27
5.4.3.
Timer Setting
(
1hour-24hours
)
:
The timer has two ways of operation:
To turn off
(When power on)
To turn on
(When power off)
Cancel timer
5.4.4.
Automatic Defrost
At low room temperatures, frost may buildup at the evaporator during operation.
The unit will automatically start defrosting and the
POWER
LED blinking. The
defrost control sequence is as follows:
A.
When the unit operates in the cooling (cool in smart mode), dehumidifying
operating mode, the ambient temperature sensor senses the evaporator coil
temperature is below -1°C , the compressor will stop operating. 10 minutes later
(or the coil temperature up to 7
℃
) the unit restart to cool operating mode.
B.
When the unit operates in the dehumidifying operating mode, When the coil
temperature sensor senses the temperature of the evaporator is below 40
℃
and
the differential between coil temperature and room temperature is below 19
℃
after the compressor operation for 20minutes, the unit start defrosting for 5
Press
Timer
key to
turn on the timer
function.
Press
Timer
key to
turn on the timer
function.
Press
ADD/MINUS
repeatedly to set the
delay OFF time
Press
ADD/MINUS
repeatedly to set the
delay ON time.
Press
ADD/MINUES
repeatedly until the LED shows ‘00’.
Note: when press
POWER
will also exit the timer setting.