TECHNICAL SPECIFICATIONS
Purpose of the control device
Function controller
Construction of the control device
Built-in electronic device
Housing
Grey, self-extinguishing
Category of heat and fire resistance
D
Measurements
10 DIN modules: 179.0 x 110.0 x 26.0 mm (7 1/16 x 1 5/16 x 1 in) for open
frame models
10 DIN modules: 179.0 x 128.0 x 60.0 mm (7 1/16 x 1 1/16 x 1 3/16 in) for
models with housing
Mounting methods for the control device
On a DIN rail in a control panel
Degree of protection provided by the casing
IP00 open frame models
IP40 front of models with housing
Connection method
Fixed screw terminal blocks for wires up to 1.5 mm²
and 2.5 mm² for open frame models
Plug-in screw terminal blocks for wires up to 1.5 mm²
and 2.5 mm² for models with housing
Plug-in clamp terminal blocks for wires up to 1.5 mm²
for plus controllers
Pico-Blade connector
Micro-USB connector
RJ45 F telephone connector (depending on model)
Maximum permitted length for connection cables
Power supply: 10 m (32.8 ft)
Analogue inputs: 10 m (32.8 ft)
Auxiliary power supply and 0-5 V ratiometric transducer power supply: 10 m
(32.8 ft)
Digital inputs: 10 m (32.8 ft)
Unipolar stepper electronic expansion valves driver: 3 m (9.84 ft)
Analogue outputs 0-10 V: 10 m (32.8 ft)
PWM analogue outputs: 1 m (3.28 ft)
Digital outputs: 100 m (328 ft)
INTRABUS port: 10 m (32.8 ft)
RS-485 MODBUS port: 1,000 m (3,280 ft)
USB port: 1 m (3.28 ft)
CAN port:
- 1,000 m (3,280 ft), baud rate: 20,000 baud
- 500 m (1,640 ft), baud rate: 50,000 baud
- 250 m (820 ft), baud rate: 125,000 baud
- 50 m (164 ft), baud rate: 500,000 baud
Operating temperature
From -10 to 55 °C (from 14 to 131 °F)
Storage temperature
From -20 to 70 °C (from -4 to 158 °F)
Operating humidity
Relative humidity without condensate from 5 to 95 %
Pollution status of the control device
2
Compliance
RoHS 2011/65/EC
WEEE 2012/19/EU
REACH (EC) Regulation no. 1907/2006
EMC 2014/30/EU
LVD 2014/35/EU
Power supply
115... 230 VAC (+10 % -15 %), 50/60 Hz (±3 Hz), max. 16 VA, 20 VA for plus controllers, 27 VA for U-EEV
controllers
Earthing methods for the control device
None
Rated impulse-withstand voltage
2.5 KV
Over-voltage category
II
Software class and structure
A
Clock
With secondary lithium battery
Clock drift
≤ 30 s/month at 25 °C (77 °F)
Clock battery autonomy in the absence of a power
supply
> 6 months at 25 °C (77 °F)