E2418DP
Rev 27.05.2021
263 RW**
0% value of analog OUT2
-32000...+32000 pressure units
264 RW**
100% value of analog OUT2
-32000...+32000 pressure units
* - the new value is applied after restart.
** - the new value is applied immediately.
*** -writing 42330 restarts the device immediately, no response on Modbus.
Broadcast ID=0 may be used to assign a new ID to a device with unknown ID.
RS485 Communication parameters
Parameter
Permitted values
Default
Supported baud rates 1200, 2400, 4800, 9600, 19200, 38400, 57600
9600
Data bits
8
8
Parity
none / odd / even
none
Stop bits
1, 2
1
Protocol
Modbus RTU
Modbus functions
03 - Read multiple registers
06 - Write a single register
Error codes
01 – Illegal function
02 – Illegal data address
03 – Illegal data value
04 – Slave device failure
(details of last error 04 can be read from register 0x0008)
Factory settings
Pressure unit
depending on the range
OUT1 parameter and scale
2: pressure, scale set by user
OUT2 parameter and scale
2: pressure, scale set by user