15
2121331-04-04/19 (Translation of the original operating instructions)
Operating Instructions
Modular Safety Control System MSC
EN
5.3.1. Information in relation to connecting cables
NOTICE
Ì
Connection cross-section range: AWG 12 – 30, (single conductor/multiple conductor) (UL).
Ì
Only use copper wires (Cu) for 60/75 °C.
Ì
It is recommended to use separate power supplies for the safety module and for other electrically
powered devices (electric motors, inverters, frequency converters) or other sources of interfer-
ence.
Ì
Cables for connections with a length of more than 50 m must have a cross-section of at least
1 mm
2
(AWG16).
5.3.1.1. Base unit MSC-CB
The connections for each module in the MSC system are listed in the table below:
TERMINAL
SIGNAL
TYPE
DESCRIPTION
VERSION
1
24 VDC
-
Power supply 24 VDC
-
2
MASTER_ENABLE1
Input
Base unit enable 1
Input (
"type B"
as per EN 61131-2)
3
MASTER_ENABLE2
Input
Base unit enable 2
Input (
"type B"
as per EN 61131-2)
4
GND
-
Power supply 0 VDC
-
5
OSSD1_A
Output
Safety output 1
PNP active high
6
OSSD1_B
Output
PNP active high
7
RESTART_FBK1
Input
Feedback loop/restart 1
Input as per EN 61131-2
8
OUT_STATUS1
Output
Programmable digital output
PNP active high
9
OSSD2_A
Output
Safety output 2
PNP active high
10
OSSD2_B
Output
PNP active high
11
RESTART_FBK2
Input
Feedback loop/restart 2
Input as per EN 61131-2
12
OUT_STATUS2
Output
Programmable digital output
PNP active high
13
OUT_TEST1
Output
Output for short circuit detection
PNP active high
14
OUT_TEST2
Output
Output for short circuit detection
PNP active high
15
OUT_TEST3
Output
Output for short circuit detection
PNP active high
16
OUT_TEST4
Output
Output for short circuit detection
PNP active high
17
INPUT1
Input
Digital input 1
Input as per EN 61131-2
18
INPUT2
Input
Digital input 2
Input as per EN 61131-2
19
INPUT3
Input
Digital input 3
Input as per EN 61131-2
20
INPUT4
Input
Digital input 4
Input as per EN 61131-2
21
INPUT5
Input
Digital input 5
Input as per EN 61131-2
22
INPUT6
Input
Digital input 6
Input as per EN 61131-2
23
INPUT7
Input
Digital input 7
Input as per EN 61131-2
24
INPUT8
Input
Digital input 8
Input as per EN 61131-2
Table 2: Base unit MSC-CB