Evikon E2608-CO2-10K User Manual Download Page 3

E2608_UM_EN. Annex 1. E2608 series Modbus RTU Communication Reference

RS485 communication interface

Databits: 8
Parity: none
Stop bits: 1 or 2
Protocol: Modbus RTU

Supported Modbus functions:
03 - read multiple registers
06 - write single register

Communication parameters

Parameter

Permitted values

Default

Supported
baudrates

1200, 2400, 4800, 9600, 19200,
38400, 57600

9600

Data bits

8

8

Parity

none

none

Stop bits

1, 2

1

Protocol

Modbus RTU

Modbus functions

03 – read multiple registers
06 – write single register

Error codes

01 – illegal function
02 – illegal data address
03 – illegal data value
04 – slave device failure (details of last error 04
can be read from register 0x0008)

E2608 series Modbus holding registers
Register addresses are shown 0-based, Addr in hexadecimal, Reg in decimal format.
Modbus holding register numbers MHR are shown in decimal 1-based format, and may be addressed either from 00001 or 40001 base.

Addr

Reg / MHR RW

Description

Supported values (dec)

Default

0x0001

1 / 40002

R

Hardware version

-

0x0002

2 / 40003

R

Software version

-

0x0003

3 / 40004

R

Product serial number

1...65535

-

0x0004

4 / 40005

RW

Slave ID (net address) *

1...247 **

1

0x0005

5 / 40006

RW

Baudrate *

1200, 2400, 4800, 9600, 19200, 38400, 57600

9600

0x0006

6 / 40007

RW

Response delay, ms

1...255

10

0x0007

7 / 40008

RW

Stop bits, parity bit *

1 – no parity bit, 1 stop bit (default after factory reset)
2 – no parity bit, 2 stop bits
3 – odd parity, 1 stop bit
4 – even parity, 1 stop bit
NOTE

: 3 and 4 are available starting from the Sofrware version 0x218 (dec. 536)

1

0x0008

8 /40009

R

Last error code

1...255

-

0x0011

17 / 40018

RW

Technological: age of data in seconds (read) /
restart(write)

0...65535 s (read), 42330(write)
writing 42330 restarts the device, response on Modbus will follow,1.5 seconds should
be waited for restart to be completed in every case

-

* — The new value is applied after restart.
** — Broadcast slave ID 0 can be used to assign a new ID to device with unknown ID. When addressing by ID 0 the device shall be the only Modbus instrument in the network.
The device will not respond to Master command when addressed by ID 0.
*** — This value is dynamic and not kept in EEPROM after restart

Summary of Contents for E2608-CO2-10K

Page 1: ...ies 4 cross shaped mounting lug with screws and 4 screws with plastic dowels for wall mount version rubber flange for duct mount version fixing clamp for remote probe versions E2608 CO2 10K_UM_EN Rev 11 07 2019 Specifications Sensor type optical NDIR Sampling method diffusion Detection range 0 10 000 ppm Resolution digital unit 1 ppm Accuracy 50 ppm 3 of reading in the range 300 5000 ppm Response ...

Page 2: ...nections via RS485 interface should not exceed 1200 m Note The outputs are not galvanically isolated from 24 V power supply and share common 0V Allowed load resistance limits are stated in Specifications table To power the instrument from an external 24 VDC source connect terminals 0V and U to the source If the integrated mains power supply module is used connect terminals L and N to the mains Not...

Page 3: ...dec Default 0x0001 1 40002 R Hardware version 0x0002 2 40003 R Software version 0x0003 3 40004 R Product serial number 1 65535 0x0004 4 40005 RW Slave ID net address 1 247 1 0x0005 5 40006 RW Baudrate 1200 2400 4800 9600 19200 38400 57600 9600 0x0006 6 40007 RW Response delay ms 1 255 10 0x0007 7 40008 RW Stop bits parity bit 1 no parity bit 1 stop bit default after factory reset 2 no parity bit 2...

Page 4: ...t in MHR 40205 2 0x00CB 203 40204 RW Forced value for analog output 1 0 1000 0 0 100 0 of output scale 0 0x00CC 204 40205 RW Forced value for analog output 2 0 1000 0 0 100 0 of output scale 0 0x00D3 211 40212 RW Parameter tied to relay RE1 0 none 1 temperature 2 gas concentration 9 control by Modbus control state set in MHR 40214 2 0x00D4 212 40213 RW Parameter tied to relay RE2 0 none 1 temperat...

Page 5: ... 1 1 Hz 50 on 50 off LED signal off on if relay1 turned on bit 12 0 1 2 Hz 50 on 50 off LED signal off on if relay2 turned on user defined 0x0100 256 40257 R Raw temperature data C 100 signed integer 4000 8500 40 00 85 00 C 0x0101 257 40258 R Raw gas sensor data ADC data 0 4095 0x0102 258 40259 R Measured temperature C 100 signed integer 4000 12500 40 00 125 00 C 0x0103 259 40260 R Gas concentrati...

Reviews: