Eureka Opal SRS4 Operation & Installation Instructions Download Page 6

Opal SRS4 Insert

 6

Opal SRS4 Insert

 7

Installation

(Continued)

530

Minimum hearth sizes

A             B            C              D

1100     1040         50            250

Mantel Clearances

890

12

Vent 

Breast plate no

thicker than

30mm

C (appliance to

mantel upright)

Hearth Depth

D (max)

B

A

Step 2

Figure 4. ZCC Installation Step 2

Depth

Width

Thickness

Elevated installation 

In some instances it may be desirable or required that the Eureka Opal  

Insert  

woodheater be installed  

onto a 

step of an existing fireplace or mid-wall inside a Gason ZCB. In either of these situations, a step or structure must 

be constructed of non-combustible material and withstand the combined weight of the appliance and ZCB. 

The following table represents the relationship between the height at which the appliance can be raised, and 

minimum required hearth depth from the front of the appliances fascia panel, to front of hearth.  

i.e. if the appliance is raised by 120mm above hearth/existing floor, the hearth can reduce from 530mm to 375mm 
in front of the appliances fascia. 

Minimum

Appliance

Hearth Depth

raised by

X

Y

890mm

Table 1. Appliance height 

vs hearth requirements

X

Y

When appliance is raised 155mm or more above floor level, a 300mm non-combustible hearth or floor protector is 

always required as per AS/NZS 2018:2001.  

If the appliance is installed onto an existing step/fireplace which projects in front of the appliance’s fascia less than 

required (corresponding height of step/fireplace to floor), an additional hearth or floor protector will be required 

to extend to the minimum required hearth depth required for the step height. 

i.e. An appliance is installed onto an existing step/fireplace 105mm above a wooden floor. The existing 

step/fireplace projects 250mm in-front of the appliance’s fascia. Using Table 1, the closest minimum height related 

to 105mm is 103mm and its reflective hearth requirement of 400mm. For this installation to conform with AS/NZS 

2918:2001, 150mm of villaboard (or similar non-combustible material) must extend in-front of step/fireplace of 

minimum width 890mm and thickness 12mm. 

 

Installation

(Continued)

Plaster, timber, MDF etc.

combustible material can

be used on sides of framing

530 
525 
500 
475 
450 
425 
400 
375 
350 
325 
300 
300 


30 
50 
70 
87 

103 
118 
132 
144 
155 

≥155 