Issue 1,    Apr-98     Applies to software version 1.0

         -

4

-                      

                             

HA026277

The 

05/ (Promote) option

Up to twelve commonly used parameters can be ‘promoted’ into
the  HOME list.  This will give the operator quick access to them

by simply pressing the 

  button.  This feature, used in

combination with ‘hide’ and ‘read only’, allows you to organise
the way in which you want your indicator formatted.

Select EDIT level to hide, reveal or promote parameters as below:

The parameter 

  ) will now appear in the HOME list.  Repeat

the procedure for any other parameters you wish to promote.
To de-promote a parameter go to 

O6 level, select the parameter

from the relevant list and change the choice from 

05/ back to

)65, 5 or #O.

Returning to Operator level
Repeat the above procedure for all the parameters you wish to hide,
promote, or make read-only then return to operator level:

Your indicator has been calibrated for life against known reference
sources in the factory.  User calibration allows you to apply offsets
to compensate for sensor and other system errors. You can apply a
simple fixed offset over the whole display range using the
parameter 

 in the O0 list, or alternatively, you may apply a 2-

point calibration as follows:

• 

Press 

 until you reach the 

O0 list

• 

Press 

 until you reach the 

)D0 parameter

• 

Press 

 or 

  to enter the password.  The factory default

password is 3.  

0 will be displayed when correct.

• 

Press 

 to reach the 

) parameter

• 

Press 

 or 

  to select 

85 (6 will restore the

factory calibration)

• 

Press 

 to select 

0.6D)

• 

Press 

 or 

 to adjust the value at which you wish to

apply the low calibration point offset. (eg zero)

• 

Press 

 to select 

D)

• 

Press 

 or 

 to set the low calibration point offset.

• 

Repeat the above to select and adjust 

0.6D# and D#

The graph below shows the effect of a low and high point offset.

These warn that a fault exists in either the indicator or the
connected devices.

Alarm

What it means

What to do about it

EE.Er

Electrically Erasable
Memory Error:  The
value of an operator
or configuration
parameter has been
corrupted.

This fault will automatically
take you into configuration
level.  Check all of the
configuration parameters
before returning to operator
level.  Once in operator level,
check all of the operator
parameters before resuming
normal operation.  If the fault
persists or occurs frequently,
contact Eurotherm Controls.

S.br

Sensor Break:  Input
sensor is open
circuit.

Check that the sensor is
correctly connected.

LLLL

Out of range low
reading

Check the value of the input

HHHH

Out of range high
reading

Check the value of the input

Err1

Error 1: ROM self-
test fail

Return the indicator for  repair

Err2

Error 2: RAM self-
test fail

Return the indicator for  repair

Err3

Error 3: Watchdog
fail

Return the indicator for  repair

Err4

Error 4: Keyboard
failure    Stuck
button, or a button
was pressed during
power up.

Switch the power off and then
on without touching any of the
indicator buttons.

Value at which you
wish to apply the
offset

Display Offset

Applied

Factory calibration

0.6D#

D#

D)

0.6D)

User calibration

High alarm 2 has been selected.

When 

 

or

 

 is pressed, instead of displaying

the parameter value, its availability in Operator
level is shown as follows:
)65

The parameter will be alterable

#O

The parameter will be hidden.

5

The parameter will be read-only

05/

The parameter will be ‘promoted’
into the HOME list (see below).

1. Press 

 

 until you reach the 

 list

heading

2. Press 

 

 until you reach 

!/6/

3. Press 

 or 

  to select 

15

4. Press 

 to return to Operator level

0

/

Press  

 or 

 to enter the password.  The

factory default password is 1.  ‘

0’ will be

displayed momentarily when the correct
password has been entered.

  Press

Press 

 until the Access List Heading is reached.

You are now in Edit level.

Press 

 and 

  to select a parameter in

the normal way.
If no button is pressed for 45 secs the
display returns to operator level.

  Press to return to the Access list header.

Press

 

 

or

 

 

to select

 ‘

O6

 level.

Other options are:

05

Operator level - shows selected 
parameters

9))

Reveals the ‘FULL’ set of parameters

/.

Gives access to configuration level.

(see CONFIGURING THE INDICATOR)

O6

!/6/

  Press

Edit Level Example:

#O

#

05

!/6/

Low alarm 1 has been selected

Press 

 or 

  to choose 

05/.

Promote Level Example:

05/

 )

T

H

IDE

, R

EVEAL AND 

P

ROMOTE 

P

ARAMETERS

U

SER 

C

ALIBRATION

D

IAGNOSTIC 

A

LARMS

Summary of Contents for 2108i

Page 1: ... 5 in DIMENSIONS AND INSTALLATION Relay Ratings 2A 264Vac resistive Wire Sizes The screw terminals accept wire sizes from 0 5 to 1 5 mm 16 to 22 AWG Hinged covers prevent hands or metal making accidental contact with live wires The rear terminals screws should be tightened to 0 4Nm 3 5lb in ELECTRICAL CONNECTIONS Alarm acknowledge reset Pt100 Providing outputs for machine and product protection A ...

Page 2: ... will always return to the HOME display When shipped from the factory the HOME display will by default show the measured temperature or PV You can select alternative HOME displays as follows Quickly press twice To prevent an Operator changing this option see TO HIDE REVEAL AND PROMOTE PARAMETERS Page 4 The button steps through parameter list headings as shown on page 3 The first list is the alarm ...

Page 3: ... measured at the rear terminals Read only Read only mV input measured at the rear terminals Read only Read only PV offset Customer set fixed calibration offset which applies over the whole display range B to display units D0 Calibration password See USER CALIBRATION to Calibration type 6 Restores Factory calibration 8 5 User calibration applies 6 0 6D Low calibration point These parameters B to di...

Page 4: ...will automatically take you into configuration level Check all of the configuration parameters before returning to operator level Once in operator level check all of the operator parameters before resuming normal operation If the fault persists or occurs frequently contact Eurotherm Controls S br Sensor Break Input sensor is open circuit Check that the sensor is correctly connected LLLL Out of ran...

Page 5: ...tic 96 CJC does not appear for J 0 C external reference or 57 inputs For see J 45 C external reference Linear input scaling on page 6 J 50 C external reference N 0 Sensor break input impedance No sensor break linear inputs only 96 threshold 96 1 5KΩ If the sensor input exceeds O 5KΩ this value the sensor break O O 15KΩ alarm will be activated Continued on the next page N 6 6 Use or to select Press...

Page 6: ... Automatic resetting means that once the alarm has been acknowledged it will automatically clear when it is no longer true 2 Manual resetting means that the alarm must first clear before it can be reset 3 In blocking mode after power on the process value must first enter a good state before the alarm becomes active This is particularly useful for low alarms which can be blocked while the process i...

Page 7: ... Fitted unconfigured Un latched alarms FH High alarm 1 FL Low alarm 1 AL High alarm 1 low alarm 3 RA Rate of change alarm 1 Latched alarms HA High alarm 1 LA Low alarm 1 RT Rate of change alarm 1 AA High alarm 1 low alarm 3 NW New alarm status Relay Output 2 XX Not fitted RF Fitted unconfigured Un latched alarms FH High alarm 2 FL Low alarm 2 RA Rate of change alarm 2 Latched alarms HA High alarm ...

Page 8: ...nductive pollution Electrically conductive pollution must be excluded from the cabinet in which the indicator is mounted For example carbon dust is a form of electrically conductive pollution Where condensation is likely for example at low temperatures include a thermostatically controlled heater in the cabinet Installation requirements for EMC For general guidance refer to Eurotherm Controls EMC ...