or silicone 
containing products 

Factory settings 

Target gas 

R404a 

Gas units 

ppm 

OUT1 assignment and scale 

2: gas, 0 - 1000 

OUT2 assignment and scale 

2: gas, 0 - 1000 

RE1 assignment and logic 

2: gas, 1: on at high values 

RE1 HIGH set point (set) 

100 

RE1 LOW set point (release) 

80 

RE2 assignment and logic 

2: gas, 1: on at high values 

RE2 HIGH set point (set) 

500 

RE2 LOW set point (release) 

400 

 
 

Evikon MCI OÜ    Teaduspargi 7, Tartu, [email protected], Tel +372 733 6310     
50411 Estonia,  

www.evikon.eu

 
 
 
   