E2618 series Modbus holding registers (continued)

Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

0x00A2

162 / 40163 RW

Zero adjustment for temperature

-32000...+32000 (-320,00...+320,00 °C)

0

0x00A5

165 / 40166 RW

Zero adjustment for gas data, ADC

-32000...+32000 ADC units

0

0x00A6

166 / 40167 RW

Slope adjustment for gas data

1...65535

512

0x00A7

167 / 40168 RW

Change rate limit for gas data,

1...32000, 0 - no limit

0

0x00A8

168 / 40169 RW

Integrating filter time constant, s

1...32000 (seconds), 0 - no filter

0

0x00C9

201 / 40202

RW

Parameter tied to analog output 1

0-none
1- temperature
2- gas concentration

9- forced Modbus control, value set in MHR / 40204

2

0x00CA

202 / 40203

RW

Parameter tied to analog output 2

0-none
1- temperature
2- gas concentration

9- forced Modbus control, value set in MHR / 40205

2

0x00CB

203 / 40204

RW

Forced value for analog output 1***

0...1000 (0,0%...100,0% of output scale)

0

0x00CC

204 / 40205

RW

Forced value for analog output  2***

0...1000 (0,0%...100,0% of output scale)

0

0x00FF

255 / 40256

RW

Sensor and analog outputs status

bit[0]=0/1 - sensor present/absent, read-only!
bit[1]=0/1 - analog outputs deactivated/activated,
bit[2]= 0/1 - in case of sensor absent, turn signaling off/on analog output1,

bit[3]=0/1 - in case of sensor absent, turn on signaling with low current/high current
on analog output1; if bit[2]==0 this bit will be ignored,
bit[4]=0/1 - in case of sensor absent, turn signaling off/on analog output2

bit[5]=0/1 - in case of sensor absent, turn on signaling with low current/high current
on analog output2; if bit[4]==0 this bit will be ignored,
bit[6]=0/1 - current/voltage output detected on output1, read-only!

bit[7]=0/1 - current/voltage output detected on output2, read-only!
bit[8]=0/1 - LED deactivated/activated,
bit[9]=0/1 - buzzer deactivated/activated,

Note

 bits [8] and [9] are always 0 for E2618 series

62d

0x0100

256 / 40257

R

Raw temperature data, °C×100

signed integer, -4000...+8500 (-40,00...+85,00 °C)

-

0x0101

257 / 40258

R

Raw gas sensor data

ADC data 0...4095

-

0x0102

258 / 40259

R

Measured temperature, °C×100

signed integer, -4000...+12500 (-40,00...+125,00 °C)

-

0x0103

259 / 40260

R

Gas concentration, ppm / ‰

signed integer, -32000...+32000 (ppm / ‰)

-

0x0105

261 / 40262

RW

0% value for analog output 1

signed integer, -32000...+32000 (ppm / ‰)

0

0x0106

262 / 40263

RW

100% value for analog output 1

signed integer, -32000...+32000 (ppm / ‰)

1000

0x0107

263 / 40264

RW

0% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

0

0x0108

264 / 40265

RW

100% value for analog output 2

signed integer, -32000...+32000 (ppm / ‰)

1000

* - The new value is applied after restart.
** - Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the
only Modbus instrument in the network. The device will not respond to Master command when addressed by ID 0.
*** - This value is dynamic and not kept in EEPROM after restart