EV3 HP & EVD HP | Installer manual ver. 1.2 | Code 1443DHPE124 

page 1 of 52 

EV3 HP & EVD HP 

Controllers for reversible single-circuit 

residential heat pumps 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Installer Manual | ENGLISH 

Code 1443DHPI124 

Summary of Contents for EV3 HP

Page 1: ...EVCO S p A EV3 HP EVD HP Installer manual ver 1 2 Code 1443DHPE124 page 1 of 52 EV3 HP EVD HP Controllers for reversible single circuit residential heat pumps Installer Manual ENGLISH Code 1443DHPI124 ...

Page 2: ... using the devices and take all the prescribed precautions Keep this manual with the devices for future consultation Only use the devices in the ways described in this manual Do not use these devices as safety devices Disposal The devices must be disposed of according to local regulations governing the collection of electrical and electronic waste ...

Page 3: ...rical connection 21 4 4 1 Example of EV3 HP electrical connection 21 4 4 2 Example of EVD HP electrical connection 22 4 5 Precautions for electrical connection 23 5 DESCRIPTION OF USER INTERFACE 24 5 1 Key functions 24 5 2 Display 24 5 3 Signals 25 5 4 Menu 27 5 4 1 Access levels 27 5 4 2 Menu list 27 6 LIST OF PARAMETERS 28 6 1 Initial information 28 7 REGULATORS 33 7 1 Initial information 33 7 2...

Page 4: ... 40 8 ALARMS 41 8 1 Initial information 41 8 2 List of alarms 41 9 ACCESSORIES 43 9 1 EVIF20SUXI RS 485 USB serial interface 43 9 1 1 Initial information 43 9 2 0025100010 drip protector 43 9 2 1 Initial information 43 9 3 CJAV connection kit 43 9 3 1 Initial information 43 10 TECHNICAL SPECIFICATIONS 44 10 1 Technical specifications 44 ...

Page 5: ...nt and function icons and four touch keys It guarantees IP65 protection for easy cleaning EVD HP is available in standard 4 module DIN format in a blind version that can be connected to a remote user interface EV3K01 if required These controllers are capable of running compressors and fans of both the on off and modulating types EV3 HP is available with a 12VAC power supply while EVD HP can be sup...

Page 6: ...CT VERSION SPLIT VERSION Models available EV3 HP EVD HP EV3K01 Purchasing codes EV3914LM2 EV3916LM2GF EVD914BM9 EV3K01XOCT Version Blind Built in LED 4 4 digit custom display Connections Micro Fit connectors Edge connectors Plug in screw terminal blocks Power supply 12VAC not insulated 12VAC DC not insulated 115 230VAC insulated Analogue inputs NTC 4 4 4 NTC 4 20 mA 1 1 1 Digital inputs Dry contac...

Page 7: ...4 4 3A SPST 2 8A SPDT 1 12A SPST 1 Digital outputs triac A res 250 VAC 200mA 1 2A 1 Digital outputs open collector 12VDC max 40mA 1 Communications ports Powered INTRABUS Other features Alarm buzzer Notes Optional extras None Clock not available for model EV3K01 RS 485 MODBUS slave port not available for model EV3K01 The purchasing codes for EV3 HP and EVD HP do not include the cabling connectors s...

Page 8: ... Micro switch for the termination of the RS 485 MODBUS line 7 Seal 8 Edge connector joint for the digital output cabling with electro mechanical relay for future reference the digital outputs DO1 DO4 9 Male Micro Fit connector for cabling for the power supply analogue inputs digital inputs analogue outputs and the INTRABUS powered port 10 If fitted plug in screw terminal block for cabling for the ...

Page 9: ...al output OC1 2 Micro switch for the termination of the RS 485 MODBUS port 3 If fitted plug in screw terminal block for cabling for the RS 485 MODBUS port 4 Plug in screw terminal block for cabling for the powered INTRABUS port 5 Plug in screw terminal block for cabling for the digital outputs with electro mechanical relay for future reference the digital outputs DO1 and DO2 6 Plug in screw termin...

Page 10: ...ow LED display with decimal point and function icons 2 On Off key subsequently also called the On Stand by key 3 Decrease key subsequently also called the Down key 4 Increase key subsequently also called the Up key 5 Setting key subsequently also called the Set key 6 Seal 7 Male female plug in screw terminal block for cabling for the power supply and the powered INTRABUS port 8 Not used For more i...

Page 11: ...he measurements of EV3 HP measurements are expressed in mm inches To be installed on a panel with snap in brackets provided The thickness of the panel on which EV3 HP is to be installed must be between 0 8 and 2 0mm 0 031 and 0 078 in 3 2 Measurements and installation of EVD HP The picture below shows the measurements of EVD HP 4 DIN modules measurements are expressed in mm inches ...

Page 12: ...35 0 x 15 0mm 1 377 x 0 590 in in a control panel The pictures below show how to install the EVD HP 1 2 To remove the EVD HP first remove any plug in screw terminal blocks fitted in the lower part then using a screwdriver loosen the DIN rail clip as shown in the pictures below 3 4 To re install the EVD HP first press the DIN rail clip fully in ...

Page 13: ...ure that the working conditions for the devices operating temperatures humidity etc are within the set limits See the section TECHNICAL SPECIFICATIONS Do not install the devices close to heat sources heating elements hot air ducts etc equipment with a strong magnetic field large diffusers etc in places subject to direct sunlight rain damp excessive dust mechanical vibrations or shocks In complianc...

Page 14: ...ature NTC DIGITAL INPUTS EV3914LM2 EV3916LM2GF EVD914BM9 IN10 EVD IN6 EV3 System flow switch NC IN9 EVD IN7 EV3 Fan thermal protection IN8 Compressor thermal protection NC IN7 EVD IN9 EV3 Maximum pressure switch NC IN6 EVD IN10 EV3 Minimum pressure switch NC ANALOGUE OUTPUTS EV3914LM2 EV3916LM2GF EVD914BM9 AO1 Compressor 0 10V phase cutting PWM AO2 Fan 0 10V phase cutting PWM DIGITAL OUTPUTS EV391...

Page 15: ...O1 DO4 max 6A common 2 Electro mechanical relay digital output DO4 2 A SPST normally open 3 Electro mechanical relay digital output DO3 2 A SPST normally open 4 Electro mechanical relay digital output DO2 2 A SPST normally open 5 Electro mechanical relay digital output DO1 2 A SPST normally open Connector 2 PART DESCRIPTION 1 Dry contact digital input IN10 2 Analogue input IN1 NTC 4 20 mA 3 Dry co...

Page 16: ...nal 15 Power supply to analogue inputs 4 20 mA 12 VDC max 40 mA 16 Reference GND for analogue inputs digital inputs analogue outputs and powered INTRABUS port 17 EV3 HP power supply 12VAC not insulated 18 EV3 HP power supply 12VAC not insulated Connector 3 if installed PART DESCRIPTION 1 RS 485 MODBUS port 2 RS 485 MODBUS port 3 RS 485 MODBUS port reference GND NB do not connect the cable shield C...

Page 17: ... digital output DO2 3A SPST normally open 3 Electro mechanical relay digital outputs DO1 and DO2 max 6A common Connector 2 PART DESCRIPTION 1 Electro mechanical relay digital output DO3 12A SPST normally open 2 Electro mechanical relay digital output DO3 and D04 common 3 Electro mechanical relay digital output DO3 and D04 common 4 Electro mechanical relay digital output DO4 8A SPDT normally open 5...

Page 18: ...e input IN2 NTC 7 Dry contact digital input IN9 8 Analogue input IN3 NTC 9 Dry contact digital input IN8 10 Analogue input IN4 NTC 11 Dry contact digital input IN7 12 Analogue input IN5 NTC 13 Reference GND for analogue inputs digital inputs and analogue outputs 14 Dry contact digital input IN6 15 Reference GND for analogue inputs digital inputs and analogue outputs 16 power supply for analogue in...

Page 19: ...ower supply powered INTRABUS port 2 INTRABUS port powered up signal 3 EV3K01 power supply 4 2 3 Description of EV3K01 connectors The picture below shows the layout of the EV3K01 connectors The table below describes the EV3K01 connectors Connector 1 PART DESCRIPTION 1 EV3K01 12 VAC DC power supply if EV3K01 is fed by DC power connect the positive pole 2 Not used 3 INTRABUS port powered up signal 4 ...

Page 20: ... on the signal transmitted along the cables connecting the devices to a RS 485 network it is necessary to terminate the line ONLY at the first and last element in the network To terminate the line it will be sufficient to place EV3 HP micro switch 1 in position ON Do not touch micro switch 2 When using EVD HP place micro switch 1 in position ON ...

Page 21: ... Example of electrical connection 4 4 1 Example of EV3 HP electrical connection The picture below shows an example of the EV3 HP electrical connection If using triac digital outputs we recommend connecting a noise filter The heat sink might reach very high temperatures do not touch it ...

Page 22: ...EVCO S p A EV3 HP EVD HP Installer manual ver 1 2 Code 1443DHPE124 page 22 of 52 4 4 2 Example of EVD HP electrical connection The picture below shows an example of the EVD HP electrical connection ...

Page 23: ... from the power supply before doing any type of maintenance The devices must be fed by power of the same phase as that feeding any module with a phase cutting command signal If using triac digital outputs we recommend connecting a noise filter The heat sink might reach very high temperatures do not touch it Connect the devices to an RS 485 network using a screened cable with twisted pair for the s...

Page 24: ... the measurements found by the probes 5 2 Display A pressure on the On stand by will switch on switch off the device When the device is switched on with the key it is possible to switch it remotely to Stand By mode by operating on the dedicated digital input through a switch The user interface has two display modes Initial display mode The upper row shows the input water temperature while the lowe...

Page 25: ... if the fan is switched off GREEN System heating element LED ON if the heating element is switched on OFF if the heating element is switched off AMBER LED for the unit of measurement of the value shown on the lower display when the probe is configured for temperature AMBER LED for the unit of measurement of the value shown on the lower display when the probe is configured for pressure AMBER Defros...

Page 26: ...ed for pressure RED IB RS485 LED BLINK if an INTRABUS RS485 communication is underway OFF if no communication is underway The table below shows the meaning of the LED signals of EVD HP LED COLORE SIGNIFICATO ON GREEN Power supply LED ON if the controller is powered OFF if the controller is not powered RUN GREEN RUN LED ON if the controller is switched on OFF if the controller is switched off RED A...

Page 27: ...hows the status of the outputs configured as digital outputs PAr Shows and allows the device parameters to be altered The parameters are grouped according to their function identified on the display by a label Each parameter has an alphabetic code followed by two numbers as shown in the table below GROUP IDENTIFICATION LABEL PARAMETER CODE Configuration ConF CF Compressor CoMP CP Fan FAn Fn Alarms...

Page 28: ...CF02 CF01 C Temperature set point in hot mode MENU PARAM DEFAULT MIN MAX U M CONFIGURATION S CF01 60 0 HEAt 90 0 C Maximum set point value in hot mode S CF02 20 0 0 0 HEAt C Minimum set point value in hot mode S CF03 30 0 CooL 90 0 C Maximum set point value in cold mode S CF04 4 0 50 0 Cool C Minimum set point value in cold mode M CF06 0 0 1 Controller LED meaning 0 heating cooling 1 heating cooli...

Page 29: ... CF35 value determines the unit of measurement for adjusting the compressor Hz or M CF36 1 0 4 AO2 output configuration type 0 Disabled 1 Phase cutting 2 0 10V 3 PWM 4 Frequency Hz The choice of CF36 value determines the unit of measurement for adjusting the fan Hz or M CF47 0 0 4 AO1 analogue output function configuration 0 Disabled 1 Not used 2 Not used 3 Not used 4 Modulating compressor S CF51 ...

Page 30: ... 2 0 0 0 25 5 C Antifreeze alarm hysteresis M Al14 0 0 1 Stop fan with antifreeze alarm 0 Disabled 1 Enabled M AL15 99 0 0 255 0 C High adjustment temperature alarm set point M AL16 5 0 255 s 10 High adjustment temperature alarm delay M Al17 105 0 0 0 255 0 C High discharge temperature alarm set point M AL18 15 0 0 0 25 5 C High discharge temperature alarm hysteresis MENU PARAM DEFAULT MIN MAX U M...

Page 31: ...or 1 Independent M Fn04 3 0 0 0 25 5 C Bar Fan adjustment delta cut off M Fn05 2 0 0 25 5 C Bar Fan cut off hysteresis M Fn06 20 0 255 s Fan cut off bypass time M Fn07 30 0 100 Hz Minimum fan speed in cold mode M Fn08 100 0 100 Hz Maximum silent running fan speed in cold mode M Fn09 30 0 50 0 80 0 C Bar Set point temp press minimum fan speed in cold mode M Fn10 20 0 0 0 25 5 C Bar Fan proportional...

Page 32: ...nt for activating pump S PM05 2 0 0 0 25 5 C Antifreeze hysteresis for activating pump MENU PARAM DEFAULT MIN MAX U M HEATING ELEMENTS S Fr02 6 Fr04 Fr03 C Heating element set point for antifreeze M Fr03 10 Fr04 127 C Maximum heating element set point for antifreeze M Fr04 10 127 Fr03 C Minimum heating element set point for antifreeze S Fr05 2 0 0 0 25 5 C Heating element hysteresis in integration...

Page 33: ...bled the unit will in Cooling mode The function mode can be selected on the keypad to move from one mode to another simply press the On Standby key 7 3 Compressor The adjustment is based on the value provided by the input water probe The compressor is run on the basis of this temperature and of the set point If a modulating compressor is to be used connect it to analogue output AN1 in which case i...

Page 34: ...de if parameter CF14 is configured correctly The diagram below represents the proportional adjustment in cold mode To keep it simple the integral component is not represented Rl04 0 The compressor enable outlet is also shown For ON OFF adjustment the cut off delta must be set to 0 and there will be only one adjustment step as shown on the diagram below ...

Page 35: ...ment in hot mode The integral component is not represented Rl04 0 For ON OFF adjustment the cut off delta must be set to 0 and there will be only one adjustment step as shown on the diagram below 7 3 3 Oil refresh If the compressor is running at a frequency lower that the CP09 parameter for a period longer than the CP10 parameter it is activated at the maximum frequency The compressor will remain ...

Page 36: ...r the flow alarm in manual re arm with the flow alarm active in automatic re arm the pump stays switched on 7 4 2 Function modes The hydraulic pump can be set to function in two modes Continuous The pump is always in ON mode if PM03 0 On call The pump is switched on at the request of the heat regulator if PM03 1 The compressor is activated with a delay PM01 from pump switch on and the pump is swit...

Page 37: ... is in Heating mode The heating elements come on when the temperature of the adjustment probe falls below threshold set by parameter HEAt Fr12 for a time period of Fr11 They switch off when the temperature rises above the threshold set by HEAt Fr12 Fr05 If the compressor is in alarm mode the adjustment is made without delay from when the heat set point is reached 7 5 3 Heating elements in antifree...

Page 38: ... independently of the compressor Fn03 1 or at the request of the compressor Fn03 0 When the fan is switched off this will be by passed by a time equal to Fn06 from switch on of a compressor During this period the fan is set to minimum speed if the regulator requests cut off 7 6 2 Adjustment in cold mode The diagram below represents the proportional adjustment in cold mode In this mode parameter Fn...

Page 39: ...epresents the ON OFF adjustment in hot mode 7 6 4 Regolazione in sbrinamento During the start defrost period the fan remains off The diagram below represents the fan adjustment when a defrost cycle is underway with compressor in On mode During the dripping period the fan is first switched off and once the 4 ways valve is inverted it is switched back on at the maximum speed for a time equal to dF07...

Page 40: ...the probe reading rises above the dF02 threshold or the compressor is switched off The reversing valve is regulated after a delay equal to the time expressed by parameter dF06 and the compressor is switched back on at full power df01 1 o 3 after a further wait equal to the time expressed by the parameter dF06 also with a switch on waiting time of dF09 If the reading rises above Fn20 the fans are a...

Page 41: ... both conditions return to normal The alarm is activated after a delay of AL02 from compressor switch on Main results The compressor and fan are switched off AtC1 Compressor thermal protection alarm The alarm is activated if the input configured as a compressor thermal protection input is active It deactivates if the input is inactive Main results The compressor is switched off AdS1 Compressor dis...

Page 42: ...er of alarm events in an hour exceeds AL07 Main results All functions switched off AHtr High temperature alarm This alarm is activated when the input water temperature exceeds AL15 for a period longer than AL16 It is deactivated when the temperature is lower than AL15 AL13 Main results The compressor is switched off EA01 EA02 EA03 EA04 EA05 Probe alarms The alarm is activated in the following situ...

Page 43: ...interface makes it possible to connect EV3 HP and EVD HP to the set up software Parameters Manager 9 2 0025100010 drip protector 9 2 1 Initial information This drip protector shields EV3 HP and EV3K01 from damp 9 3 CJAV connection kit 9 3 1 Initial information These kits make it possible to cable EV3 HP and EVD HP CONTROLLER PURCHASING CODE EV3 HP CJAV37 EVD HP CJAV38 ...

Page 44: ... Category of heat and fire resistance EV3 HP D EVD HP EV3K01 Measurements EV3 HP 75 0 x 33 0 x 59 0mm 2 952 x 1 299 x 2 322 in L x H x D EVD HP 71 0 x 110 0 x 60 0mm 2 795 x 4 330 x 2 362 in L x H x D 4 DIN modules EV3K01 75 0 x 33 0 x 39 5mm 2 952 x 1 299 x 1 555 in L x H x D Mounting methods for the control device EV3 HP To be fitted to a panel snap in brackets provided EVD HP On a DIN rail 35 0...

Page 45: ... by EVD HP 3m 9 8ft for independent power supply Analogue inputs 10m 32 8ft Power supply for transducer analogue inputs 4 20mA 10m 32 8ft Digital inputs 10m 32 8ft Analogue outputs 0 10V 10m 32 8ft Phase cutting analogue outputs 10m 32 8 ft PWM analogue outputs 1m 3 28ft Electro mechanical relay digital outputs 10m 32 8ft Triac digital outputs 10m 32 8ft Open collector digital outputs 10m 32 8ft I...

Page 46: ...3K01 Environmental compliance EV3 HP RoHS 2011 65 EC WEEE 2012 19 EU REACH EC Regulation 1907 2006 EVD HP EV3K01 EMC compliance EV3 HP EN 60730 1 IEC 60730 1 EVD HP EV3K01 Power supply EV3 HP 12VAC 15 50 60 Hz 3 Hz max 6VA not insulated supplied by a class 2 circuit Protect the power supply with a 1 A T 250V fuse EVD HP 115 230VAC 10 15 50 60 Hz 3 Hz max 6VA insulated Protect the power supply with...

Page 47: ... power supply of the device Drift 60s month at 25 C 77 F EVD HP EV3K01 Not available Analogue inputs EV3 HP 5 inputs 4 for NTC probes 1 can be set up using the configuration parameter for NTC 4 20mA probes or transducers EVD HP EV3K01 None NTC analogue inputs 10 KΩ 25 C 77 F Sensor type ß3435 Measurement field from 50 to 150 C from 58 to 248 F Resolution 0 1 C Accuracy 0 5 C from 20 to 40 C 1 C fr...

Page 48: ...nalogue outputs Output 10VDC max 10mA Protection none PWM analogue outputs Output 10VDC max 10mA Frequency 10 2KHz Duty cycle 5 95 Protection none Digital outputs EV3 HP Up to 6 outputs 4 with SPST electro mechanical relay 2A res 250 VAC 1 with triac 200mA res 250VAC at 25 C 77 F 1 with triac 2A res 250VAC at 25 C 77 F EVD HP Up to 5 outputs 2 with SPST electro mechanical relay 3A res 250VAC 1 wit...

Page 49: ... EV3 HP C EVD HP EV3K01 not applicable Displays EV3 HP Custom 4 4 digit display EVD HP Signalling LED EV3K01 Custom 4 4 digit display Communications ports EV3 HP Up to 2 ports 1 powered INTRABUS port 1 RS 485 MODBUS slave port EVD HP EV3K01 1 powered INTRABUS port Alarm buzzer EV3 HP Built in EVD HP Not available EV3K01 Built in ...

Page 50: ...________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________________ _______________________________________________________________________________...

Page 51: ...document is the sole property of EVCO EVCO does not accept any liability for any possible errors it includes The customer builder installer or end user assumes all responsibility for the configuration of the device EVCO may not be held liable for any damage caused by failure to follow the instructions EVCO reserves the right to make any modifications without prejudicing the essential functional an...

Page 52: ...EVCO S p A EV3 HP EVD HP Installer manual ver 1 2 Code 1443DHPE124 page 52 of 52 EVCO S p A Via Feltre 81 32036 Sedico Belluno ITALY Tel 0437 8422 Fax 0437 83648 info evco it www evco it ...