EVCO S.p.A.
EV3 HP & EVD HP | Installer manual ver. 1.2 | Code 1443DHPE124
page 32 of 52
M Fn18
100
0
100
Hz - %
Maximum fan speed in hot mode
M Fn19
0,0
-50,0
80,0
°C-Bar
Maximum fan speed set-point in hot mode
M Fn20
50,0
-50,0
80,0
°C-Bar
Fan activation set-point in defrost mode
M Fn21
10,0
0,0
25,5
°C-Bar
Fan activation hysteresis in defrost mode
M
Fn23
30
0
255
Hz - %
Fan speed in defrost mode
MENU
PARAM.
DEFAULT
MIN.
MAX.
U.M.
PUMP
M
PM01
20
0
255
s
Compressor switch-on delay from pump switch-on
M
PM02
10
0
255
s
Pump switch-off delay from compressor switch-off
M
PM03
1
0
1
- - - -
Pump ON mode at request
0= disabled (pump on constantly)
1= enabled
S
PM04
4
-127
127
°C
Antifreeze set-point for activating pump
S
PM05
2,0
0.0
25.5
°C
Antifreeze hysteresis for activating pump
MENU
PARAM.
DEFAULT
MIN.
MAX.
U.M.
HEATING ELEMENTS
S
Fr02
6
Fr04
Fr03
°C
Heating element set-point (for antifreeze)
M
Fr03
10
Fr04
127
°C
Maximum heating element set-point (for antifreeze)
M
Fr04
-10
-127
Fr03
°C
Minimum heating element set-point (for antifreeze)
S
Fr05
2,0
0,0
25,5
°C
Heating element hysteresis in integration mode
M
Fr11
180
0
255
s*10
Heating element activation delay in integration mode
M
Fr12
6,0
0,0
25,5
°C
Heating element delta temperature in integration mode
MENU
PARAM.
DEFAULT
MIN.
MAX.
U.M.
DEFROST
M
dF01
1
0
3
- - - -
Enable defrost
0 = disabled
1 = with activated compressor
2 = for compressor stop (similar to dF01 = 1 but without
activating the compressor)
3 = Time interval defrost (similar to dF01 = 1 but ending
up for exceeded time
M
dF02
-5,0
-50.0
80.0
°C-Bar
Defrost start set-point