E2610-CO
Rev 28.10.2020
For easier connection, terminal blocks of E2610 series devices are removable. To
dismount the terminal block, pull it off from the PCB. Connect the power terminals N and L
to the 24 V AC/DC source if you are using detector version -24 or to 230 V AC mains if you
are using detector version -230 (see diagram below).
The terminals on the E2610 series devices are suitable for a wide range of wires with
cross-section 0,2...1,5 mm
2
. We recommend to strip the wire end by 5...6 mm and tin it, or
to use the wire end sleeves. To connect the wire, loosen the screw, insert the wire end into
the terminal hole and tighten the screw.
Connect external devices. Relay switch-over outputs may be used to control directly 24 V
or 230 V (for versions -24 and -230 respectively) powered alarm sirens, ventilation fans,
shut-off valves, or other actuators. Attach terminal blocks to the board.
4. Push enclosure to the base.