
25
2126330-10-03/21 (translation of the original operating instructions)
Operating Instructions Safety Systems
MGB-L..B-EI-… (Ethernet/IP) and With Data Structure Type A
EN
14.4. Electrical function test
1. Switch the operating voltage on or perform a reset via output bit
Q.PF
in the data block of the diagnostic function.
2. Close all guards and insert the bolt tongue into the locking module.
In case of guard locking by solenoid force
¨
activate guard locking.
Ì
The machine must not start automatically.
Ì
It must not be possible to open the guard.
Ì
The following applies to MGB-L0
: The green LED (State) is illuminated.
Ì
The following applies to MGB-L1/2
: The green LED (State) and the yellow LED (Lock) are illuminated.
3. Enable operation in the control system.
Ì
It must not be possible to deactivate guard locking as long as operation is enabled.
4. Disable operation in the control system and deactivate guard locking.
Ì
The guard must remain locked until there is no longer any risk of injury.
Ì
It must not be possible to start the machine as long as guard locking is deactivated.
Ì
It must be possible to open the guard.
Repeat steps 2-4 for each guard.
14.5. Ethernet/IP data bytes
The MGB system contains the following modules:
Ì
Bus module, MGB-B-…EI (includes everything required for Ethernet/IP connection)
Ì
Locking module, MGB-L. (forms the door locking mechanism together with the handle module)
Each MGB module occupies a certain number of data bytes in the input and output range of the control system.
The data bytes are combined into data blocks (see tables below).
A distinction is made between the following data types:
Ì
data for safe functions
Ì
data for non-safe functions
Important!
Safety bits and non-safe control bits are transmitted together via CIP Safety
®
. Only safety bits (
FI.x
and
FO.x
) may be used for safety functions
Inputs
Bit
7
6
5
4
3
2
1
0
Byte 0 = Connection Header
-
-
-
-
-
Diagnostic
Active
Connection
Faulted
RunMode
Byte 1 = Connection Header
DiagnosticSequenceCount
Byte 2 = Connection Header
-
-
-
-
-
-
-
-
Byte 3 = Connection Header
-
-
-
-
-
-
-
-
Byte 4 = Failsafe Inputs 0
FI.MS2
FI.MS1
FI.MS0
-
-
-
FI.EN
FI.ES
Byte 5 = Failsafe Inputs 1
FI.UK
FI.SK
-
-
-
FI.L
FI.B
FI.D
Byte 6 = Inputs 0
EN-S1
-
S92.2
S92.1
S91.2
S91.1
S90.2
S90.1
Byte 7 = Inputs 1
EN-S2
-
S95.2
S95.1
S94.2
S94.1
S93.2
S93.1
Byte 8 = Inputs 2
S4.2
S4.1
S3.2
S3.1
S2.2
S2.1
S1.2
S1.1
Byte 9 = Diagnostics
D.LT
-
D.OL
D.MS
D.EN
D.ES
D.PF
-
Bytes 10,11
FaultCode
Outputs
Bit
7
6
5
4
3
2
1
0
Byte 0 = Failsafe Outputs 0
-
-
-
-
-
-
-
FO.L
Byte 1 = Outputs 0
EN-H1
-
H95
H94
H93
H92
H91
H90
Byte 2 = Outputs 1
EN-H2
-
-
-
H4
H3
H2
H1
Byte 3 = Acknowledge
Q.PF
Q.G
-
-
ST4
ST3
ST2
ST1
Legend, see