Consequences:
• all outputs will be deactivated

H-t

For EVC30S40J7XXX02 / 03 / 04 / 05.
use temperature alarm
Solutions:
• press 

B2

 to display the use temperature

• see parameters P14 and P15
Consequences:
• all outputs will be deactivated

When the cause of the alarm has disappeared, the instrument restores
normal functioning, except for the use temperature alarm
(code “

H-t

”), which requires the 

B1

 key to be pressed or the encoder

button). This switches the instrument off.

13

INTERNAL DIAGNOSTICS

13.1

Internal diagnostics

CODE MEANING

AL1

For EVC30S40J7XXX00 / 01.
chamber probe error
Solutions:
• check that the probe is a J thermocouple
• check the integrity of the probe
• check the instrument-probe connection
• verify the chamber temperature
Main consequences:
• the temperature regulation output will be deactivated

AL1

For EVC30S40J7XXX02 / 03 / 04 / 05 (if parameter P3 is set
at 0).
top probe error
Solutions:
• the same as the previous case but relative to the top probe
Main consequences:
• the top output will be deactivated
For EVC30S40J7XXX02 / 03 / 04 / 05 (if the parameter P3
is set at 1).
chamber probe error
Solutions:
• the same as the previous case but relative to the chamber

probe

Main consequences:
• the top output and the floor output will be deactivated

AL2

For EVC30S40J7XXX02 / 03 / 04 / 05 (if parameter P3 is set
at 0).
floor probe error
Solutions:
• the same as the previous case but relative to the floor

probe

Main consequences:
• the floor output will be deactivated

When the causes of the alarm have disappeared, the instrument will
go back to normal functioning.

14

TECHNICAL DATA

14.1

Technical data

With reference to the model with most hardware.

Container:

 open frame board

Front panel protection rating:

 IP 00.

Connections:

 6.3 mm faston (0.248 in, power supply and outputs),

screw terminal board (measurement inputs), 4-pole connector (to the
encoder).

Temperature of use:

from 0 to 55 

°

C (from 32 to 131 

°

F,

10 ... 90% relative humidity without condensate).

Power supply:

 230 Vac, 50/60 Hz, 1.5 VA.

Alarm buzzer:

 incorporated.

Measurement inputs:

 2 for J thermocouple; the instrument also

incorporates a sensor for the detection of the use temperature.

Range of measurement:

from 20 to 500 

°

C (from 99 to 999 

°

F).

Resolution:

 1 

°

C/1 

°

F.

Digital outputs:

 2 5 A res. relays @ 250 Vac (NO).

Summary of Contents for EVC30S40

Page 1: ... regulation The output activity depends mainly on the temperature of the chamber the work set point and the parameter P5 Top If functioning with 1 measurement input parameter P3 1 the out put is measured in a cyclical mode preferably when the floor output is off the parameter P10 establishes the cycle time Using the procedure given in paragraph 6 2 1 it is possible to set the duration of output sw...

Page 2: ...g the floor set point For EVC30S40J7XXX02 if the parameter P3 is set at 0 make sure that the instrument is in on status and that no procedure is in progress press B5 the display shows the corresponding value and the L2 LED will flash press B2 or B5 within 15 s see also parameters P5 P6 and P8 do not operate for 15 s the L2 LED will switch off and the instrument will exit the procedure To exit the ...

Page 3: ...2 the L1 LED switches off and the L2 LED will flash press B2 or B5 within 15 s see also parameters P6 P7 and P8 press B1 the display will show the time t3 the L2 LED switches off and the L3 LED will flash press B2 or B5 within 15 s see also parameters P3 P4 and P5 press B1 the instrument will exit the procedure and L3 LED will switch off To exit the procedure in advance do not operate for 15 s any...

Page 4: ... deactivated For EVC30S40J7XXX02 03 04 05 if the parameter P3 is set at 1 chamber probe error Solutions the same as the previous case but relative to the chamber probe Main consequences the top output and the floor output will be deactivated AL2 For EVC30S40J7XXX02 03 04 05 if parameter P3 is set at 0 floor probe error Solutions the same as the previous case but relative to the floor probe Main co...

Page 5: ...t differential if P3 0 minimum top set point and floor set point if P3 1 minimum work set point firmware code 3 time t3 maximum value enabling of the use temperature alarm code H t 1 YES duration of auxiliary output switch on see also P7 if P3 0 maximum top set point and floor set point if P3 1 maximum work set point firmware version code 3 time t2 predefined value temperature over which the use t...

Page 6: ...dified DESCRIPTION predefined value of the power supplied at the floor percentage of P10 only if P3 1 see also P9 firmware code 3 enabling of the use temperature alarm code H t 1 YES firmware version code 3 temperature over which the use temperature alarm is activated code H t see also P14 firmware revision code 3 size displayed when the instrument is on 0 if P3 0 top temperature if P3 1 chamber t...

Reviews: