6.1.2. Configuring a blind programmable controller
The following procedures show an example of configuration of a blind programmable controller through a built-in programmable
controller (in the example it is c-pro 3 kilo) and through its user interface.
It is also possible to configure the controller using an user interface; look at paragraph 6.3 “Configuring a device through an
user interface”.
Operate as follows:
1.
Switch off the power supply of the controllers.
2.
Connect the blind controller to the built-in controller through the CAN port; look at chapter 4 “ELECTRICAL CONNECTION”.
3.
Switch on the power supply of the controllers.
4.
Keep pressed 2 s buttons UP and DOWN: the display will show the following menu.
<CPro 3 Kilo LCD>
Info
English
Parameters
...
Backup / Restore
Diagnostic
Debug
5.
Press and release button UP or button DOWN to select “Networks”.
6.
Press and release button ENTER.
7.
Press and release button ENTER again to set the password value.
8.
Press and release button DOWN over and over again to set “-19”.
9.
Press and release button ENTER again.
10.
Press and release button UP or button DOWN to select “CAN Bus”.
11.
Press and release button ENTER again.
12.
Set parameter NetworkNode using button UP or button DOWN to select the parameter and using button ENTER to modify
and to confirm the value.
According to the factory setting the address of the CAN node of a programmable controller has value 1 (therefore operate on
the controller to set parameter NetworkNode to [ 1 ] 1).
13.
Press and release button UP or button DOWN to select “>”.
14.
Press and release button ENTER again: the display will show the Main menu of the blind controller.
15.
Operate as shown in paragraph 6.1.1 “Configuring a built-in programmable controller”.