1.

 

Device description 

Limit switch boxes serve to provide feedback and control the position of industrial valves, which are activated using pneumatic actuators. 
The shaft of the limit switch box has a positive connection with the shaft of the actuator and is rotated with the rotational movement of the 
actuator. The actuating cams attached to the shaft, activate the installed sensors, which support the electronic signal transmission. 
The flex Ex eb ia limit switch boxes are equipped with 1 to 4 Ex ia certified intrinsically safe proximity switches. That includes 1-4 inductive 
proximity V3-sensors, 1-3 slot type sensors, 1-2 cylindrical sensors or 1 dual sensor. 

2.

 

Intended use 

The flex Ex e ia limit switch box from the EUROTEC Antriebszubehör GmbH is intended for use in the explosive area of zones 1 and 2 with 
gases, mists or vapours and zone 21 and 22 with combustible dust. 
 

ATEX / IECEx 

EAC Ex (TR-CU-012) 

  II 2G Ex eb ia IIC/IIB T4-T6 Gb 

1 Ex e ia IIC <<T6…T4>> Gb X 

 II 2D Ex tb IIIC T80°C-T135°C Db 

Ex tb IIC T80°C/T95°C/T130°C Db X 

EPS 16 ATEX 1012 X / IECEx EPS 16.0006 X 

 

 
Its approved for use in the following ambient temperature ranges: 
T6/T80°C:  

-55°C/-25°C...+40°C 

T5/T95°C:  

-55°C/-25°C...+60°C 

T4/T135°C: -55°C/-25°C...+75°C 
 
The approved ambient temperature varies, depending on the sealing compound and the installed switch type. You can find the ambient 
temperature in the corresponding data sheet and on the product label. For the use to a minimum ambient temperature of -25°C the limit 
switch boxes type EFX can also be fitted with a viewing glass in the cover housing.  A lower temperature range down to -55°C applies to limit 
switch boxes, which are made of components, that are at least suitable for this temperature. 
 
The electrical input ratings are determined by the separately certified intrinsically safe inductive sensors that are used. You will find the 
values for Ui, Ii, Pi, Ci and Li on the product label of your limit switch box as well as in the instruction manual of the sensor. 

3.

 

Labeling 

The labeling on the housing is shown in Fig. 1 and varies depending on the installed switch type. You can find the number of the indicated 
responsible office for the QM system and the serial number below the CE mark. It consists of the year of manufacture and the respective 
order number. 

 

         Fig. 1: Labeling 
 
 

 

The housings are not intended to be used as stepladders, to climb into the system. This can lead to damaging 
them and having a negative effect on their function. If the housing is damaged, water as well as dirt and 
combustible material can accumulate inside the housing. This can lead to a short circuit. Furthermore, the 
device can heat up severely due to the accumulation and can cause an explosion.

 

 