Evco EV3H94 Instruction Sheet Download Page 3

EVCO S.p.A. | EV3H94 | Instruction sheet ver. 1.0 | Code 1043H94E104 | Page 3 of 5 | PT 05/21 

SETTINGS 

7.1 

Setting configuration parameters 

1. 

 

Touch the SET key for 4 s: the display will show the label “PA”. 

2. 

 

Touch the SET key. 

3. 

 

Touch the UP or DOWN key within 15s to set -19”. 

4. 

 

Touch  the  SET  key  (or  take  no  action  for  15s):  the  display  will 

show the label “SP”. 

5. 

 

Touch the UP or DOWN key to select a parameter. 

6. 

 

Touch the SET key. 

7. 

 

Touch the UP or DOWN key within 15s to set the value. 

8. 

 

Touch the SET key (or take no action for 15s). 

9. 

 

Touch the SET key for 4s (or take no action for 60s) to exit the 

procedure. 

 

7.2 

Set the date,  time and day of the week (if module EVIF23TSX, EVIF25TWX or 

interface EVIF25TBX is connected) 

 

 

N.B. 

-  Do not disconnect the device from the mains within two minutes since the setting 

of the time and day of the week. 

-  if the device communicates with the EVconnect app, the date, time and day of the 

week will be automatically set by the smartphone or tablet. 

 

Check that the keypad is not locked. 

1. 

 

Touch the DOWN key for 4 s. 

2. 

 

Touch the UP or DOWN key within 15 s to select the label “rtc”. 

3. 

 

Touch the SET key: the display will show the label “yy” followed 

by the last two figures of the year. 

4. 

 

Touch the UP or DOWN key within 15 s to set the year. 

5. 

Repeat actions 3. and 4. to set the next labels. 

 

LAB. 

DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL 

 

month (01… 12) 

 

day (01… 31) 

 

time (00… 23) 

 

minute (00… 59) 

6. 

 

Touch the SET key: the display will show the label for the day of 

the week. 

7. 

 

Touch the UP or DOWN key within 15 s to set the day of the 

week.

 

 

LAB. 

DESCRIPTION 

 

Mon 

Monday 

 

tuE 

Tuesday 

 

UEd 

Wednesday 

 

thu 

Thursday 

 

Fri 

Friday 

 

Sat 

Saturday 

 

Sun 

Sunday 

8. 

 

Touch the SET key: the device will exit the procedure. 

9. 

 

Touch the ON/STAND-BY key to exit the procedure beforehand. 

 

7.3 

Restoring factory settings (default) 

 

 

N.B. 

-  check  that  the  factory  settings  are  appropriate;  see  the  section  CONFIGURATION 

PARAMETERS

 

1. 

 

Touch the SET key for 4 s: the display will show the label “PA”. 

2. 

 

Touch the SET key. 

3. 

 

Touch the UP or DOWN key within 15s to set “149”. 

4. 

 

Touch  the  SET  key  (or  take  no  action  for  15s):  the  display  will 

show the label “dEF”. 

5. 

 

Touch the SET key. 

6. 

 

Touch the UP or DOWN key within 15s to set “1”. 

7. 

 

Touch  the SET key  (or  take no  action  for 15 s):  the  display  will 

show “-  -  -” flashing for 4 s, after which the device will exit the 

procedure. 

8. 

Disconnect the device from the power supply. 

9. 

 

Touch  the  SET  key  for  1s  before  action  6  to  exit  the  procedure 

beforehand. 

 

 

 

 

 

CONFIGURATION PARAMETERS 

 

 

No. 

PAR. 

DEF.  SETPOINT 

MIN... MAX.

 

SP1 

55.0  setpoint in economy mode 

r3... r4 

SP2 

65.0  setpoint in comfort mode 

r1... r2 

SP3 

45.0  overboost activation threshold 

10 °C/°F... r2 

SP5 

55.0  heat pump switch-off threshold 

r1... SP2 

SP6 

75.0  photovoltaic system setpoint 

40... 100 °C/°F 

SP7 

5.0 

setpoint in antifreeze mode 

0... 40 °C/°F 

SP8 

40.0  setpoint in green mode 

0... 100 °C/°F 

SP9 

-7.0  cold evaporator alarm threshold 

-25... 25 °C/°F 

 

SPA 

 

-25 

 

evaporator  failure  alarm  thresh-

old  

-50... 25 °C/°F 

 

 

No. 

PAR. 

DEF.  ANALOGUE INPUTS 

MIN... MAX. 

10 

CA1 

0.0 

DHW tank upper probe offset 

-25... 25 °C/°F 

11 

CA2 

0.0 

DHW tank lower probe offset 

-25... 25 °C/°F 

12 

CA3 

0.0 

evaporator probe offset 

-25... 25 °C/°F 

13 

 

P0 

 

 

type of probe 

 

0  = PTC 

1  = NTC 

2  = Pt 1000 

14 

P1 

enable decimal point °C 

0  = no 

1  = yes 

15 

P2 

temperature measurement unit 

0  = °C 

1  = °F 

16 

 

 

 

P3 

 

 

 

 

 

 

enabled probes 

 

 

 

0  = DHW  tank  upper  probe 

+ high pressure input 

1  = DHW  tank  upper  and 

lower probe 

17 

 

 

 

 

P4 

 

 

 

 

 

 

 

 

evaporator probe function 

 

 

 

 

0  = disabled (defrost every 

d18 minutes) 

1  = defrost  activation  and 

defrost end 

2  = defrost activation 

18 

 

 

 

 

 

 

P5 

 

 

 

 

 

 

 

 

 

 

 

 

value displayed 

 

 

 

 

 

 

0  = DHW  tank  upper  tem-

perature 

1  = setpoint 

in 

comfort 

mode 

2  = DHW  tank  lower  tem-

perature 

3  = evaporator temperature 

19 

P8 

display refresh time 

0... 250 s: 10 

 

No. 

PAR. 

DEF.  REGULATION 

MIN... MAX. 

20 

r0 

3.0 

setpoint differential 

1... 30 °C/°F 

21 

 

r1 

 

40.0 

 

minimum  setpoint  in  comfort 

mode 

10 °C/°F... r2 

 

22 

 

r2 

 

70.0 

 

maximum  setpoint  in  comfort 

mode 

r1... 100 °C/°F 

 

23 

 

r3 

 

40.0 

 

minimum  setpoint  in  economy 

mode 

10 °C/°F... r4 

 

24 

 

r4 

 

55.0 

 

maximum  setpoint  in  economy 

mode 

r3... 100 °C/°F 

 

25 

 

r5 

 

 

enable 

setpoint 

blocking 

in 

economy and comfort modes 

0  = no 

1  = yes 

 

26 

r6 

15.0 

heater  threshold  in  comfort 

mode 

0... 50 °C/°F 

27 

 

r7 

 

15.0 

 

heater  threshold  differential  in 

comfort mode 

1... 30 °C/°F 

 

 

No. 

PAR. 

DEF.  COMPRESSOR 

MIN... MAX. 

28 

 

C0 

 

 

compressor  on  delay  from  pow-

er-on 

0... 240 min 

 

29 

 

C1 

 

 

minimum  time  between  two 

power-ons of compressor 

0... 240 min 

 

30 

C2 

minimum compressor-off time 

0... 240 min 

31 

C3 

minimum compressor-on time 

0... 240 s 

32 

 

C10 

 

400 

 

compressor  hours  for  mainte-

nance 

0... 999 h x 100 

 

0  = disabled 

33 

 

C11 

 

120 

 

interval for cold evaporator con-

trol 

0... 999 min 

 

34 

 

C12 

 

60 

 

compressor-on  delay  from  fan 

on for cold evaporator control 

0... 240 s 

 

35 

 

C13 

 

20 

 

compressor-on delay from green 

multi-purpose input reset 

0... 240 min 

 

36 

 

C14 

 

20 

 

compressor-on  consecutive  time 

for  evaporator failure control  

-1... 240 min 

 

-1 = disabled 

 

No. 

PAR. 

DEF.  DEFROST 

MIN... MAX. 

37 

 

 

 

 

d1 

 

 

 

 

 

 

 

 

type of defrost 

 

 

 

 

0  = electric 

1  = hot gas 

2  = compressor stopped 

3  = hot  gas  balancing  the 

pressure 

38 

d2 

3.0 

defrost end threshold 

-50... 50 °C/°F 

39 

 

 

 

 

 

d3 

 

 

 

 

 

30 

 

 

 

 

 

defrost duration 

 

 

 

 

 

0... 99 min 

0 = defrost disabled 

If P4 = 1, maximum duration 

default 0 in map 3 of 

EV3H94N9PXRX01 and 

EV3H94N9VXRX01 

40 

 

d17 

 

-2.0 

 

evaporation threshold for defrost 

interval count 

-50... 50 °C/°F 

 

41 

 

d18 

 

30 

 

defrost interval 

 

0... 240 min 

0  = manual only 

 

Summary of Contents for EV3H94

Page 1: ... given in the section MEASUREMENTS AND INSTALLATION 2 Power up the device as set out in the section ELECTRICAL CONNECTION an internal test will start up The test normally takes a few seconds when it is finished the display will switch off 3 Configure the device as shown in the section Setting configuration parameters Recommended configuration parameters for first time use PAR DEF PARAMETER MIN MAX...

Page 2: ...gionella and overboost functions are not active compressor switched on if d1 1 defrost relay active if d1 1 or 2 fans switched on if d1 2 heaters switched on to prevent too high temperature drop in the storage tank 5 6 Photovoltaic system It activates with photovoltaic input active operation as in comfort mode except for SP2 setpoint which becomes SP6 setpoint 5 7 Green It activates with multi pur...

Page 3: ... 1 SP1 55 0 setpoint in economy mode r3 r4 2 SP2 65 0 setpoint in comfort mode r1 r2 3 SP3 45 0 overboost activation threshold 10 C F r2 4 SP5 55 0 heat pump switch off threshold r1 SP2 5 SP6 75 0 photovoltaic system setpoint 40 100 C F 6 SP7 5 0 setpoint in antifreeze mode 0 40 C F 7 SP8 40 0 setpoint in green mode 0 100 C F 8 SP9 7 0 cold evaporator alarm threshold 25 25 C F 9 SPA 25 evaporator ...

Page 4: ... min 00 00 disabled N PAR DEF SAFETIES MIN MAX 81 PA1 426 level 1 password 99 999 82 PA2 824 level 2 password 99 999 N PAR DEF DATA LOGGING EVLINK MIN MAX 83 bLE 1 enable Bluetooth 0 no 1 sì 1 reserved 84 rE0 15 data logger sampling inter val 0 240 min 85 rE1 1 recorded temperature 0 nessuna 1 DHW tank upper 2 DHW tank lower 3 evaporator 4 DHW tank upper and lower 5 tutte N PAR DEF MODBUS MIN MAX ...

Page 5: ...rm buzzer Built in Communication ports 1 TTL MODBUS slave port for EVconnect app EPoCA remote monitoring system or for BMS N B The device must be disposed of according to local regulations governing the collection of electrical and electronic equipment This document and the solutions contained therein are the intellectual property of EVCO and thus pro tected by the Italian Intellectual Property Ri...