EVER EASYLINE AVR USB UPS Range Operating Manual
Type 02
2017-01-27 12:25
Technical Service, tel.: +48 61 6500 400
www.ever.eu
22
TECHNICAL PARAMETERS
PARAMETERS \ TYPE
EASYLINE 650 AVR USB
EASYLINE 850 AVR USB
EASYLINE 1200 AVR USB
Part number
T/EASYTO-000K65/00
T/EASYTO-000K85/00
T/ EASYTO-001K20/00
Output Power (Apparent / Active)
1)
650 VA
360 W
850 VA
480 W
1200 VA
600 W
GENERAL DATA AND ENVIRONMENTAL
Topology
VI (line interactive)
Number of phases (in/out)
1 / 1
Housing Type
Tower
Operating temperature
2)
0 ÷ + 40 °C
Storage temperature
0 ÷ + 40 °C
Relative humidity during operation
0 ÷ 90 % (non-condensing)
Relative humidity during storage
0 ÷ 90 % (non-condensing)
Operating elevation
3)
< 2000 m
Protection level
IP20
Environment of installation
Office / industrial rooms with low level of pollution
Cooling
Gravity
INPUT
Rated input voltage
230 V AC
Input voltage range and tolerance
170 ÷ 280 V AC ± 7 %
Input voltage rated frequency
50 Hz
Input voltage frequency range and tolerance
45 ÷ 55 Hz ± 1 Hz
Transfer thresholds: Mains – UPS
170 ÷ 280 V AC ± 7 %
OUTPUT
Rated output voltage
230 V AC
Output voltage range and tolerance - normal
mode
230 V AC ± 10 %
Output voltage range and tolerance - battery
mode
230 V AC ± 10 %
Automatic Voltage Regulation (AVR)
+/- 10%
Shape of output voltage (battery mode /
normal mode)
Stepped approximation of sine wave / Same as input
Output voltage rated frequency
50 Hz
Output frequency range and tolerance – mains
operation mode
Synchronously
Output frequency range and tolerance –
battery mode
50 Hz ± 1Hz
Output voltage filtering
RC
Transfer thresholds: UPS– Mains
176 V ÷ 274 V AC ± 7 %
Transfer time to battery mode
< 6 ms
Transfer time to normal mode
0 ms
BATTERIES AND TYPICAL RUNTIME
Internal Batteries
12 V / 7 Ah VRLA
12 V / 9 Ah VRLA
12 V / 7 Ah VRLA
Number of internal batteries
1
1
2
Maximum overall internal batteries capacity
7 Ah
9 Ah
7 Ah
Backup time – internal batteries (80 % / 50 %
Pmax)
2 / 8 min
2 / 6 min
4,5 / 11 min
Nominal voltage DC circuit
12 V DC
12 V DC
24 V DC
Internal batteries maximum charging time –
after discharging at 80 % Pmax *
6 h
Summary of Contents for EASYLINE AVR USB