Specifications
For assembly:
• tilt the module approximately 20 degrees forwards in relation to the horizontal
• insert the rotation rod in the baseplate recipient (see fig. 2.1)
• raise the module to the horizontal
• turn the lock by a quarter-turn.
The minimum space between 2 modules side by side must be at least 20 mm.
If the modules are mounted on top of each other, it is essential to leave a vertical space of at
least 80 mm between 2 modules, in order to guarantee good ventilation.
For installations in fan-cooled cabinets, it is recommended to fit a fan failure detection device.
For disassembly:
• unlock the top attachment by a quarter-turn
• tilt the module approximately 20 degrees forwards in relation to the horizontal
• release the module from its baseplate.
Warning
Before disassembling the module, make
sure that the heatsink is not hot.