Evikon E2610-HFC User Manual Download Page 7

E2610-HFC

Rev 24.03.2021

Installation guidelines

There are no precise rules or standards to follow when installing gas detectors. The
following points must be taken into account:

Application (air quality control or leakage detection)

Properties of the space under investigation (room geometry, direction, and
velocity of airflows, etc.),

Halocarbons are heavier than air and tend to sink. The sensor should be placed
near the floor.

The device should be accessible for maintenance and repair.

The aforementioned conditions above will affect the coverage area of the device. however,
the coverage area for a detector is usually between 2.5 to 5 meters radius.

For early leakage detection install the sensor as close as possible to the potential leakage
sources (flanges, valves, pressure reducers, pumps, etc.), taking into consideration other
points listed above.

For general area monitoring without definite leakage sources, the detector should be
distributed evenly in the room.

Do not locate the detector close to ventilation openings and strong air currents. Avoid the
areas without air circulation (corners, niches) as well.

For personal safety control, the detectors are installed in the breathing zone (at the height
of the head of people or animals). The recommended sensor position is vertical, pointing
downwards.

7

Summary of Contents for E2610-HFC

Page 1: ...Refrigerant Detector E2610 HFC User Manual...

Page 2: ...3 Specifications 5 Product description 6 Safety requirements 6 Operating conditions 6 Installation guidelines 7 Connections 8 Operation 10 Maintenance 10 Calibration 10 Delivery set 11 Order code for...

Page 3: ...e environment Now hydrofluorocarbons are the most commonly used halocarbon refrigerants Hydrofluoroolefins HFO is the last generation of refrigerants more environmentally friendly than HFCs but modera...

Page 4: ...21 asphyxiation in confined spaces At higher temperatures 250 C decomposition products may include hydrofluoric acid HF and carbonyl halides An escape of refrigerant through a leak may damage the refr...

Page 5: ...tal interface UART Relay outputs 2 SPDT max 5 A 30 VDC 250 VAC Alarm Buzzer 85 dB Enclosure ABS plastic with ventilation slots wall mount protection class IP20 Dimensions H85 W85 D37 mm CE marking Acc...

Page 6: ...uch the electronic components directly as they are sensitive to static electricity Connection diagrams can be found in the connections section The device might not perform correctly or be damaged if t...

Page 7: ...a of the device however the coverage area for a detector is usually between 2 5 to 5 meters radius For early leakage detection install the sensor as close as possible to the potential leakage sources...

Page 8: ...f the enclosure by gently pulling along four guiding pins 2 Attach the base to the wall with two screws see drawings below 3 Use rounded cutouts on the side of the base to let in the cables from the p...

Page 9: ...10 series devices are suitable for a wide range of wires with cross section 0 2 1 5 mm2 We recommend to strip the wire end by 5 6 mm and tin it or to use the wire end sleeves To connect the wire loose...

Page 10: ...w 70 of the LOW alarm setpoint If the gas level exceeds the HIGH alarm setpoint the bottom red LED starts flashing and the buzzer starts beeping at a rate of 2 Hz and also the relay RE2 switches over...

Page 11: ...Detector E2610 HFC Mounting accessories 2 screws and 2 plastic dowel plugs Order code for E2610 HFC options E2610 options Order code Integrated 90 265 V mains power supply module E2610 HFC 230 Integra...

Page 12: ...Manufacturer will at its option either repair or replace a product that proves to be defective This warranty is void if the product has been operated in conditions outside ranges specified by the Manu...

Reviews: