![Evco EV3H94 Instruction Sheet Download Page 3](http://html.mh-extra.com/html/evco/ev3h94/ev3h94_instruction-sheet_2441812003.webp)
EVCO S.p.A. | EV3H94 | Instruction sheet ver. 1.0 | Code 1043H94E104 | Page 3 of 5 | PT 05/21
7
SETTINGS
7.1
Setting configuration parameters
1.
Touch the SET key for 4 s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15s to set -19”.
4.
Touch the SET key (or take no action for 15s): the display will
show the label “SP”.
5.
Touch the UP or DOWN key to select a parameter.
6.
Touch the SET key.
7.
Touch the UP or DOWN key within 15s to set the value.
8.
Touch the SET key (or take no action for 15s).
9.
Touch the SET key for 4s (or take no action for 60s) to exit the
procedure.
7.2
Set the date, time and day of the week (if module EVIF23TSX, EVIF25TWX or
interface EVIF25TBX is connected)
N.B.
- Do not disconnect the device from the mains within two minutes since the setting
of the time and day of the week.
- if the device communicates with the EVconnect app, the date, time and day of the
week will be automatically set by the smartphone or tablet.
Check that the keypad is not locked.
1.
Touch the DOWN key for 4 s.
2.
Touch the UP or DOWN key within 15 s to select the label “rtc”.
3.
Touch the SET key: the display will show the label “yy” followed
by the last two figures of the year.
4.
Touch the UP or DOWN key within 15 s to set the year.
5.
Repeat actions 3. and 4. to set the next labels.
LAB.
DESCRIPTION OF THE NUMBERS FOLLOWING THE LABEL
n
month (01… 12)
d
day (01… 31)
h
time (00… 23)
n
minute (00… 59)
6.
Touch the SET key: the display will show the label for the day of
the week.
7.
Touch the UP or DOWN key within 15 s to set the day of the
week.
LAB.
DESCRIPTION
Mon
Monday
tuE
Tuesday
UEd
Wednesday
thu
Thursday
Fri
Friday
Sat
Saturday
Sun
Sunday
8.
Touch the SET key: the device will exit the procedure.
9.
Touch the ON/STAND-BY key to exit the procedure beforehand.
7.3
Restoring factory settings (default)
N.B.
- check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
1.
Touch the SET key for 4 s: the display will show the label “PA”.
2.
Touch the SET key.
3.
Touch the UP or DOWN key within 15s to set “149”.
4.
Touch the SET key (or take no action for 15s): the display will
show the label “dEF”.
5.
Touch the SET key.
6.
Touch the UP or DOWN key within 15s to set “1”.
7.
Touch the SET key (or take no action for 15 s): the display will
show “- - -” flashing for 4 s, after which the device will exit the
procedure.
8.
Disconnect the device from the power supply.
9.
Touch the SET key for 1s before action 6 to exit the procedure
beforehand.
8
CONFIGURATION PARAMETERS
No.
PAR.
DEF. SETPOINT
MIN... MAX.
1
SP1
55.0 setpoint in economy mode
r3... r4
2
SP2
65.0 setpoint in comfort mode
r1... r2
3
SP3
45.0 overboost activation threshold
10 °C/°F... r2
4
SP5
55.0 heat pump switch-off threshold
r1... SP2
5
SP6
75.0 photovoltaic system setpoint
40... 100 °C/°F
6
SP7
5.0
setpoint in antifreeze mode
0... 40 °C/°F
7
SP8
40.0 setpoint in green mode
0... 100 °C/°F
8
SP9
-7.0 cold evaporator alarm threshold
-25... 25 °C/°F
9
SPA
-25
evaporator failure alarm thresh-
old
-50... 25 °C/°F
No.
PAR.
DEF. ANALOGUE INPUTS
MIN... MAX.
10
CA1
0.0
DHW tank upper probe offset
-25... 25 °C/°F
11
CA2
0.0
DHW tank lower probe offset
-25... 25 °C/°F
12
CA3
0.0
evaporator probe offset
-25... 25 °C/°F
13
P0
1
type of probe
0 = PTC
1 = NTC
2 = Pt 1000
14
P1
1
enable decimal point °C
0 = no
1 = yes
15
P2
0
temperature measurement unit
0 = °C
1 = °F
16
P3
1
enabled probes
0 = DHW tank upper probe
+ high pressure input
1 = DHW tank upper and
lower probe
17
P4
2
evaporator probe function
0 = disabled (defrost every
d18 minutes)
1 = defrost activation and
defrost end
2 = defrost activation
18
P5
0
value displayed
0 = DHW tank upper tem-
perature
1 = setpoint
in
comfort
mode
2 = DHW tank lower tem-
perature
3 = evaporator temperature
19
P8
5
display refresh time
0... 250 s: 10
No.
PAR.
DEF. REGULATION
MIN... MAX.
20
r0
3.0
setpoint differential
1... 30 °C/°F
21
r1
40.0
minimum setpoint in comfort
mode
10 °C/°F... r2
22
r2
70.0
maximum setpoint in comfort
mode
r1... 100 °C/°F
23
r3
40.0
minimum setpoint in economy
mode
10 °C/°F... r4
24
r4
55.0
maximum setpoint in economy
mode
r3... 100 °C/°F
25
r5
0
enable
setpoint
blocking
in
economy and comfort modes
0 = no
1 = yes
26
r6
15.0
heater threshold in comfort
mode
0... 50 °C/°F
27
r7
15.0
heater threshold differential in
comfort mode
1... 30 °C/°F
No.
PAR.
DEF. COMPRESSOR
MIN... MAX.
28
C0
5
compressor on delay from pow-
er-on
0... 240 min
29
C1
5
minimum time between two
power-ons of compressor
0... 240 min
30
C2
5
minimum compressor-off time
0... 240 min
31
C3
0
minimum compressor-on time
0... 240 s
32
C10
400
compressor hours for mainte-
nance
0... 999 h x 100
0 = disabled
33
C11
120
interval for cold evaporator con-
trol
0... 999 min
34
C12
60
compressor-on delay from fan
on for cold evaporator control
0... 240 s
35
C13
20
compressor-on delay from green
multi-purpose input reset
0... 240 min
36
C14
20
compressor-on consecutive time
for evaporator failure control
-1... 240 min
-1 = disabled
No.
PAR.
DEF. DEFROST
MIN... MAX.
37
d1
2
type of defrost
0 = electric
1 = hot gas
2 = compressor stopped
3 = hot gas balancing the
pressure
38
d2
3.0
defrost end threshold
-50... 50 °C/°F
39
d3
30
defrost duration
0... 99 min
0 = defrost disabled
If P4 = 1, maximum duration
default 0 in map 3 of
EV3H94N9PXRX01 and
EV3H94N9VXRX01
40
d17
-2.0
evaporation threshold for defrost
interval count
-50... 50 °C/°F
41
d18
30
defrost interval
0... 240 min
0 = manual only