32
CONNECTIONS – PLUMBING
All plumbing work must be carried out by a qualified person and in compliance
with the Standard AS/NZS 3500.4 and all local codes and regulatory authority
requirements.
All gas work must be carried out by a qualified person and in compliance with
the Standard AS 5601 or AS/NZS 5601.1, as applicable under local
regulations, and all local codes and regulatory authority requirements. In New
Zealand, the installation must also conform with NZS 5261, as applicable under
local regulations.
CONNECTION SIZES
Hot water connection:
RP¾/20
Cold water connection:
RP¾/20
Relief valve connection:
RP½/15
Gas inlet:
RP½/15 flared compression
Gas regulator (propane models):
RP½/15 flared compression
WATER INLET AND OUTLET
All pipe work must be cleared of foreign matter before connection and purged
before attempting to operate the water heater. All olive compression fittings
must use brass or copper olives. Use thread sealing tape or approved thread
sealant on all fittings.
An isolation valve and non return valve
must be installed on the cold water line
to the water heater. An acceptable
arrangement is shown in the diagram.
Refer also to
page 25 and to
on page 26.
A disconnection union must always be provided at the cold water inlet and hot
water outlet on the water heater to allow for disconnection of the water heater.
This water heater has either a plastic dip tube or fitting
liner in the inlet and outlet fittings (see diagram). These
must be in place for the water heater to function
properly. Do not remove or damage them by using heat
nearby. They will be pushed into the correct position as
the fitting is screwed in.