Instruction Manual ZHK
76/140
V07-21.0
4. Fixing of the clamps
-
Tighten the clamps using a torque wrench. Fix the screw with a torque of 5/ 6,5 Nm.
Figure 171:
Mounted clamps
5. Installation of threaded strut
The threaded strut is mounted on the pressured side and holds the pressure side tube in position,
in order to relieve the pressure side flexible tube connection from axial forces. The strut needs to
be fixed near to the vertical tube coming from the pump pressure side as shown in
For installing the threaded strut, the following parts are needed (included in the scope of supply by
EUROCLIMA),
1. Clamp for threaded strut
2. Threaded strut (M10)
3. Base support for strut
Figure 172:
Position and parts for installing the strut
To install the threaded strut, proceed as follows:
-
Fix the clamp for the strut at the upper horizontal tube near to the vertical pump coming from
the pump.
-
The base support shall be installed vertically under the upper clamp. (For spray humidifier
equipped with UV water treatment, a small discrepancy may be possible.)
-
Cut the threaded rod to the required length and fix the rod accordingly. (For spray humidifier
equipped with UV water treatment, the rod may be bent to pass the UV circuit tubes).
-
Tighten the lower nut and the counter nut in order to fix down slightly the tube assembly.
In the event of problems or needing support with your product, do not hesitate to contact EURO-
CLIMA for any further clarification or support.