Instruction Manual ZHK
V07-19.0
81/129
Cable type for motor connection
The motor can be powered directly or via a frequency converter. A shielded cable must be used for
the motor cable and the shield must be grounded on both ends (frequency converter / main switch
& motor).
Correct direction of motor rotation is a result of direction of fan impeller rotation which is marked by
an arrow: for EC fan refer to
, for plug fan refer to
, for fan with housing refer
Before connecting the motor check the rotating field of mains connection with a suitable device. Af-
terwards, connect the phases accordingly to motor terminal or main switch (if supplied and wired
by EUROCLIMA).
Figure 177:
Rotation marking of
plug fans
Figure 178:
Rotation marking of
housing fans
Figure 179:
Rotation marking of EC fans
Fastening torque for electrical connections on the control panel refer to
Thread
Ø
M4 M5 M6
Nm
min. 0,8 1,8 2,7
max. 1,2 2,5 4
Table 7:
Torques for the motor terminal board
Before connecting to the local power network, check that the local power supply
coincides with the motor requirements from the nameplate. In general the fan
motors are designed for continuous operation. Abnormal operating conditions,
particularly multiple start-ups at short intervals should be avoided, it could lead to
thermal overloading of the motor.