1143W24E4.00 · EV3 200 Web
03/2021
| 41 |
Par. Description
MU
Range
Default
r12
Differential position r0.
0
=Asymmetrical;
1 = Symmetrical.
---
0/1
0
COMPRESSOR Group
C0 Compressor ON delay from power-on.
min
0...240
0
C2
MinimumcompressorOFFtime.
min
0...240
3
C3 Minimum compressor ON time.
s
0...240
0
C4
CompressorOFFtimeincabinetprobealarm.
min
0...240
10
C5 Compressor ON time in cabinet probe alarm.
min
0...240
10
C6 Condensation temperature above which the condenser overheat alarm sounds.
°C/°F
0.0...199
80.0
C7
Condensertemperatureabovewhichthecompressorlockedalarmsounds,once
C8 time
has elapsed.
°C/°F
0.0...199
90.0
C8
Delayinactivationofcompressorlockedalarmduetothreshold
C7 being exceeded.
min
0...15
1
C10 Compressor hours for maintenance. 0 = Disabled.
h
0...999*100
0
C11 Second compressor switch-on delay from first compressor switch-on.
s
0...240
10
C13 Number of start-ups per compressor rotation. 0 = Disabled.
num
0...10
0
DEFROST Group
d0 Defrost interval. 0 = Manual defrost only. If d8
=3,maximuminterval.
h
0...99
8
d1
Type of defrost.
0 = Electrical heaters;
1 = Cycle reversed (hot gas);
2 = When compressor stops.
---
0...2
0
d2 Evaporation temperature above which defrost with evaporator probe terminates (Pr3 = 5).
°C/°F
-99.0...99.0
8.0
d3 Defrost duration. If P3
=1,maximumduration.
min
0...99
30
d4
Enable defrost when device is switched on.
0 = Disabled;
1 = Enabled.
---
0/1
0
d5 Defrost activation delay from power-on.
min
0...99
0
d6
Value displayed during defrost.
0 = Regulation;
1
=Lockeddisplay;
2
=Code"
DEF
".
---
0...2
1
d7 Evaporator dripping time after defrost.
min
0...15
0
d8
Defrost interval count mode.
0 = Hours device ON;
1 = Hours compressor ON;
2 = Hours evaporator temperature < d9;
3
=Adaptive;
4 = In real time (RTC).
---
0...4
0
d9 Evaporation threshold for automatic defrost interval count.
°C/°F
-99.0...99.0
0.0
d11
Enable defrost terminated warning due to maximum duration (code dFd).
0 = No; 1 = Yes.
---
0/1
0
d15 Compressor ON time before hot gas defrost.
min
0...99
0
d16 Pre-dripping time for hot gas defrost.
min
0...99
0
d18
Adaptivedefrostinterval.
0 = Manual defrost only.
min
0...999
40
d19
Adaptivedefrostthreshold(relativetooptimalevaporationtemperature).
°C/°F
0.0...40.0
3.0
d20 Compressor-on consecutive time for defrost.
min
0...999
180
d21 Compressor-on consecutive time for defrost from power-on and from over-cooling.
min
0...500
200
d22
Evaporation threshold for adaptive defrost interval count (relative to optimal evaporation
temperature).
°C/°F
-10.0...10.0
-2.0
ALARM Group
AA
Select value for high/low temperature alarms
0 = Regulation temperature;
1 = Evaporator temperature;
2 = Probe Pb3 temperature.
---
0...2
0
A1
Lowtemperaturealarmthreshold.
°C/°F
-99.0...99.0
-10.0