![EVAPCO eco-Air Series User Manual Download Page 24](http://html1.mh-extra.com/html/evapco/eco-air-series/eco-air-series_user-manual_2441638024.webp)
24
Controller User Manual
The Fan Speed/Temperature Screen shown in Figure 31 determines the various speeds at which the eco-Air unit runs in various modes.
Note that the fan speeds are set in percentage of the fan motor’s nameplate speed. The energy saving speed is not active unless the
eco-Air unit is equipped with a precooling system. The energy saving fan speed allows the precooling system to activate one the fan
speed reaches the energy saving value. Once the precooling system is activated, the fan motors will continue to increase in speed if
the active setpoint is not met. The speed will continue to increase until the maximum allowed fan speed is met. To disable the energy
saving functionality, set the energy saving fan speed to the maximum allowed fan speed.
The quiet operation fan speed limits the speed of the fan motors whenever the Quiet Mode is activated. Quite Mode may be activated
via the scheduler or a digital input. If the quiet mode fan speed is less than the energy saving fan speed, the precooling system will
be prevented from operating. See Figure 7 for setup information.
When cooling is not required and the fan speed settles to the minimum allowed fan speed, the fans will turn off based on the shutoff
timer and offset.
Fan speed and temperature setpoints
Parameter
Description
Default
Max. Allowed
The maximum speed that the fan motors will reach when
Quiet Mode is not active.
100%
Quiet Operation
The maximum fan motor speed allowed when Quiet Mode
is activated via the scheduler or digital input.
100%
Energy Saving
The fan speed at which the pre-cooling system will
activate.
100%
Min. Allowed
The minimum speed at which the fan motors will spin.
20% (NEMA Motors)
10%(EC Type Fans)
Min. Shutoff Timer
The amount of time that must elapse whenever the fan
speed reaches the minimum allowed percentage before
the fans are turned off.
30 seconds
Min. Shutoff Offset
The temperature offset below the setpoint before the fans
are turned off.
2.0 °F
Table 12
The parameters of the Fan Speeds Screen.
Figure 31
Summary of Contents for eco-Air Series