Exceeding  the  feeding  alarm  temperature  activates  the  alarm  algorithm  
to  attempt  to  cool  down  the  boiler.  The  heating  zone  is  heated  up  to  the  alarm 
temperature of the zone. 

 

Correction of sensors 

Correction  of  temperature  sensors  allows  to  correct  temperature  reading  errors, 
such  as  the  ones  resulting  from  improper  contact  between  the  sensor  and  the 
pipe. 

9. CONTROLLER OPERATION 

The  temperature  of  the  heating  zone  is  adjusted  with  the  PI  algorithm  (proportional-
integral algorithm), which enables obtaining fast and accurate control for different loads. 
The  controller  controls  the  temperatures  of  the  boiler  and  the  controlled  zone. 
Periodically, it calculates the difference between the preset and measured temperature.  
If the difference exceeds half of the hysteresis value, then the mixer position is corrected 
with  the  speed  determined  by  "Dynamics"  parameter.  If  the  mixer  was  switched  on  to 
operate at the same direction by at least 100 s, the controller switches the valve actuator 
permanently to set it in the limit position.  
The CH pump is switched on if the temperature of the feeding sensor exceeds the value 

of  the  "Shutdown  temperature"  parameter  by  2°C,  and  it  is  switched  off  if  the 

temperature of the feeding sensor drops below the shutdown temperature. 

The heating zone is switched off if: 

 

The heating season (WINTER) is switched on. 

 

The current time is selected in the schedule. 

 

The room thermostat is active or operation with room thermostat is switched off. 

 

Automatic  operation  is  switched  off  or  the  mean  outdoor  temperature  is  lower 
than the switch-off temperature in the case of switched on automatic operation.  

 

The  feeding  temperature  is  higher  than  required  or  the  feeding  temperature 
sensor is switched off. 

CAUTION!

 The temperature preset for a heating zone is not displayed if: 

 

The feeding sensor temperature is lower than the shutdown temperature. 

 

The  room thermostat  reached the preset temperature and switched  off the zone 
(pump operation switched off). 

 

There is a stoppage set up in an operation schedule. 

 

The zone was switched off automatically (it is warm outside). 

10. ANTI-STOP SYSTEM 

Anti-Stop system activates the pump and the mixing valve directly upon each switch-on 
of the controller (also upon restoring factory settings), and later 

 every 10 days. During 

its operation, "AT" letters flash at the display.  
If an alarm situation (overheating or sensor damage) occurs when the Anti-Stop system 
is active, the operation of the Anti-Stop system will be ceased. 

11. ALARM SITUATIONS 

To  ensure  safe  and  reliable  operation,  the  controller  features  a  number  of  protections. 
The list of alarm events is shown in the table below. In case an alarm situation occurs, 
audible  alarm  is  generated,  and  a  relevant  message  is  displayed.  Upon  resolution  
of the alarm situation, the controller automatically resumes operation.  

Alarm 

Message 

Controller response

 

Feeding sensor 
shorted 

ALARM: FEEDING 
shortage 

Activation of an audible alarm. CH 
temperature operated up to the preset 
temperature.

 

Breach of the feeding ALARM: FEEDING 

Activation of an audible alarm. CH 
temperature operated up to the preset 

Summary of Contents for 12M

Page 1: ...ather based setting of a heating zone preset temperature Weekly operating schedule Cooperation with a room thermostat Switching the heating off automatically in case of external temperature increase F...

Page 2: ...es Indicates opening of the mixer Indicates closing of the mixer The symbol is displayed if the mixer is neither being opened nor being closed e g within the hysteresis or during gaps between turning...

Page 3: ...be installed in a place where the temperature does not exceed 40 C CAUTION Do not immerse the temperature sensors in liquids nor install them at flue gas outlets to the stack INSTALLING TEMPERATURE SE...

Page 4: ...cores of a 5 m long cable to the connection on the board keeping cable polarization is not necessary Fix the cable in the housing Place the cover and tighten it with two screws Mount the temperature s...

Page 5: ...f hour If the operating times of heating zone are selected the pump and the mixer operate automatically In the situation when the hourly operating schedule is not selected lack of heat demand the pump...

Page 6: ...lculates the currently required heating zone temperature Caution Temperatures must meet the condition of T10 C T0 C T 20 C otherwise the control will not work properly Room thermostat Enables switchin...

Page 7: ...with room thermostat is switched off Automatic operation is switched off or the mean outdoor temperature is lower than the switch off temperature in the case of switched on automatic operation The fee...

Page 8: ...m Pump switch off Outdoor temperature sensor shortage ALARM WEATHER shortage Activation of an audible alarm The controller operates with the temperature preset for 20 C Outdoor temperature sensor brea...

Page 9: ...KACZY SKA hereby declares that the type of EUROSTER 12M equipment conforms to the following directives 2014 35 EU LVD 2014 30 EU EMC 2011 65 EU RoHS The complete text of the Declaration of EU conformi...

Page 10: ...t The attitudes influencing protection of the common good of clean environment are shaped at this level Households are also one of the larger users of small equipment and its rational management at th...

Page 11: ...exclusively by the manufacturer or by other party clearly authorized by the manufacturer 5 Warranty becomes invalidated in case of any mechanical damage incorrect operation and or making any repairs b...

Reviews: