Instruction Manual ZHK
120/140
V07-21.0
9.6 UV section
The UV section has to be checked and cleaned regularly. Broken lamps must be replaced before
the next commissioning. Avoid direct contact with the lamps.
9.7 Dampers
EUROCLIMA dampers of Type J are nearly maintenance free. Check for dirt, damage and corro-
sion, clean if necessary with compressed air or steam jet. Check the function and correct rotation.
Spray the wheels with silicone spray if necessary.
Warning!
Gears cannot be treated with organic oils! Check linkages are functioning, tighten the screws if
necessary.
9.8 Sound attenuators
Acoustic baffles are basically maintenance-free. However, they must be checked for damage
within major maintenance work and shall be replaced or properly repaired, if required.
9.9 Weather louver
Check for dirt, damage and corrosion and that it is free from leaves, paper, etc.
9.10 Energy recovery systems
The manual of the component manufacturer must be read and followed when undertaking cleaning
works.
9.10.1 Plate heat exchangers
Plate heat exchangers are made of highly corrosion-resistant high-grade aluminum and have no
drive or moving parts. The lifetime is nearly unlimited, as long as the differential pressure between
the plates does not exceed the maximum allowed and operating instructions are followed.
The only maintenance required is cleaning:
-
Clean the condensate drain, inspect and fill the U-trap. The plate pack is normally self-clean-
ing.
o
Remove fibers and dust at the exchanger inlet with a brush.
o
Clean oils and fats with hot water, household cleaners or degreasing steam.
-
Check for proper operation of the differential pressure switch
–
for function refer to
chapter 7.7
Differential pressure restriction for plate heat exchangers
).
-
If there is a bypass damper, please refer to
chapter 9.7 (Dampers)
.
NOTICE!
Attention!
Heat exchanger must not be damaged mechanically or chemically through clean-
ing.
Summary of Contents for ZHK