EVCO S.p.A. | EV3143 | Instruction sheet ver. 1.0 | Code 1043143E103 | Page 3 of 3 | PT 22/19
97
F1S
0
seconds beater off during batch
freezing heating
0... 59 s
2
NO. PAR.
DEF. BATCH FREEZING COOKING
MIN... MAX.
98
SPC
30.0
plate setpoint during batch freez-
ing cooking and plate setpoint
during batch freezing cooking
r23... r24
99
SU2
30.0
tank setpoint at end of batch
freezing heating and tank setpoint
during batch freezing cooking
r25... r26
100
r2H
2.0
tank differential setpoint during
batch freezing cooking
1... 25 °C/°F
101
C2H
1
duration in hours of batch freezing
cooking
0... 23 h
102
C2n
0
duration in minutes of batch
freezing cooking
0... 59 min
103
C2S
0
duration in seconds of batch
freezing cooking
0... 59 s
104
n2H
0
hours beater on during batch
freezing cooking
0... 23 h
105
n2n
2
minutes beater on during batch
freezing cooking
0... 59 min
106
n2S
0
seconds beater on during batch
freezing cooking
0... 59 s
107
F2H
0
hours beater off during batch
freezing cooking
0... 23 h
108
F2n
2
minutes beater off during batch
freezing cooking
0... 59 min
109
F2S
0
seconds beater off during batch
freezing cooking
0... 59 s
3
NO. PAR.
DEF. BATCH FREEZING COOLING
MIN... MAX.
110
SU3
30.0
tank setpoint at end of batch
freezing cooling and tank setpoint
during batch freezing conserva-
tion
r27... r28
111
SA3
10.0
tank setpoint for beater on at end
of batch freezing cooking
0... 25 °C/°F
112
n3H
0
hours beater on during batch
freezing cooling
0... 23 h
113
n3n
2
minutes beater on during batch
freezing cooling
0... 59 min
114
n3S
0
seconds beater on during batch
freezing cooling
0... 59 s
115
F3H
0
hours beater off during batch
freezing cooling
0... 23 h
116
F3n
2
minutes beater off during batch
freezing cooling
0... 59 min
117
F3S
0
seconds beater off during batch
freezing cooling
0... 59 s
4
NO.
PAR.
DEF.
BATCH FREEZING CONSERVA-
TION
MIN... MAX.
118
r4H
2.0
tank differential setpoint during
batch freezing conservation
1... 25 °C/°F
119
n4H
0
hours beater on during batch
freezing conservation
0... 23 h
120
n4n
2
minutes beater on during batch
freezing conservation
0... 59 min
121
n4S
0
seconds beater on during batch
freezing conservation
0... 59 s
122
F4H
0
hours beater off during batch
freezing conservation
0... 23 h
123
F4n
2
minutes beater off during batch
freezing conservation
0... 59 min
124
F4S
0
seconds beater off during batch
freezing conservation
0... 59 s
125
F4C
0
beater mode during batch freez-
ing conservation
0 = independent on the com-
pressor
1 = on if compressor on, ac-
cording to n4... and F4...
if compressor off
NO. PAR.
DEF. SECURITY
MIN... MAX.
126 H4E
0
timeout for locking the keypad
0... 240 s
127 POF
1
enable ON/STAND-BY key
0 = no
1 = yes
128 PAS
-19
password
-99... 999
129 PA1
- - -
unused
-
130 PA2
- - -
unused
-
NO. PAR.
DEF. UNUSED
MIN... MAX.
131
Hr0
- - -
unused
-
NO. PAR.
DEF. UNUSED
MIN... MAX.
132
rE0
- - -
unused
-
133
rE1
- - -
unused
-
NO. PAR.
DEF. MODBUS
MIN... MAX.
134
LA
247
MODBUS address
1... 247
135
Lb
2
MODBUS baud rate
0 = 2,400 baud
1 = 4,800 baud
2 = 9,600 baud
3 = 19,200 baud
136
bLE
- - -
unused
-
NO. PAR.
DEF. SECURITY
MIN... MAX.
137
bu1
0
duration of buzzer activation
when setpoint reached
0... 240 s
138
Pbu
2
enable buzzer
0 = disabled
1 = keys only
2 = alarms only
3 = keys and alarms
9
ALARMS
CODE DE8CRIPTION
RESET
TO CORRECT
Pr1
probe 1 alarm
automatic
- check P0
Pr2
probe 2 alarm
automatic
- check integrity of the probe
- check electrical connection
rtc
unused
unused
unused
AL1
low
temperature
alarm
probe 1
automatic
check A1 and A2
AH1
high
temperature
alarm
probe 1
automatic
check A4 and A5
AL2
low
temperature
alarm
probe 2
automatic
check A11 and A12
AH2
high
temperature
alarm
probe 2
automatic
check A14 and A15
id
door open alarm
automatic
check i5 and i6
PF
power failure alarm
manual
- touch a key
- check electrical connection
COH
high condensation signal
automatic
check C13
CSd
high condensation alarm
manual
- switch the device off and on
- check C14
iA
multi-purpose input alarm
automatic
check i5 and i6
it
thermal switch alarm
automatic
- switch the device off and on
- check i5 and i6
10
TECHNICAL SPECIFICATIONS
Purpose of the control device:
function controller.
Construction of the control device:
built-in electronic device.
Housing:
black, self-extinguishing.
Category of heat and fire resistance:
D.
Measurements:
75.0 x 33.0 x 59.0 mm (2 15/16 x 1 5/16 x
2 5/16 in) with fixed screw terminal blocks
75.0 x 33.0 x 81.5 mm (2 15/16 x 1 5/16 x
3 3/16 in) with plug-in screw terminal blocks
Mounting methods for the control device:
to be fitted to a panel, snap-in brackets pro-
vided
Degree of protection provided by the casing:
IP65 (front).
Connection method:
fixed screw terminal blocks for
wires up to 2.5 mm²
plug-in screw terminal blocks
for wires up to 2.5 mm² (on
request)
Micro-MaTch connector
Maximum permitted length for connection cables:
power supply: 10 m (32.8 ft)
analogue inputs: 10 m (32.8 ft)
digital inputs: 10 m (32.8 ft)
digital outputs: 10 m (32.8 ft).
Operating temperature:
from 0 to 55 °C (from 32 to 131 °F).
Storage temperature:
from -25 to 70 °C (from -13 to 158 °F).
Operating humidity:
relative humidity without condensate from 10
to 90%.
Pollution status of the control device:
2.
Compliance:
RoHS 2011/65/EC
WEEE 2012/19/EU
REACH
(EC)
Regulation
no. 1907/2006
EMC 2014/30/EU
LVD 2014/35/EU.
Power supply:
230 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3143N7
115 VAC (+10% -15%), 50/60 Hz (±3 Hz), max. 2 VA insulated in EV3143N5.
Earthing methods for the control device:
none.
Rated impulse-withstand voltage:
4 KV.
Over-voltage category:
III.
Software class and structure:
A.
Analogue inputs:
2 for PTC or NTC probes (probe 1 and probe
2).
PTC probes:
Type of sensor:
KTY 81-121 (990
@ 25 °C, 77 °F)
Measurement field:
from -50 to 150 °C (from -58 to 302 °F)
Resolution:
0.1 °C (1 °F).
NTC probes:
Type of sensor:
ß3435 (10 K
@ 25 °C, 77 °F)
Measurement field:
from -40 to 105 °C (from -40 to 221 °F)
Resolution:
0.1 °C (1 °F).
Digital inputs:
1 dry contact (door switch/multi-purpose).
Dry contact:
Type of contact:
5 VDC, 1.5 mA
Power supply:
none
Protection:
none.
Digital outputs:
3 electro-mechanical relays.
K1 relay:
SPST, 16 A res. @ 250 VAC
K2 relay:
SPDT, 8 A res. @ 250 VAC.
K3 relay:
SPST, 5 A res. @ 250 VAC.
Type 1 or Type 2 actions:
type 1.
Additional features of Type 1 or Type 2 actions:
C.
Displays:
custom display, 3 digit, with function icons.
Alarm buzzer:
built-in.
Communications ports:
1 TTL MODBUS slave port for BMS.
N.B.
The device must be disposed of according to local regulations governing the collection
of electrical and electronic equipment.
This document and the solutions contained therein are the intellectual property of EVCO and thus protected
by the Italian Intellectual Property Rights Code (CPI). EVCO imposes an absolute ban on the full or partial
reproduction and disclosure of the content other than with the express approval of EVCO. The customer
(manufacturer, installer or end user) assumes all responsibility for the configuration of the device.
EVCO accepts no liability for any possible errors in this document and reserves the right to make any
changes at any time without prejudice to the essential functional and safety features of the equipment.