Evco S.p.A. • Code 104K614E00 • page 3/7
5.7.2
The slowing phase
During the slowing phase:
• compressor activity mainly depends on the SEt4, rC0 and rC5 pa-
rameters and that of the resistances from the SEt4, rH0 and rH4 pa-
rameters
• the evaporator fan activity depends mainly on parameter F4
• the activity of the humidifier mainly depends on parameters Ur4,
rU2 and rU3 (the rU3 parameter establishes the duration of humidi-
fier switch-on, in the course of time rU2, such to cause 100% relative
humidity). If the temperature of the room falls below that established
with parameter rU1, humidification will not be available
• defrosting is never activated
• the LEDs
,
, and
are on.
The slowing phase lasts until the cycle is interrupted by pressing the
for 4 s.
6
HEATING MANUAL CYCLE
6.1 Start/stop of the heating manual cycle
To start the cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press
: the display will show the first label available
• press
or
within 15 s to select “
Hot
”
• press
within 15 s: the display will show “
Go
”
• press
within 15 s: the LED
will switch on and the cycle will
be started.
To stop the cycle:
• press
for 4 s.
6.2.1
Modifying the settings of the heating manual
cycle
To set the duration of the heating manual cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press
: the display will show the first label available
• press
or
within 15 s to select “
Hot
”
• press
within 15 s: the display will show “
hh
” followed by the
two numbers regarding the hours and the LED
will
switch on
• press
or
within 15 s
• press
within 15 s: the display will show “
nn
” followed by the
two numbers regarding the minutes
• press
or
within 15 s.
To set the work set-point during the heating manual cycle:
• press
during the modification of the duration of the heating
manual cycle (i.e. during modification of the minutes): the
display will show “
SEt
” for 1 s after which the value is
shown
• press
or
within 15 s; parameters rH1and rH2 are also
seen.
It is also possible to set the heating manual cycle work set-point via the
SEt5 parameter.
To set the percentage relative humidity during the heating manual
cycle:
• press
during the modification of the work set-point during the
heating manual cycle: the display will show “
Ur
” for 1 s
after which the value is shown
• press
or
within 15 s; parameters rU3, rU5 and rU6 are
also seen.
• press
within 15 s: the display will show “
Hot
” again.
It is also possible to set the percentage of relative humidity during the
heating manual cycle via the Ur5 parameter.
To go back to previous levels:
• press
during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
6.2.2
The heating manual cycle
During the heating manual cycle:
• the activity of the resistances depends mainly on parameters SEt5,
rH0 and rH3
• the compressor stays off
• the evaporator fan activity depends mainly on parameter F3
• the activity of the humidifier mainly depends on parameters Ur5,
rU2 and rU3 (the rU3 parameter establishes the duration of humidi-
fier switch-on, in the course of time rU2, such to cause 100% relative
humidity). If the temperature of the room falls below that established
with parameter rU1, humidification will not be available.
• defrosting is never activated
• the LED
is on.
The heating manual cycle lasts until it is interrupted by pressing the
for 4 s. When the duration of the heating manual cycle has ended,
the buzzer is activated for the time established with parameter dur5.
7
COOLING MANUAL CYCLE
7.1 Start/stop of the cooling manual cycle
To start the cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press
: the display will show the first label available
• press
or
within 15 s to select “
Cold
”
• press
within 15 s: the display will show “
Go
”
• press
within 15 s: the LED
will switch on and the cycle will
be started.
To stop the cycle:
• press
for 4 s.
7.2.1
Modifying the settings of the cooling manual
cycle
To set the work set-point during the cooling manual cycle:
• make sure that the instrument is in stand-by and that there is no
procedure in progress
• press
: the display will show the first label available
• press
or
within 15 s to select “
Cold
”
• press
within 15 s: the display will show “
SEt
” for 1 s after which
the value is shown
• press
or
within 15 s; parameters rC1 and rC2 are also
seen.
• press
within 15 s: the display will show “
Cold
” again.
It is also possible to set the heating manual cycle work set-point via the
SEt6 parameter.
To go back to previous levels:
• press
during modification of the values.
To exit the procedure:
• do not operate for 15 s (any modifications will be saved).
7.2.2
The cooling manual cycle
During the cooling manual cycle:
• the activity of the compressor depends mainly on parameters SEt6,
rC0 and rC4
• the resistances remain off
• the evaporator fan activity depends mainly on parameter F0
• the humidifier remains off
• defrosting can be activated
• the LED
is on.
The cooling manual cycle lasts until it is interrupted by pressing the
for 4 s.
8
USER INTERFACE
8.1 Preliminary considerations
The following functioning states exist:
• the “on” status (the instrument is powered and a functioning cycle
is in progress: the regulators can be switched on)
• the “stand-by” status (the instrument is powered but no functioning
cycle is in progress: the regulators are off)
• the “off” status (the instrument is not powered).
Successively, the term “switch-on” means the passage from the stand-
by status to the on status; the term “switch-off” means the passage from
the on status to the stand-by status.
If the power supply is shut-off during the stand-by status, the same
status will be proposed again when the power supply is restored.
If the power supply is shut-off during the on status, instrument function-
ing will depend on parameter P6 when the power supply is restored.
8.2 The display
If the instrument is on, during normal functioning the display will
show the size established via parameter P4:
• if P4 = 0, the display will show the temperature of the room if a
functioning cycle is in progress and will be off if the instrument is in
stand-by
• if P4 = 1, the display will show the end time of the provering phase
if a functioning cycle is in progress and will be off if the instrument
is in stand-by
• if P4 = 2, the display will show the temperature of the room (for 3 s)
alternating with the end time of the provering phase (for 1 s) if a
functioning cycle is in progress and will be off if the instrument is in
stand-by
• if P4 = 3, the display will show the temperature of the room if a
functioning cycle is in progress and the real time if the instrument is
in stand-by
• if P4 = 4, the display will show the end time of the provering phase
if a functioning cycle is in progress and the real time if the instrument
is in stand-by
• if P4 = 5, the display will show the temperature of the room (for 3 s)
alternating with the end time of the provering phase (for 1 s) if a
functioning cycle is in progress and the real time if the instrument is
in stand-by.
8.3 Displaying the room temperature
• make sure that no procedure is in progress
• press
for 1 s: the display will show the first label available
• press
or
to select “
Pb1
”
• press
To exit the procedure:
• press
or do not operate for 60 s
• press
or
until the display shows the size established via
parameter P4 or do not operate for 60 s.
Alternatively:
• press
8.4 Displaying the evaporator temperature
• make sure that no procedure is in progress
• press
for 1 s: the display will show the first label available
• press
or
to select “
Pb2
”
• press
To exit the procedure:
• press
or do not operate for 60 s
• press
or
until the display shows the size established via
parameter P4 or do not operate for 60 s.
Alternatively:
• press
If the evaporator probe is absent (parameter P3 = 0), the “
Pb2
” label
will not be displayed.
8.5 Displaying the end time and date of the provering
phase
• make sure that an automatic cycle is in progress and no procedure
is in progress
• press
for 1 s: the display will show the first label available
• press
or
to select “
End
”
• press
: the display will show the following in succession:
- the conclusion time of the provering phase (e.g. “
02:00
”)
- “
dd
” followed by the two numbers of the day of conclusion of the
provering phase (e.g. “
dd26
”)
- “
MM
” followed by the two numbers of the end month of the
provering phase (e.g. “
MM03
”)
To exit the procedure:
• press
or do not operate for 60 s
• press
or
until the display shows the size established via
parameter P4 or do not operate for 60 s.
Alternatively:
• press
If a heating or cooling manual cycle is in progress, the “
End
” label will
not be displayed.
The end time of the provering phase is displayed in the 24 hour format
(hours: minutes).
In the example, the provering phase will be concluded at 02:00 on
26 March. the display will show all information for 1 s.
If parameter P9 is set at 0, the display will only show the conclusion
time of the provering phase.