E2608-LEL
Rev 08.01.2021
21
state set in MHR / 40214
0x00D4 212 / 40213 RW Parameter tied to relay
RE2
0 – none
2 – gas concentration
9- – control by Modbus
control, state set in MHR /
40215
2
0x00D5 213 / 40214 RW Forced state for relay
RE1***
0 –off, 1 – on
0
0x00D6 214/ 40215 RW Forced state for relay
RE2***
0 – off, 1 – on
0
0x00D7 215 / 40216 RW Switching delay for relay
RE1
0...1000 (s)
0
0x00D8 216 / 40217 RW Switching delay for relay
RE2
0...1000 (s)
0
0x00D9 217 / 40218 RW Minimal on/off time for
relay RE1
0...1000 (s)
0
0x00DA 218 / 40219 RW Minimal on/off time for
relay RE2
0...1000 (s)
0
Addr
Reg /
MHR RW Description Supported values (dec)
Default
0x00DB
219 /
40220
RW
Control
logic for
relay RE1
0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within the range
4 – relay on for the values out of the range
0
0x00DC
220 /
40221 RW
Control
logic for
relay RE2
0 – none
1 – relay on at high values
2 – relay on at low values
3 – relay on at values within the range
4 – relay on for the values out of the range
0
0x00DD
221 /
40222
RW
LOW
setpoint for
relay RE1
0...65535 (gas units)
see
Specifications