background image

E2608-NH3-P

Rev 27.07.2022

Installation guidelines

Before proceeding with the installation it is mandatory to read the Safety requirements
section and make sure to comply with all listed instructions. Installation standards EN
60079-29-2 and EN 45544-4 are also recommended for further instructions and related
information about the installation. During the installation of the detector-transmitter the
following points must be considered:

Application (air quality control or leakage detection)

Properties of the space under investigation (room geometry, direction, and
velocity of airflows, etc.),

Ammonia is lighter than air, so the sensor should be placed higher than the
potential leakage or formation source.

The device should be accessible for maintenance and repair.

The aforementioned conditions above will affect the coverage area of the device. however,
the coverage area for a detector-transmitter is usually between 2.5 to 5 meters radius.

For early leakage detection install the sensor as close as possible to the potential leakage
sources (flanges, valves, pressure reducers, pumps, etc.), taking into consideration other
points listed above.

For general area monitoring without definite leakage sources, the detector-transmitters
should be distributed evenly in the room.

For personal safety control, the detector-transmitters are installed in the breathing zone (at
the height of the head of people or animals). The recommended sensor position is vertical,
pointing downwards.

Wall mount version

Attach the mounting lugs to the back of the detector-transmitter using the provided
screws. Screw the device to the wall through the mounting lug holes (for dimensions see
the drawing in the next section).

Duct mount version

Cut a hole with a diameter of 36...45 mm in the air duct at the chosen mounting place.
Place the rubber flange aligning the holes in the flange and the air-duct and fix the flange
with four self-tapping screws. Pass the sensor probe through the flange and adjust it to the
appropriate depth. Unscrew four lid screws and detach the lid from the
detector-transmitter.

7

Summary of Contents for PluraSens E2608-NH3-P

Page 1: ...PluraSens Ammonia Detector Transmitter E2608 NH3 P User Manual...

Page 2: ...Sensor probe handling 9 Gas sensor replacement procedures 9 Electrical connections 10 Correct and incorrect cabling for 24 VAC 12 Operation 13 Maintenance 13 Calibration 13 Delivery set 14 Order code...

Page 3: ...emical formula NH3 Molar weight 17 Relative gas density to air 0 59 Conversion 1 ppm 0 70 mg m3 Boiling point 33 3 C Low explosive limit LEL vol in air 15 Upper explosive limit UEL vol in air 28 Odor...

Page 4: ...olation Analog outputs 2 4 20 mA 0 10 V user settable Outputs assignment OUT1 Gas OUT2 Gas Output scale width 10 resolution Recommended 20 100 of the detection range Analog output scale can be set acc...

Page 5: ...as Normal ambient oxygen level Avoid strong mechanical shock vibrations or EMI Avoid exposure to corrosive gases or silicone containing products Other options Remote probe Protection IP65 default cabl...

Page 6: ...to the safety provisions applicable in the country of use Do not perform any maintenance operation with the power on Do not let water or foreign objects inside the device Removal of the PCB from the e...

Page 7: ...ius For early leakage detection install the sensor as close as possible to the potential leakage sources flanges valves pressure reducers pumps etc taking into consideration other points listed above...

Page 8: ...E2608 NH3 P Rev 27 07 2022 Mounting dimensions Wall mount version with mounting lugs Duct mount version 8...

Page 9: ...or head cap and remove the old filter Place a new filter into the cap and tighten it again NOTE Never stab or press the filter near its center where the sensor is located since this may damage the sen...

Page 10: ...connection diagram below connect the analog outputs and digital interface terminals to the relevant devices according to your tasks Version without PSU Version with PSU Jumpers J1 OUT1 type open 4 20...

Page 11: ...A and B on the device represent DATA and DATA respectively polarity must be respected when connecting to an external RS485 network Both analog outputs can be independently changed between 4 20 mA and...

Page 12: ...E2608 NH3 P Rev 27 07 2022 Correct and incorrect cabling for 24 VAC 12...

Page 13: ...rt on off pulses Normal operating measurement Continuously on or off Make sure that the detector transmitter is properly mounted the external devices connected power LED green on and the control LED r...

Page 14: ...flange for Remote probe option Fixing clamp for Remote probe option Order code for E2608 NH3 P options E2608 options Order code Remote probe 3 m cable E2608 NH3 P RP33 3 Remote probe 10 m cable E2608...

Page 15: ...parameter Flexible setting of analog output scales for each output Output zero and slope adjustment for calibration Free assignment of each of two relays to the chosen parameter Several relay control...

Page 16: ...ple registers 06 Write a single register Error codes 01 Illegal function 02 Illegal data address 03 Illegal data value 04 Slave device failure details of last error 04 can be read from register 0x0008...

Page 17: ...Description Supported values dec Default 0x00A5 165 40166 RW Zero adjustment for gas data ADC 32000 32000 ADC units 0 0x00A6 166 40167 RW Slope adjustment for gas data 1 65535 512 0x00A7 167 40168 RW...

Page 18: ...RE1 0 1000 s 0 0x00D8 216 40217 RW Switching delay for relay RE2 0 1000 s 0 0x00D9 217 40218 RW Minimal on off time for relay RE1 0 1000 s 0 0x00DA 218 40219 RW Minimal on off time for relay RE2 0 10...

Page 19: ...aling off on analog output1 bit 3 0 1 in case the sensor is absent turn on signaling with low current high current on analog output1 if bit 2 0 this bit will be ignored bit 4 0 1 in case of sensor abs...

Page 20: ...x0107 263 40264 RW 0 value for analog output 2 32000 32000 gas units User defined 0x0108 264 40265 RW 100 value for analog output 2 32000 32000 gas units User defined The new value is applied after re...

Page 21: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Man...

Reviews: