IPCN11,5
REAR WALL B =
50 mm
SIDE WALL A =
100 mm
THICKNESS INSULATING MATERIAL C, E =
40 mm
FLOOR D =
- mm
FRONT R =
1000 mm
It is in any case advisable, as well as respecting minimum distances, to
install the fireproof heat-resistant insulating panels (mineral wool, aerated
concrete, etc.).
The following is recommend:
Promasil 1000
Classification temperature: 1000 °C
Density: 245 kg/m
3
Shrinkage at reference temperature, 12 h: 1.3/1000°C %
Cold crushing strength: 1.4 MPa
Bending strength: 0.5 MPa
Reversible thermal expansion: 5.4x10
-6
m/mK
EXAMPLES OF INSTALLATION:
EXAMPLES OF INCORRECT
INSTALLATION:
Exhaust pipes must never be fitted pointing downwards or horizontally so that fumes are discharged directly through the external wall.
Specific heat capacity: 1.03 kJ/kg K
Thermal conductivity λ:
200 °C
0.07 W/mK
400 °C
0.10 W/mK
600 °C
0.14 W/mK
800 °C
0.17 W/mK
Thickness: 40 mm
English - 11